Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 6 of 9

Thermocouple/Millivolt Input Module (Cat. No. 1771-IXE Series D) User Manual, pages 51 to 60

Pages 51 to 60 of 85

The original document is the PDF (708 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-IXE

Page 51

Chapter

Chapter Objective Diagnostics Reported by the Module

7

We describe how to troubleshoot your module by observing LED indicators and by monitoring status bits reported to the processor.

At power–up, the module momentarily turns on both indicators as a lamp test, then checks for

• • • • correct RAM operation EPROM operation EEPROM operation a valid write block transfer with configuration data Thereafter, the module lights the green RUN indicator when operating without fault, or lights the red FAULT indicator when it detects fault conditions. If the red FAULT indicator is on, block transfers will be inhibited. The module also reports status and specific faults (if they occur) in every transfer of data to the PC processor. Monitor the green and red status indicators and status bits in word 1 of the BTR file when troubleshooting your module. Figure 7.1 Status Indicators

% #

-

- -) ) -

Page 52

7–2

Troubleshooting

Troubleshooting with the Indicators

Table 7.A shows LED indications and probable causes and recommended actions to correct common faults. Table 7.A Troubleshooting Chart for Thermocouple/Millivolt Input Module (1771-IXE/D) Probable Cause

Indication

Recommended Action

Both LEDs are OFF

No power to module Possible short on the module LED driver failure

Check power to I/O chassis. Recycle as necessary. Replace module.

Red FLT LED ON and Green RUN LED is ON

Microprocessor, oscillator or EPROM failure

Replace module.

Red FLT LED ON

If immediately after power-up, indicates RAM or EPROM failure.1

Replace module.

If during operation, indicates possible microprocessor or backplane interface failure.1

Replace module.

Power-up diagnostics successfully completed.

Normal operation.

If LED continues to flash, and write block transfers (BTW) cannot be accomplished, you have a possible interface failure.

Replace module.

Green RUN LED is flashing

1 When red LED is on, the watchdog timer has timed out and backplane communications are terminated. Your user program should monitor communication.

Status Reported by the Module

Status Reported in Word 1 Design your program to monitor status bits in the lower byte of word 1, and to take appropriate action depending on your application requirements. You may also want to monitor these bits while troubleshooting with your industrial terminal. The module sets a bit (1) to indicate it has detected one or more of the following conditions as shown in Table 7.B. Table 7.B Status Reported in Word 1 Word

Bit

Explanation

1

00

Module is powered but has not received its first (configuration) block transfer. The green LED is flashing.

01

One or more inputs are out of the range for which you configured the module.

02

Module updated its inputs before the processor read them. The RTS interval timed out before the processor read the data.

03

Not used

04

The module's ambient temperature is below 0oC. Temperature readings will be inaccurate.

05

The module's ambient temperature is above 60oC. Temperature readings will be inaccurate.

Word 1 (cont)

Publication 1771-6.5.130 Ć May 1999

Page 53

Troubleshooting

Word

Bit

7–3

Explanation

0."!

+0(! *+/ )+!0(" 2&(( +*/&*0" /+

#+- %

Status Reported in Words 2 and 3 Design your program to monitor over/under range bits, and to take appropriate action depending on your application requirements. You may also want to monitor these bits while troubleshooting with your industrial terminal. Bits 00–07 and 10–17 each represent an input for channels 1–8, respectively. For example, bit 04 represents input channel 5. The module sets a bit (1) to indicate it has detected an out of range condition. Refer to Table 7.C. Table 7.C Status Reported in Words 2 and 3 Word

Bit

Condition

&/ &. &. &*,0/ +**" /&+*. +--" / /%&. &*!& +))0*& 2&/% /%" )& -+,-+ "..+-- /%&. &*!& ! +*1"-/"- +- #0."-

&/ &. &. &*,0/ +**" /&+*. +--" / /%&. &*!& /%"-)+ +0,(" #0* ' -

&*,0/ &. /%" 4+0 "*/"-"!

