Page 28

CompactLogix Controllers Specifications

Figure 8 - Maximum Output Current per Module - 24V DC Operation Current Derating Based on Temperature 5

Current per Module (A)

4 3 2 1

1 A at 60 °C (131 °F) 0

0 (32)

10 (50)

20 (68)

30 (86)

40 (104)

50 (122)

60 (140)

70 (158)

Ambient Temperature °C (°F) Temperature

Derated Current

40 °C (104 °F)

4A

55 °C (131 °F)

2A

60 °C (140 °F)

1A

Table 18 - Embedded Power Supply Attribute

1769-L24ER-QB1B

Input voltage range

19.2…31.2V DC

Input voltage, nom Line requirement, max

1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B

24V DC (1)

2.1 A @ 24V DC, Class 2/SELV

Available 5V DC bus current

1.54 A

1.0 A

Available 24V DC bus current

0.95 A

0.8 A

Inrush, max

< 30 A @ 19.2…31.2V DC

Line loss ride through

10 ms…10 s

Short circuit protection

Internal fuse Not user replaceable

Overvoltage protection

Yes

Isolation voltage

30V AC/30V DC (continuous), reinforced insulation type Type tested at 500V AC or 710V DC for 60 s; outputs to system backplane

(1) Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F).

28

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 29

CompactLogix Controllers Specifications

I/O Module Support - CompactLogix 5370 L3 and Compact GuardLogix 5370 Controllers The CompactLogix 5370 L3 controllers offer local expansion modules that are installed across up to three banks of modules. You must use 1769 Compact I/O modules with these controllers. Remember the following when using I/O modules with the CompactLogix 5370 L3 and Compact GuardLogix 5370 controllers: • The controller must be the leftmost module in the local bank of the system. • The number of I/O modules that are supported in a controller system varies by controller catalog number. Cat. No.

Local 1769 Compact I/O Modules Supported, max

1769- L30ER 1769-L30ERM 1769-L30ERMS 1769-L30ER-NSE

8

1769-L33ER 1769-L33ERM 1769-L33ERMS

16

1769-L36ERM 1769-L36ERMS

30

You can install I/O modules in as many as three banks, that is, the local bank and two additional banks. You can install as many as three I/O modules between the controller and power supply. You can install as many as eight I/O modules to the right of the power supply in the local bank. You can install as many as eight I/O modules on both the left and right sides of the power supply in additional banks. You must consider the distance rating and current draw of the controller and all I/O modules when designing your system. • Systems with multiple banks can be installed vertically or horizontally. • You must use expansion cables to connect banks in multi-bank systems. • • • • •

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

29

Page 30

CompactLogix Controllers Specifications

• You must terminate the end of the last bank in a system.

Horizontal Orientation

Local Bank

Additional Bank

Additional Bank

1769-CRL1 Compact I/O Communication Bus Expansion Cables

End Cap

Local Bank 1769-CRR1 Compact I/O Communication Bus Expansion Cables

Vertical Orientation

End Cap

Additional Bank

Local I/O Performance of CompactLogix 5370 L3 Controllers The requested packet interval (RPI) defines the frequency at which the controller sends data to and receives data from I/O modules. In the programming software, you set an RPI rate for each I/O module in your system. The CompactLogix 5370 L3 controllers always attempt to scan an I/O module at the configured RPI rate. If there is not enough system bandwidth, that is, if other, higher priority tasks prevent the 1769 Compact I/O subsystem task from completing before the next scheduled time for it to run again, an I/O Task Overlap minor fault occurs. Higher priority tasks that prevent the 1769 Compact I/O subsystem task from completing before the next scheduled time for it to run again use up system bandwidth. For individual I/O modules, a Module RPI Overlap minor fault occurs if there is at least one I/O module that cannot be serviced within its RPI time. The specific configuration parameters for a system determine the impact on actual RPI rates. These configuration factors can impact the effective scan frequency for any individual module: • Rates at which the RPI rates of other 1769 Compact I/O are set • Number of other 1769 Compact I/O modules in the system • Types of other 1769 Compact I/O modules in the system • Application user task priorities

30

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 31

CompactLogix Controllers Specifications

Table 19 - RPI Rate Guidelines Type of Module

Guidelines

1769 Compact I/O digital and analog (any mix) modules

The following guidelines apply: • 1…2 modules can be scanned in 0.5 ms. • 3…4 modules can be scanned in 1 ms. • 5…30 modules can be scanned in 2 ms. • Some input modules have a fixed 8 ms filter, so selecting a faster RPI has no effect.

1769 Compact I/O specialty modules

The following conditions apply: • For every full-sized 1769-SDN module in the system, increase the RPI of every other module by 2 ms. • For every 1769-HSC module in the system, increase the RPI of every other module by 1 ms. • For every full-sized 1769-ASCII module system, increase the RPI of every other module by 1 ms. • For every 1769-SM2 module in the system, increase every the RPI of other module by 2 ms. For example, if there are four digital I/O modules in the system that is configured with an RPI = 1 ms and a 1769-SDN module is added to the system, increase the RPI value for all four digital I/O modules by 2 ms. Therefore, when the 1769-SDN module is added to the system the four digital I/O modules use an RPI = 3 ms. If, in the same system, you add a second 1769-SDN module, the RPI value of the four digital I/O modules is increased to 5 ms.

