Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 6 of 8

CompactLogix Controllers Specifications, pages 46 to 54

Pages 46 to 54 of 72

The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1769-IQ6X0W4

Page 46

CompactLogix Controllers Specifications

Figure 9 - Embedded Power Supply Temperature Derating Total Output: 29 W @ 60 °C (140 °F) or Below

0.8

2.0

1.5 +5V Bus Load (Amps)

60 °C (140 °F) 1.0

1.0

0.5 0.2 0.0 0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

+24V Bus Load (Amps)

Table 31 - Certifications - 1769 Packaged CompactLogix Controllers Certification(1)

1769-L23-QBFC1B, 1769-L23E-QB1B, 1769-L23E-QBFC1B c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1769-L23x Minimum Spacing Requirements 50 mm (2 in.)

50 mm (2 in.)

50 mm (2 in.) 50 mm (2 in.)

46

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 47

CompactLogix Controllers Specifications

1769-L23E-QB1B CompactLogix Dimensions 185.2 mm (7.29 in.)

132 mm (5.20 in.)

123.86 mm 118 mm (4.88 in.) (4.65 in.)

132.9 mm (5.23 in.)

18 mm (0.17 in.)

1769-L23E-QBFC1B CompactLogix Dimensions 249.5 mm (9.81 in.)

132 mm (5.20 in.)

123.86 mm 118 mm (4.88 in.) (4.65 in.)

98.47 mm (3.88 in.)

98.47 mm (3.88 in.)

18 mm (0.17 in.)

1769-L23-QBFC1B CompactLogix Dimensions 249.5 mm (9.81 in.)

123.86 mm 118 mm (4.88 in.) (4.65 in.)

132 mm (5.20 in.)

98.47 mm (3.88 in.)

98.47 mm (3.88 in.)

18 mm (0.17 in.)

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

47

Page 48

CompactLogix Controllers Specifications

1769 Modular CompactLogix Controllers

In a 1769-L3x controller system, the 1769 I/O modules can be placed to the left and the right of the power supply. As many as eight modules can be placed on each side of the power supply. Table 32 - Features - 1769 Modular CompactLogix Controllers Characteristic

1769-L31

1769-L32C

1769-L32E

1769-L35CR

1769-L35E

Available user memory

512 KB

750 KB

750 KB

1.5 MB

1.5 MB

CompactFlash card

1784-CF128

1784-CF128

1784-CF128

1784-CF128

1784-CF128

Communication ports

2 RS-232 ports (isolated DF1 or ASCII; only nonisolated DF1)

1 ControlNet port 1 RS-232 serial port (DF1 or ASCII)

1 EtherNet/IP port 1 RS-232 serial port (DF1 or ASCII)

1 ControlNet port 1 RS-232 serial port (DF1 or ASCII)

1 EtherNet/IP port 1 RS-232 serial port (DF1 or ASCII)

Module expansion capacity

16 1769 modules

16 1769 modules

16 1769 modules

30 1769 modules

30 1769 modules

Power supply distance rating

4 modules

4 modules

4 modules

4 modules

4 modules

The CompactLogix controller has a power supply distance-rating of four modules. The controller must be the leftmost module in the first bank of the system. The maximum configuration for the first bank of a CompactLogix controller is the controller and three I/O modules to the left of the power supply and eight I/O modules to the right of the power supply.

Bank 0

Bank 1

Bank 2

48

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 49

CompactLogix Controllers Specifications

1769-L3x Local I/O Performance You can configure an individual RPI for each local 1769 Compact I/O module. The RPI defines the frequency at which the controller sends and receives all I/O data on the backplane. Type of Module

Guideline

Digital and analog (any mix)

• 1…4 modules can be scanned in 1 ms • 5…30 modules can be scanned in 2 ms • Some input modules have a fixed 8 ms filter, so selecting a faster RPI has no effect

Specialty

• Full-sized 1769-SDN modules add 2 ms per module • 1769-HSC modules add 1 ms per module • Full-sized 1769-ASCII modules add 1 ms per module

You can always select an RPI that is slower than listed previously. These considerations show how fast modules can be scanned - not how fast an application can use the data. The RPI is asynchronous to the program scan. Other factors, such as program execution duration, affect I/O throughput. Table 33 - Technical Specifications - 1769 Modular CompactLogix Controllers Attribute