&*,0/ "3 ""!"! /%" 4+0 "*/"-"! #+-

5 - - 5

Page 54

7–4

Troubleshooting

Status Reported in Word 13 Design your program to monitor status bits in word 13 during auto–calibration, and to take appropriate action depending on your requirements. You may also want to monitor these bits while troubleshooting with your industrial terminal. The module sets a bit (1) to indicate it has detected one or more of the following conditions as shown in Table 7.D. Table 7.D Status Reported in Word 13 Word

Bit

Condition "#' "#' +

Chapter Summary

,

"#' )#

In this chapter, you learned how to interpret the LED status indicators, status words and troubleshoot your input module.

Page 55

Appendix

A

Number of Inputs

8, all of the same type or 4 each of 2 different types

I/O Chassis Location

Any single I/O module slot

Type of Input (Selectable)

Type E, chromel/constantan Type J, iron/constantan Type K, chromel/alumel Type R, Pt/Pt-13% Rh Type T, copper/constantan Type S, Pt/Pt-10% Rh Millivolt

Thermocouple Linearization

IPTS-68 standard, NBS MN-125

Cold Junction Compensation

Range: 0 to 60oC Accuracy: +0.5oC

Temperature Scale (Selectable)

oC or oF

Input Resolution

1oC, 1oF, or 10uV

Input Isolation

1000V peak between inputs, between input and common, and between input and backplane connections

Common Mode Rejection

120dB at 60Hz, up to 1000V peak

Common Mode Impedance

Greater than 10 megohms

Normal Mode Rejection

60dB at 60Hz

Input Overvoltage Protection

120V rms, continuous

Open Input Detection

Open input produces a maximum value reading in less than 10 seconds

Input Connections

18-terminal wiring arm (Cat. No. 1771-WI)

Data Format (Selectable)

4-digit BCD 2's complement binary signed magnitude binary

Calibration

Auto-calibration (offset and gain) Zero offset and gain adjustment for each channel via programming terminal Verify every six months for maintaining absolute accuracy

Processor Compatibility

Any A-B processor using the 1771 I/O structure and block transfer

Environmental Conditions Operating Temperature: Rate of Change: Storage Temperature: Relative Humidity:

(-270 to 1000oC) (-210 to 1200oC) (-270 to 1380oC) (-50 to 1770oC) (-270 to 400oC) (-50 to 1770oC) (-100 to +100mV dc)

0 to 60oC (32 to 140oF) Ambient changes greater than 0.5oC per minute may temporarily degrade performance during periods of change -40 to 85oC (-40 to 185oF) 5 to 95% (without condensation)

Backplane Power Consumption

750mA @ 5V; 3.75 Watts maximum

Field Wiring Arm

Cat. No. 1771-WI

Keying

Between 20 and 22 Between 24 and 26

Agency Certification (when product is marked)

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives • C-Tick marked for all applicable acts

Publication 1771-6.5.130 Ć May 1999

Page 56

A–2

Specifications

Thermocouple/Millivolt Input Module Accuracy

The accuracy of your thermocouple readings depends on:

• module accuracy • lead resistance effect • accuracy of the thermocouple The accuracy of the module is shown in NO TAG and NO TAG at ambient temperature (25oC) and over the temperature range (0–60oC). Use the calibration procedure in Chapter 6 to adjust your module to compensate for your specific environment. Table A.A Thermocouple Range Accuracy Based on Temperatures Above 0oC Thermocouple Type

Temperature Range oC

Max Error @ Calibration Temperature (25oC)1

Temperature Drift oC/oC (0-60oC) or oF/oF (32-140oF)

E

-270 to 1000

+0.74oC/+1.08oF

+0.0400

J

-210 to 1200

+0.78oC/+1.10oF

+0.0423

K

-270 to 1380

+0.77oC/+1.15oF

+0.0640

-270 to 400

+0.77oC/+1.17oF

+0.0183

-50 to 1770

+1.50oC/+2.11oF

+0.0914

-50 to 1770

+1.50oC/+2.31oF

+0.0926

T R S

1 Error is specified from 0oC (32oF) to the maximum range of the thermocouple. Error does not include thermocouple error (see appendix F). Table A.B Millivolt Range Accuracy Millivolt Range