You can set individual RPI values of 1769 Compact I/O module higher than those values listed in Table 19. For example, if your application scans one or two modules, you do not have to use RPI values = 0.5 ms. You can set the RPI to a higher value, such as 1.0 ms, if necessary. Remember, higher RPI values result in scanning the data less frequently.

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

31

Page 32

CompactLogix Controllers Specifications

The RPI is asynchronous to the program scan. Other factors, such as program execution duration, affect I/O throughput. Table 20 - Certifications - CompactLogix 5370 Controllers and Compact GuardLogix 5370 Controllers Certification(1)

1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: • AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T4 Gc • ITS12ATEX47611X

TÜV

N/A

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications.

1769-L24ER-QB1B, 1769L24ER-QBFC1B, 1769-L27ERM-QBFC1B

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T4 Gc • DEMKO12ATEX 1116807X

1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) • EN 60204-1; Electrical equipment of machines • EN ISO 13849-1; Safety-related parts of control systems • EN 62061; Functional safety of safetyrelated control systems European Union 2011/65/EU RoHS, compliant with: EN 50581; Technical documentation

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T5 Gc X • ITS09ATEX46118X

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T5 Gc • DEMKO 15ATEX1388X TÜV Certified for Functional Safety Capable of SIL 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

32

1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 33

CompactLogix Controllers Specifications

CompactLogix 5370 L1 Controllers Minimum Spacing Requirements

50 mm (2 in.) End Cap

1734 POINT I/O Module

1734 POINT I/O Module

Side

1769-L16ER-BB1B, 1769-L18ER-BB1BB, or 1769-L18ERM-BB1B Controller with Embedded Power Supply and I/O Module

50 mm (2 in.)

1734 POINT I/O Module

50 mm (2 in.)

Top

Side

50 mm (2 in.)

Bottom

CompactLogix 5370 L2 Controllers Minimum Spacing Requirements

Bottom

50 mm (2 in.) End Cap

Compact I/O Module

Compact I/O Module

Compact I/O Module

Side

CompactLogix 5370 L2 Controller with Embedded Power Supply and I/O Points

50 mm (2 in.)

Compact I/O Module

50 mm (2 in.)

Top

Side

50 mm (2 in.)

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

33

Page 34

CompactLogix Controllers Specifications

CompactLogix 5370 L3 and Compact GuardLogix 5370 Controllers Minimum Spacing Requirements

Bottom

50 mm (2 in.) End Cap

1769 Compact I/O Module

Power Supply

Side

CompactLogix 5370 L3 or Compact GuardLogix 5370 L3 Controllers

50 mm (2 in.)

1769 Compact I/O Module

50 mm (2 in.)

Top

Side

50 mm (2 in.)

CompactLogix 5370 L1 Controllers Dimensions 100 mm (3.94 in.)

144 mm (5.67 in.)

34

130 mm (5.11 in.)

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

105 mm (4.13 in.)

Page 35

CompactLogix Controllers Specifications

CompactLogix 5370 L2 Controllers Dimensions 1769-L24ER-QB1B

24VDC SINK\ SOURCE

0

24VDC SOURCE

QB1B

1

2

3

6

7

8

9

10

11 12 13 14

15

DC INPUT

L24ER

0

1

2

3

6

7

DC OUTPUT

115 mm (4.53 in.)

4

5

8

9

10

11 12 13 14

15

4

5

DC IN

00 08 01 09 02 10 03 11 04 12 05 13 06 14

118 mm (4.65 in.)

07 15

COM COM 0 1

105 mm (4.13 in.)

NC NC +V +V 00 08 01 09 02 10 03 11 04 12

00:00:BC:2E:69:F6

05 13 06 14 07 15

COM COM 0 1 DC OUT

+24VDC

COM

FG

1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B (Dimensions are the same on both controller catalog numbers.) 140 mm (5.51 in.)

7 15

DC INPUT

3

6

7

8

9

10

11 12 13 14

15

HSC

00 08

A0+ A0-

Z0+ Z0-

03 11

A1+ A1-

04 12

B1+ B1-

05 13

Z1+ Z1-

06 14

COM COM 0 1

+V +V OUT OUT 0 2 OUT 0UT 1 3

NC NC

COM COM

00 08 01 09 02 10 03 11 04 12 05 13 06 14 07 15

COM

A1 B1 Z1

0

2 FUSE

1

3

OK

B0+ B0-

02 10

+V +V

+24VDC

5

5

DC IN

07 15

00:00:BC:2E:69:F6

4

IN

6

11 12 13 14

2

OUT

3

10

HIGH SPEED COUNTER

2

9

1

01 09

118 mm (4.65 in.)

4

A0 B0 Z0

1

8

0

DC OUTPUT

24VDC SINK\ SOURCE

0

24VDC SOURCE

QBFC1B

V in 0+ I in 0+ V/I in 0-

V in 2+ I in 2+ V/I in 2-

V CJC in + 3+ I in 3+

CJC V in 1+ I in 1+

V/I in 3-

V/I in 1V V OUT OUT 0+ 1+ I I OUT in 0+ 1+

COM COM 0 1

COM COM

DC OUT

ANALOG

FG

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

35

Page 36

CompactLogix Controllers Specifications

CompactLogix 5370 L3 Controllers Dimensions 55 mm (2.17 in.)

132 mm (5.20 in.)

105 mm (4.13 in.)

118 mm (4.65 in.)

Compact GuardLogix 5370 Controllers Dimensions 89 mm (3.50 in.)

132 mm (5.20 in.)

36

118 mm (4.65 in.)

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

114 mm (4.13 in.)