The text of a spec sheet · part 4 of 8
CompactLogix Controllers Specifications, pages 28 to 36
Pages 28 to 36 of 72
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1769-IQ6X0W4
Page 28
CompactLogix Controllers Specifications
Figure 8 - Maximum Output Current per Module - 24V DC Operation Current Derating Based on Temperature 5
Current per Module (A)
4 3 2 1
1 A at 60 °C (131 °F) 0
0 (32)
10 (50)
20 (68)
30 (86)
40 (104)
50 (122)
60 (140)
70 (158)
Ambient Temperature °C (°F) Temperature
Derated Current
40 °C (104 °F)
4A
55 °C (131 °F)
2A
60 °C (140 °F)
1A
Table 18 - Embedded Power Supply Attribute
1769-L24ER-QB1B
Input voltage range
19.2…31.2V DC
Input voltage, nom Line requirement, max
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
24V DC (1)
2.1 A @ 24V DC, Class 2/SELV
Available 5V DC bus current
1.54 A
1.0 A
Available 24V DC bus current
0.95 A
0.8 A
Inrush, max
< 30 A @ 19.2…31.2V DC
Line loss ride through
10 ms…10 s
Short circuit protection
Internal fuse Not user replaceable
Overvoltage protection
Yes
Isolation voltage
30V AC/30V DC (continuous), reinforced insulation type Type tested at 500V AC or 710V DC for 60 s; outputs to system backplane
(1) Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F).
28
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 29
CompactLogix Controllers Specifications
I/O Module Support - CompactLogix 5370 L3 and Compact GuardLogix 5370 Controllers The CompactLogix 5370 L3 controllers offer local expansion modules that are installed across up to three banks of modules. You must use 1769 Compact I/O modules with these controllers. Remember the following when using I/O modules with the CompactLogix 5370 L3 and Compact GuardLogix 5370 controllers: • The controller must be the leftmost module in the local bank of the system. • The number of I/O modules that are supported in a controller system varies by controller catalog number. Cat. No.
Local 1769 Compact I/O Modules Supported, max
1769- L30ER 1769-L30ERM 1769-L30ERMS 1769-L30ER-NSE
8
1769-L33ER 1769-L33ERM 1769-L33ERMS
16
1769-L36ERM 1769-L36ERMS
30
You can install I/O modules in as many as three banks, that is, the local bank and two additional banks. You can install as many as three I/O modules between the controller and power supply. You can install as many as eight I/O modules to the right of the power supply in the local bank. You can install as many as eight I/O modules on both the left and right sides of the power supply in additional banks. You must consider the distance rating and current draw of the controller and all I/O modules when designing your system. • Systems with multiple banks can be installed vertically or horizontally. • You must use expansion cables to connect banks in multi-bank systems. • • • • •
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
29
Page 30
CompactLogix Controllers Specifications
• You must terminate the end of the last bank in a system.
Horizontal Orientation
Local Bank
Additional Bank
Additional Bank
1769-CRL1 Compact I/O Communication Bus Expansion Cables
End Cap
Local Bank 1769-CRR1 Compact I/O Communication Bus Expansion Cables
Vertical Orientation
End Cap
Additional Bank
Local I/O Performance of CompactLogix 5370 L3 Controllers The requested packet interval (RPI) defines the frequency at which the controller sends data to and receives data from I/O modules. In the programming software, you set an RPI rate for each I/O module in your system. The CompactLogix 5370 L3 controllers always attempt to scan an I/O module at the configured RPI rate. If there is not enough system bandwidth, that is, if other, higher priority tasks prevent the 1769 Compact I/O subsystem task from completing before the next scheduled time for it to run again, an I/O Task Overlap minor fault occurs. Higher priority tasks that prevent the 1769 Compact I/O subsystem task from completing before the next scheduled time for it to run again use up system bandwidth. For individual I/O modules, a Module RPI Overlap minor fault occurs if there is at least one I/O module that cannot be serviced within its RPI time. The specific configuration parameters for a system determine the impact on actual RPI rates. These configuration factors can impact the effective scan frequency for any individual module: • Rates at which the RPI rates of other 1769 Compact I/O are set • Number of other 1769 Compact I/O modules in the system • Types of other 1769 Compact I/O modules in the system • Application user task priorities
30
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 31
CompactLogix Controllers Specifications
Table 19 - RPI Rate Guidelines Type of Module
Guidelines
1769 Compact I/O digital and analog (any mix) modules
The following guidelines apply: • 1…2 modules can be scanned in 0.5 ms. • 3…4 modules can be scanned in 1 ms. • 5…30 modules can be scanned in 2 ms. • Some input modules have a fixed 8 ms filter, so selecting a faster RPI has no effect.
1769 Compact I/O specialty modules
The following conditions apply: • For every full-sized 1769-SDN module in the system, increase the RPI of every other module by 2 ms. • For every 1769-HSC module in the system, increase the RPI of every other module by 1 ms. • For every full-sized 1769-ASCII module system, increase the RPI of every other module by 1 ms. • For every 1769-SM2 module in the system, increase every the RPI of other module by 2 ms. For example, if there are four digital I/O modules in the system that is configured with an RPI = 1 ms and a 1769-SDN module is added to the system, increase the RPI value for all four digital I/O modules by 2 ms. Therefore, when the 1769-SDN module is added to the system the four digital I/O modules use an RPI = 3 ms. If, in the same system, you add a second 1769-SDN module, the RPI value of the four digital I/O modules is increased to 5 ms.