1769-L31

1769-L32C

1769-L32E

1769-L35CR

1769-L35E

User memory

512 KB

750 KB

750 KB

1.5 MB

1.5 MB

Optional nonvolatile memory

1784-CF128

Number of I/O modules, max

16

16

16

30

30

Number of I/O banks, max

3

Number of expansion I/O modules, max

16 1769 modules

Replacement battery

1769-BA

30 1769 modules

Current draw @ 5V DC

330 mA

650 mA

660 mA

680 mA

660 mA

Current draw @ 24V DC

40 mA

40 mA

90 mA

40 mA

90 mA

Power dissipation

2.61 W

4.21 W

5.5 W

4.36 W

5.5 W

Isolation voltage

30V (continuous), basic insulation type Type tested at 710V DC for 60 s; RS-232 channel 0 to system No isolation between RS-232 channel 1 and system

30V (continuous), basic insulation type Type tested at 710V DC for 60 s; RS-232 to system, ControlNet to system, RS-232 to ControlNet, ControlNet channel A to ControlNet channel B

30V (continuous), basic insulation type Type tested at 710V DC for 60 s; RS-232 to system, Ethernet to system, RS-232 to Ethernet

30V (continuous), basic insulation type Type tested at 710V DC for 60 s; RS-232 to system, ControlNet to system, RS-232 to ControlNet, ControlNet channel A to ControlNet channel B

30V (continuous), basic insulation type Type tested at 710V DC for 60 s; RS-232 to system, Ethernet to system, RS-232 to Ethernet

Communication ports

CH0 - RS-232 DF1, DH-485, ASCII Fully isolated 38.4 Kbps max CH1 - RS-232 DF1, DH-485 Nonisolated 38.4 Kbps max

RS-232 Fully isolated 38.4 Kbps max ControlNet port

RS-232 Fully isolated 38.4 Kbps max EtherNet/IP port 10/100 BASE-T

RS-232 Fully isolated 38.4 Kbps max ControlNet port

RS-232 Fully isolated 38.4 Kbps max EtherNet/IP port 10/100 BASE-T

Serial cables

1756-CP3 or 1747-CP3, right angle connector to controller, straight to serial port, 3 m

Weight, approx

0.30 kg (0.66 lb)

0.32 kg (0.70 lb)

0.30 kg (0.66 lb)

Slot width

1

Module location

DIN rail or panel mount

0.32 kg (0.70 lb)

0.30 kg (0.66 lb)

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

49

Page 50

CompactLogix Controllers Specifications

Table 33 - Technical Specifications - 1769 Modular CompactLogix Controllers Attribute

1769-L31

1769-L32C

Panel-mounting screw torque

1.1…1.8 Nm (10…16 lbin) - use M4 or #8 screws

Power supply distance rating

4 modules

Power supply

1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4

Wire category(1)

2 - on communication ports

North American temperature code

T5

T4A

IEC temperature code

NA

NA

Enclosure type rating

None (open-style)

1769-L32E

1769-L35CR

1769-L35E

T4

NA

T4

(1) Use this conductor category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 34 - Certifications - 1769 Modular CompactLogix Controllers Certification(1)

1769-L31 c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

EX, 1769-L32C, 1769-L35CR

1769-L32E, 1769-L35E

European Union 2004/108/EC EMC Directive, compliant with: • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection ’n’ • EN 60079-0; General Requirements (Zone 2) • II 3 G Ex nA IIC T4 Gc

CI, ControlNet International conformance tested to ControlNet specifications, EtherNet/IP, - ODVA conformance tested to EtherNet/IP specifications.

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Real-time Clock Accuracy The following table lists the real-time clock accuracy specifications for the 1769 Modular CompactLogix controllers. Ambient Temperature

Accuracy

0 °C (32 °F)

54…-56 s/mo

25 °C (77 °F)

9…-124 s/mo

40 °C (104 °F)

-84…-234 s/mo

55 °C (131 °F)

-228…-394 s/mo

60 °C (140 °F)

-287…-459 s/mo

50

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 51

CompactLogix Controllers Specifications

1769-L3x Minimum Spacing Requirements 50 mm (2 in.)

50 mm (2 in.)

50 mm (2 in.)

50 mm (2 in.)

1769-L3x CompactLogix Dimensions 67.5 mm (2.66 in.)

87 mm (3.42 in.)

131.6 mm (5.18 in.)

