Page 109

Chapter

7

Troubleshooting

What This Chapter Contains This chapter describes the diagnostics provided by the LED diagnostic indicators on the 1771-SDN module’s front panel. For information about the Module Status Indicator Network Status Indicator Node/Error Code Indicator

Module Status Indicator

See page 7-1 7-2 7-2

The bicolor (green/red) Module Status LED indicates whether the 1771-SDN module has power and is functioning properly. Module Status Indicator

Module Status Indicator

Network Status Indicator

If the indicator is

Then

Take this action

Off

There is no power applied to the module.

Verify power connections and apply power.

Green

The module is operating normally.

No action required.

Flashing Green

The module is not configured.

Configure the module.

Flashing Red

There is an invalid configuration.

Verify DIP switch settings. Check configuration setup.

Red

The module has an unrecoverable fault.

Replace the module.

Top Part of Module

1

Publication 1771-UM118C-EN-P - June 2003

Page 110

7-2

Troubleshooting

Network Status Indicator

Each of the channels (1 and 2) on the 1771-SDN Scanner module has a bicolor (green/red) network status indicator that provides troubleshooting information about the channel’s communication links. Network Status Indicator

If the indicator is Then

Which indicates

Take this action

Off

The device has no power or the The channel is disabled for DeviceNet Power-up the module, provide network channel is disabled for communication. power to the channel, and be sure the communication due to a bus off channel is enabled in both the module condition, loss of network power, or configuration table and the module it has been intentionally disabled. command word.

Green

Normal operation.

Flashing Green

The two-digit numeric display for the The channel is enabled but no channel indicates an error code that communication is occurring. provides more information about the condition of the channel.

Flashing Red

The two-digit numeric display for the At least one of the slave devices in the Examine the failed device and the channel displays an error code that module’s scanlist table has failed to scanlist table for accuracy. provides more information about the communicate with the module. condition of the channel. The network has faulted.

Red

The communications channel has The module may be defective. failed. The two digit numeric display for the channel displays an error code that provides more information about the condition of the channel.

Node/Error Code Indicator Top of Module

All slave devices in the scanlist table None. are communicating normally with the module. Configure the scanlist table for the channel to add devices.

Reset the module. If failures continue, replace module.

Each channel also has a Node/Error Code indicator that displays numeric codes providing diagnostic information. The display flashes at approximately one second intervals, depending on network traffic. The following table summarizes the meanings of the numeric codes. Numeric Display Code Summary Numeric Description Code

Node/Error Code Indicator

Publication 1771-UM118C-EN-P - June 2003

Take this action

0 - 63

Normal operation. The numeric code is None. the 1771-SDN’s node address on the DeviceNet network.

70

Module failed Duplicate Node Address Change the module node address to check. another available one. The node address you selected is already in use on that channel.

71

Illegal data in scanlist table (node number alternately flashes).

72

Slave device stopped communicating Inspect the field devices and verify (node number alternately flashes). connections.

Reconfigure the scanlist table and remove any illegal data.

Page 111

Troubleshooting

7-3

Numeric Display Code Summary Numeric Description Code

Take this action

73

Device's identity information does not Verify that the correct device is at this match electronic key in scanlist table node number. Make sure that the device entry (node number alternately at the flashing node address matches flashes). the desired electronic key (vendor, product code, product type).

74

Data overrun on port detected.

Modify your configuration and check for invalid data. Check network communication traffic.

75

No scanlist is active in the module.

Enter a scanlist.

76

No direct network traffic for module detected.

None. The module hears other network communication.

77

Data size expected by the device does Reconfigure your module for the correct not match scanlist entry (node number transmit and receive data size. alternately flashes).

78

Slave device in scanlist table does not Add the device to the network, or delete exist (node number alternately the scanlist entry for that device. flashes).

79

Module has failed to transmit a message.

Make sure that your module is connected to a valid network. Check for disconnected cables. Verify baud rate.

80

Module is in IDLE mode.

Put PLC-5 in RUN mode. Enable RUN bit in module command register.

81

Module is in FAULT mode.

Check ladder program for cause of fault bits.

82

Error detected in sequence of Check scanlist table entry for slave fragmented I/O messages from device device to make sure that input and (node number alternately flashes). output data lengths are correct. Check slave device configuration.

83

Slave device is returning error responses when module attempts to communicate with it (node number alternately flashes).

Check accuracy of scanlist table entry. Check slave device configuration. Slave device may be in another master’s scanlist. Reboot slave device.

84

Module is initializing the DeviceNet channel.

None. This code clears itself once module attempts to initialize all slave devices on the channel.

85

Data size was incorrect for this device at runtime.

86

Device is producing zero length data (idle state) while channel is in Run Mode.

Check device configuration and slave node status.

87

The primary owner has not allocated the slave.

Put the primary owner on line.

88

This is not an error. At power-up and reset, the module displays all 14 segments of the node address and status display LEDs.

None.

• Slave device is transmitting incorrect length data. • Verifiy device is not configured for variable poll connection data • Try replacing the device

Publication 1771-UM118C-EN-P - June 2003

Page 112

7-4

Troubleshooting

Numeric Display Code Summary Numeric Description Code

Publication 1771-UM118C-EN-P - June 2003

Take this action • Put the slave device into configurable mode. • Check the slave’s EDS file to see if the slave is configured offline. • Check to see if the slave device has been replaced with an incompatible device.

89

Slave device initialization using Auto Device Replacement parameters failed.

90

User has disabled communication port. Reconfigure your module. Check the disable bit in the Module Command Register.

91

Bus-off condition detected on comm port. Module is detecting communication errors.

92

No network power detected on comm Provide network power. Make sure that port. module drop cable is providing network power to module comm port.

95

Application FLASH update in progress. None. Do not disconnect the module while application FLASH is in progress. You will lose any existing data in the module’s memory.

97

Module halted by user command.

Check ladder program for cause of fault bits.

98

Unrecoverable firmware failure.

Service or replace your module.

99

Unrecoverable hardware failure.

Service or replace your module.

Check DeviceNet connections and physical media integrity. Check system for failed slave devices or other possible sources of network interference.