You can set individual RPI values of 1769 Compact I/O module higher than those values listed in Table 19. For example, if your application scans one or two modules, you do not have to use RPI values = 0.5 ms. You can set the RPI to a higher value, such as 1.0 ms, if necessary. Remember, higher RPI values result in scanning the data less frequently.
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
31
Page 32
CompactLogix Controllers Specifications
The RPI is asynchronous to the program scan. Other factors, such as program execution duration, affect I/O throughput. Table 20 - Certifications - CompactLogix 5370 Controllers and Compact GuardLogix 5370 Controllers Certification(1)
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM
Australian Radiocommunications Act, compliant with: • AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T4 Gc • ITS12ATEX47611X
TÜV
N/A
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3
EAC
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications.
1769-L24ER-QB1B, 1769L24ER-QBFC1B, 1769-L27ERM-QBFC1B
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T4 Gc • DEMKO12ATEX 1116807X
1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM
European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) • EN 60204-1; Electrical equipment of machines • EN ISO 13849-1; Safety-related parts of control systems • EN 62061; Functional safety of safetyrelated control systems European Union 2011/65/EU RoHS, compliant with: EN 50581; Technical documentation
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T5 Gc X • ITS09ATEX46118X
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T5 Gc • DEMKO 15ATEX1388X TÜV Certified for Functional Safety Capable of SIL 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
32
1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 33
CompactLogix Controllers Specifications
CompactLogix 5370 L1 Controllers Minimum Spacing Requirements
50 mm (2 in.) End Cap
1734 POINT I/O Module
1734 POINT I/O Module
Side
1769-L16ER-BB1B, 1769-L18ER-BB1BB, or 1769-L18ERM-BB1B Controller with Embedded Power Supply and I/O Module
50 mm (2 in.)
1734 POINT I/O Module
50 mm (2 in.)
Top
Side
50 mm (2 in.)
Bottom
CompactLogix 5370 L2 Controllers Minimum Spacing Requirements
Bottom
50 mm (2 in.) End Cap
Compact I/O Module
Compact I/O Module
Compact I/O Module
Side
CompactLogix 5370 L2 Controller with Embedded Power Supply and I/O Points
50 mm (2 in.)
Compact I/O Module
50 mm (2 in.)
Top
Side
50 mm (2 in.)
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
33
Page 34
CompactLogix Controllers Specifications
CompactLogix 5370 L3 and Compact GuardLogix 5370 Controllers Minimum Spacing Requirements
Bottom
50 mm (2 in.) End Cap
1769 Compact I/O Module
Power Supply
Side
CompactLogix 5370 L3 or Compact GuardLogix 5370 L3 Controllers
50 mm (2 in.)
1769 Compact I/O Module
50 mm (2 in.)
Top
Side
50 mm (2 in.)
CompactLogix 5370 L1 Controllers Dimensions 100 mm (3.94 in.)
144 mm (5.67 in.)
34
130 mm (5.11 in.)
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
105 mm (4.13 in.)
Page 35
CompactLogix Controllers Specifications
CompactLogix 5370 L2 Controllers Dimensions 1769-L24ER-QB1B
24VDC SINK\ SOURCE
0
24VDC SOURCE
QB1B
1
2
3
6
7
8
9
10
11 12 13 14
15
DC INPUT
L24ER
0
1
2
3
6
7
DC OUTPUT
115 mm (4.53 in.)
4
5
8
9
10
11 12 13 14
15
4
5
DC IN
00 08 01 09 02 10 03 11 04 12 05 13 06 14
118 mm (4.65 in.)
07 15
COM COM 0 1
105 mm (4.13 in.)
NC NC +V +V 00 08 01 09 02 10 03 11 04 12
00:00:BC:2E:69:F6
05 13 06 14 07 15
COM COM 0 1 DC OUT
+24VDC
COM
FG
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B (Dimensions are the same on both controller catalog numbers.) 140 mm (5.51 in.)
7 15
DC INPUT
3
6
7
8
9
10
11 12 13 14
15
HSC
00 08
A0+ A0-
Z0+ Z0-
03 11
A1+ A1-
04 12
B1+ B1-
05 13
Z1+ Z1-
06 14
COM COM 0 1
+V +V OUT OUT 0 2 OUT 0UT 1 3
NC NC
COM COM
00 08 01 09 02 10 03 11 04 12 05 13 06 14 07 15
COM
A1 B1 Z1
0
2 FUSE
1
3
OK
B0+ B0-
02 10
+V +V
+24VDC
5
5
DC IN
07 15
00:00:BC:2E:69:F6
4
IN
6
11 12 13 14
2
OUT
3
10
HIGH SPEED COUNTER
2
9
1
01 09
118 mm (4.65 in.)
4
A0 B0 Z0
1
8
0
DC OUTPUT
24VDC SINK\ SOURCE
0
24VDC SOURCE
QBFC1B
V in 0+ I in 0+ V/I in 0-
V in 2+ I in 2+ V/I in 2-
V CJC in + 3+ I in 3+
CJC V in 1+ I in 1+
V/I in 3-
V/I in 1V V OUT OUT 0+ 1+ I I OUT in 0+ 1+
COM COM 0 1
COM COM
DC OUT
ANALOG
FG
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
35
Page 36
CompactLogix Controllers Specifications
CompactLogix 5370 L3 Controllers Dimensions 55 mm (2.17 in.)
132 mm (5.20 in.)
105 mm (4.13 in.)
118 mm (4.65 in.)
Compact GuardLogix 5370 Controllers Dimensions 89 mm (3.50 in.)
132 mm (5.20 in.)
36
118 mm (4.65 in.)
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
114 mm (4.13 in.)