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

51

Page 52

CompactLogix Controllers Specifications

1768 CompactLogix Controllers

The 1768-L4x controller combines both a 1768 backplane and a 1769 backplane. The 1768 backplane supports the 1768 controller, the 1768 power supply, and a maximum of four 1768 modules. The 1769 backplane supports 1769 modules. Table 35 - Features - 1768 CompactLogix Controllers Characteristic

1768-L43

1768-L43S

1768-L45

1768-L45S

Available user memory

2 MB

2 MB standard 0.5 MB safety

3 MB

3 MB standard 1 MB safety

CompactFlash card

1784-CF128

1784-CF128

Communication options

• EtherNet/IP (standard and safety) • ControlNet (standard and safety) • DeviceNet (standard)

• EtherNet/IP (standard and safety) • ControlNet (standard and safety) • DeviceNet (standard)

Serial communication port

1 RS-232 port

1 RS-232 port

Module expansion capacity

• Two 1768 modules • Sixteen 1769 modules

• Two 1768 modules • Thirty 1769 modules

Power supply distance rating, Programming languages

• • • •, Relay ladder Structured Text Function block Sequential function chart

• Standard task: all languages • Safety task: relay ladder, safety application instructions

• • • •

Relay ladder Structured Text Function block Sequential function chart

• Standard task: all languages • Safety task: relay ladder, safety application instructions

Compact GuardLogix Safety System The Compact GuardLogixcontroller is a 1768-L4xS CompactLogix controller that provides safety control to achieve SIL 3/PLe according to ISO 13849. A major benefit of this system is that it’s still one project, safety and standard together. See page 5 for more information about developing projects with Compact GuardLogix controllers.

52

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 53

CompactLogix Controllers Specifications

1768-L4x Placement In a 1768-L4x controller system, place 1768 modules between the power supply and the controller. Place 1768 modules to the left of the controller.

Communication or Motion Power Supply

Controller

1769 I/O

Place 1769 modules to the right of the 1768 backplane: • As many as eight 1769 modules can be attached to the right of the 1768 system. • The 1769 I/O connected directly to the 1768 backplane does not need a 1769 power supply. • Additional 1769 modules must be in additional I/O banks. • Each additional I/O bank must have its own 1769 power supply. Place 1769 modules to the right of the controller. Communication or Motion Power Supply

Controller

1769 I/O

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

53

Page 54

CompactLogix Controllers Specifications

1768-L4x Local I/O Performance Configure an individual RPI for each local 1769 Compact I/O module. Use the default RPI numbers that the programming software automatically assigns or select faster RPI values as fast as 1 ms. I/O module update times do not affect overall 1768 bus performance in the following situations: • Use faster RPI values for time critical I/O without impacting overall 1769 Compact I/O performance. • Use Immediate Output (IOT) instructions for further reduction in I/O module update times. Table 36 - Technical Specifications - 1768 CompactLogix Controllers Attribute

1768-L43

1768-L43S

1768-L45

1768-L45S

User memory

2 MB

2 MB standard 0.5 MB safety

3 MB

3 MB standard 1 MB safety

Optional nonvolatile memory

1784-CF128

Number of 1768 modules, max

2

Number of 1768 communication modules, max

2

Number of 1768 motion modules, max

2

4

Number of 1769 I/O modules, max

16

30

Number of I/O banks, max

2

3

Replacement battery

None needed

Backplane current draw @ 24V DC

1.3 A

1768 current draw @ 5V DC

2.8 A

5.6 A

1769 current draw @ 5V DC

2.0 A

2.0 A

Total 1768 and 1769 current draw @ 5V DC

4.8 A

7.6 A

Power dissipation

6.3 W

7.5 W

8.3 W

9.5 W

Power consumption

31.3 W

33.6 W

48.0 W

50.4 W

Isolation voltage

30V (continuous), functional insulation type Type tested at 500V AC for 60 s; RS-232 to system

Communication ports

RS-232 Fully isolated, 38.4 Kbps max

Serial cables

1756-CP3 or 1747-CP3, right angle connector to controller, straight to serial port, 3 m

Weight, approx

0.34 kg (11.99 oz)

0.45 kg (15.9 oz)

0.34 kg (11.99 oz)

0.45 kg (15.9 oz)

Dimensions (HxWxD)

131.1 x 56.4 x 121.1 mm (5.18 x 2.22 x 4.81 in.)

131.6 x 89.6 x 122.1 mm (5.18 x 3.53 x 4.81 in.)

131.1 x 56.4 x 121.1 mm (5.18 x 2.22 x 4.81 in.)

131.6 x 89.6 x 122.1 mm (5.18 x 3.53 x 4.81 in.)

Slot width

1

1.5

1

1.5

N/A

T4

4

1.4 A

Module location

DIN rail or panel mount

Panel-mounting screw torque

1.16 Nm (10 lbin) - use M4 or #8 screws

Power supply distance rating

4 modules

Power supply

1768-PA3, 1768-PB3

Wire category(1)

2 - on communication ports

IEC temperature code

N/A

North American temperature code

T4

Enclosure type rating

None (open-style)

T4

2.0 A

2.1 A

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

54

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015