Page 64

CompactLogix Controllers Specifications

1769-L23x CompactLogix Connections The controller that you select determines the connections for I/O and messages. Controller

Supports

1769-L23EQB1B

32 CIP connections 8 TCP/IP connections

1769-L23EQBFC1B

The total connection requirements for a 1769 CompactLogix system include both local and remote (distributed) connections. The controller supports 100 connections. The available remote connections depend on the network interface.

1769-L3x CompactLogix Connections The controller that you select determines the connections for I/O and messages. Controller

Supports

1769-L32C 1769-L35CR

32 CIP connections

1769-L32E 1769-L35E

32 CIP connections 32 TCP/IP connections

The total connection requirements for a 1769 CompactLogix system include both local and remote (distributed) connections. The controller supports 100 connections. The available remote connections depend on the network interface.

1768-L4x CompactLogix Connections The communication module that you select determines the connections for I/O and messages. Communication Module

Supports

1768-ENBT 1768-EWEB

128 CIP connections 64 TCP/IP connections

1768-CNB 1768-CNBR

48 CIP connections

The total connection requirements for a 1768 CompactLogix system include both local and remote (distributed) connections. The controller supports 250 connections. The available remote connections depend on the network interface.

64

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 65

CompactLogix Controllers Specifications

Determine Total Connection Use The total connection requirements for a CompactLogix system include both local and remote (distributed) connections. The controllers support these numbers of connections: • 1769-L23x and 1769-L3x controllers support 100 connections. • 1768-L4x controllers support 250 connections. • CompactLogix 5370 controllers support 256 connections. The available remote connections depend on the network interface. Connection Type

Device Quantity

Connections per Device

Remote ControlNet communication module Configured as a direct (none) connection Configured as a rack-optimized connection

0 or 1

Remote I/O module over a ControlNet network (direct connection)

1

Remote Ethernet communication module Configured as a direct (none) connection Configured as a rack-optimized connection

0 or 1

Remote I/O module over an EtherNet/IP network (direct connection)

1

Remote device over a DeviceNet network (accounted for in rack-optimized connection for local 1756-DNB module)

0

Produced tag and first consumer Each additional consumer

2

Consumed tag

1

Cached message

1

Message

1

RSLinx Enterprise subscriber (16 maximum)

1

Total Connections

1

Total

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

65

Page 66

CompactLogix Controllers Specifications

CompactLogix Controller Accessories Memory Cards Memory cards offer nonvolatile memory to store a user program and tag data on a controller. Through the programming software, you can manually trigger the controller to save to or load from nonvolatile memory or configure the controller to load from nonvolatile memory on powerup. .

IMPORTANT

The 1769-L23x packaged CompactLogix controllers do not offer a nonvolatile memory option.

The CompactLogix 5370 controllers come with a 1784-SD1 Secure Digital (SD) card installed. You can order a 1784-SD2 SD card separately for additional nonvolatile memory with the CompactLogix 5370 controllers. The 1768-L4x and 1769-L3x modular CompactLogix controllers offer a CompactFlash card as a nonvolatile memory option. You install the CompactFlash card in a socket on the controller. Through the programming software, you can manually trigger the controller to save to or load from nonvolatile memory or configure the controller to load from nonvolatile memory on powerup. Table 39 - Technical Specifications - 1784-CF128, 1784-SD1, 1784-SD2 Attribute

1784-CF128

1784-SD1

1784-SD2

Memory

128 MB

1 GB

2 GB

Supported controllers

1769 modular controllers 1768 controllers

CompactLogix 5370 controllers

Weight, approx

14.2 g (0.5 oz)

1.76 g (0.062 oz)

Table 40 - Environmental Specifications - 1784-CF128, 1784-SD1, 1784-SD2 Attribute

1784-CF128, 1784-SD1, 1784-SD2

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…70 °C (-13…158 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

Group 1, Class A

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

66

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 67

CompactLogix Controllers Specifications

Table 41 - Certifications - 1784 Memory Cards Certification(1)