Max Error @ Calibration Temperature (25oC)

Millivolt Drift

-100 to 100

+8.85uV

+3.856uV/oC

Table A.C Radiated Noise Susceptibility

Publication 1771-6.5.130 Ć May 1999

Radiated Noise

Susceptibility Error

300-1000MHz Circular Wave, Field Strength = 10V/M

< +1%

Page 57

Specifications

Lead Resistance Compensation

A–3

Allowable Distances The open thermocouple detection circuit injects a current of approximately 7.3 nanoamps into the thermocouple cable. A total lead resistance of 1370 ohms (685 ohms one–way) cable resistance will produce +1 count (10uV) of error.

Source Impedance Compensation for Millivolt Inputs Source resistance causes similar errors to occur with millivolt inputs. If source resistance is less than 100 ohms, no compensation is necessary to maintain stated accuracy. If source resistance is greater than 100 ohms, the error can be calculated as follows: &&%& Where

% #'

Rs = source resistance (one–way cable resistance) Vin = applied input voltage

When using thermocouples, Vin is the approximate thermocouple voltage of the temperature of interest.

&&%&

-

#'

To maintain a display error of < 5uV at Vin = OV, RS should be < 341 ohms. Refer to NBS NM–125 Thermocouple Reference Tables for determining actual thermocouple voltage versus temperature readings.

Filtering

The analog input module has hardware–based high frequency filters on all channels to reduce the effect of electrical noise on the input signal. In addition, a 6–pole digital filter, which begins rolling off at 8.0Hz, is also incorporated.

- +

Page 58 read from a scan by OCR; it may hold reading errors

A-4 Specifications

Publication 1771-6.5.130 - May 1999

Page 59

Appendix

Sample Programs for the Input Module PLC-2 Family Processors

-

-

B

The following are sample programs for entering data in the configuration words of the write block transfer instruction when using the PLC–2, PLC–3 or PLC–5 family processors.

To enter data in the configuration words, follow these steps. NOTE: For complete programming sample, refer to Figure 4.1. Example: Enter the following rung for a write block transfer:

Power Up Bit

BTW BLOCK XFER WRITE DATA ADDR: 030 MODULE ADDR: 110 BLOCK LENGTH: 27 FILE: 400-432

010 EN 06 110 DN 06

400 is the address of the write block transfer data file. You want to examine configuration word 1. In RUN/PROG Mode Action

Result

1. Press [SEARCH]8<data address>

Finds the block address transfer instruction

2. Press CANCEL COMMAND

Removes preceeding command

3. Press [DISPLAY]0 or 1

Displays the file in binary or BCD

4. Press [SEARCH]51

On line data change

Cursor defaults to first entry in file when SEARCH 51 is pressed. 5. Press [INSERT]

Writes data to file element

In PROG Mode Action

Result

1. Press [SEARCH]8<data address>

Finds the block transfer instruction

2. Press CANCEL COMMAND

Removes preceeding command

3. Press [DISPLAY]0 or 1

Displays the file in binary or BCD

4. Press [DISPLAY]001 and enter data

Puts cursor on word 1

5. Press [INSERT]

Publication 1771-6.5.130 Ć May 1999

Page 60

B–2

Programming Examples

Use the above procedure to enter the required words of the write block transfer instruction. Be aware that the block length will depend on the number of channels selected and whether alarming or user calibration are implemented. For example, the block may contain only 1 word if no alarming or user calibration are implemented, but may contain 27 words if using 8 inputs with alarming and user calibration. The PLC–2 family write block transfer data file should look like Figure B.1. Figure B.1 Write Block Transfer Data Transfer for a PLC-2 Family Processor

$-

-

PLC-3 Family Processors

-

Following is a sample procedure for entering data in the configuration words of the write block transfer instruction when using a PLC–3 processor. For a complete sample program, refer to Figure Figure 3.2. To enter data in the configuration words, follow these steps: Example: Enter the following rung for a write block transfer: !#

*0

$-

- -

-

F0003:0000 is the address of the write block transfer data file. You want to enter/examine word 1.

4