1784-CF128, 1784-SD1, 1784-SD2

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61000-6-4; Industrial Emissions • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1769 CompactLogix Batteries The 1769-L23x and 1769-L3x controllers come with one 1769-BA lithium battery. The 1768 controllers and the CompactLogix 5370 controllers do not require a battery. The controller uses internal nonvolatile memory to store its program during shutdown. Energy that is stored in the system maintains controller power long enough to store the program to internal nonvolatile memory, but not the external CompactFlash card nor SD card respectively. Table 42 - Technical Specifications - 1769-BA Attribute

1769-BA

Description

Lithium battery (0.59 g)

CompactLogix controllers

1769-L23-QBFC1B, 1769-L23E-QB1B, 1769-L23E-QBFC1B 1769-L31 1769-L32C, 1769-L35CR 1769-L32E, 1769-L35E

Removable Terminal Kits You can order removable terminal kits with the CompactLogix 5370 L1 and L2 controllers separately. The kits are used to connect wiring to the controllers. Table 43 describes the kits. Table 43 - CompactLogix 5370 Controllers Removable Terminal Kits Cat. No.

Controllers Supported

Description

1769-RTB45

CompactLogix 5370 L1

• Four 10-pin connectors are used to connect wiring to the embedded digital I/O module of the controller. • One 5-pin connector is used to connect an external 24V DC power source to the controller.

1769-RTB40DIO

CompactLogix 5370 L2

Four 10-pin connectors are used to connect wiring to the embedded digital I/O module of the controller.

1769-RTB40AIO

1769-L24ER-QBFC1B and 1769L27ERM-QBFC1B

Four 10-pin connectors are used to connect wiring to the embedded analog I/O module of the controller.

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

67

Page 68

CompactLogix Controllers Specifications

Cold Junction Compensation The CompactLogix 5370 L2 controllers require the use of the 1769-CJC CompactLogix CJC Sensor when the embedded analog input of the controller is configured for Thermocouple mode.

Ethernet Communication Cables

Attribute

Value

Connector type

RJ45 Male to RJ45 Male

Connector angle

Straight-through

Length

Varies by catalog number

Connector Number

Color

1585J-M8xBJM-2

1

White/Orange

TxData +

2

Orange

TxData -

3

White/Green

Recv Data +

4

Blue

Unused

-

5

White/Blue

Unused

-

6

Green

Recv Data -

7

White/Brown

Unused

-

8

Brown

Unused

-

Serial Communication Cables 1 CD 2 RXD 3 TXD 4 DTR 5 Common 6 DSR 7 RTS 8 CTS 9 RI

Internal Jumper

1 CD 3 TXD 2 RXD 6 DSR 5 Common 4 DTR 8 CTS 7 RTS 9 RI

To Controller

To Serial Port

Attribute

1756-CP3

Connector type

Female 9-pin D-shell

Connector angle

Right angle connector to controller, straight to serial port

Length

3 m (118 in.)

68

1747-CP3

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

1585J-M4TBJM-2

Page 69

CompactLogix Controllers Specifications

Notes:

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

69

Page 70

CompactLogix Controllers Specifications

Notes:

70

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 71

CompactLogix Controllers Specifications

Notes:

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

71

Page 72

Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, ArmorBlock, ArmorBlock MaXum, ArmorPOINT, CompactBlock, Compact I/O, CompactLogix, ControlLogix, DriveLogix, FLEX, FLEX Ex, FlexLogix, Guard I/O, GuardLogix, InView, LISTEN. THINK. SOLVE, MicroLogix, PanelView, PLC-2, PLC-3, PLC-5, POINT I/O, PowerFlex, Rockwell Automation, Rockwell Software, RSLinx, SCANport, SLC, and SoftLogix are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. ControlNet, DeviceNet, and EtherNet/IP are trademarks of the ODVA.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Publication 1769-TD005J-EN-P - September 2015 Supersedes Publication 1769-TD005I-EN-P - August 2014