PLC-5 DeviceNet Scanner Module 1771-SDN User Manual, pages 113 to 118
Pages 113 to 118 of 149: A - 1785-ENET Module Channel Configuration; B - Installing and Configuring the ControlNet Communications Driver
The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-SDN
Page 113
Appendix
A
1785-ENET Module Channel Configuration
Configuring the Communications Channel
Before you can communicate with the PLC-5 processor over an Ethernet network, you must configure the 1785-ENET module’s Ethernet communications channel and download the configuration to the PLC-5 processor. The following example describes how to do this using RSLogix 5 software. 1. Select Channel Configuration under the Controller folder in the Project window.
The Edit Channel Properties window will open.
192
1
168
1
1
Publication 1771-UM118C-EN-P - June 2003
Page 114
A-2
1785-ENET Module Channel Configuration
2. Select the Channel 3A tab. 3. Select Ethernet as the Channel Type. 4. Uncheck the BOOTP Enabled box to disable BOOTP. 5. Enter the IP Address you want to assign to the PLC-5 processor (e.g., 192.168.1.1). 6. Download the configuration to the processor, using a communications driver that was previously configured, (e.g, ControlNet or DH+). See chapter 6 for examples of downloading to the PLC-5 using these drivers.
Publication 1771-UM118C-EN-P - June 2003
Page 115
Appendix
B
Installing and Configuring the ControlNet Communications Driver
The examples using ControlNet in this manual were performed with a 1784-KTCX15 communication interface card installed in the personal computer that was used as a programming terminal. This appendix describes how to install and configure the 1784-KTCX15 card.
Installing the 1784-KTCX15 Communication Interface Card More
Perform the following steps to install the 1784-KTCX15 card in your personal computer. 1. Set the card’s base memory address location on switches S1 and S2.
For detailed information on installing the 1784-KTCX15, refer to the ControlNet Communication Interface Card Installation Instructions, publication number 1784-5.33. Front of Switches Front View D000:0000 Factory-set address (recommended setting)
up (1) S2
Side View down (0) S1 down (0)
up (1)
2. Set the card’s base I/O space address location on switch S3.
Front of Switches
Front View up (1)
240h shown (adjust for your system)
Side View down (0)
S3 up (1) down (0)
1
Publication 1771-UM118C-EN-P - June 2003
Page 116
B-2
Installing and Configuring the ControlNet Communications Driver
These settings depend on the devices installed on your computer. We used the following addresses: Base I/O Space Address Base Memory Address
240 D000:000 (factory default)
When deciding which addresses to use, remember that each card in your computer must have a unique base memory address and a unique base I/O space memory address. If another card in the host computer is using one or both of the selected addresses, you must change the card’s switch settings to an available address. TIP
Consult with your IT/PC support group to find out if it is necessary to change any of your computer’s memory address or IRQ settings.
3. Insert the card in a vacant 16- or 32-bit ISA/EISA expansion slot.
Configuring the 1784-KTCX15 Communications Driver After installing the card in the computer, you must run RSLinx to configure the driver. 1. Start RSLinx. 2. Select Configure Drivers from the Communications menu. The following window will appear:
3. Select the Allen-Bradley 1784-KT/KTC(X) device from the pull-down list and click on Add/New.
Publication 1771-UM118C-EN-P - June 2003
Page 117
Installing and Configuring the ControlNet Communications Driver
B-3
4. When prompted for a name for the new driver, select the default name assigned by the system, i.e., AB_KTC-1. The Configure Device window will appear:
5. Enter the following configuration: Station Name Net. Address Interrupt I/O Base Mem. Address
ABKTC 17(1) None 240(2) D000(2)
(1)
This is an unscheduled device. For maximum efficiency, set its address higher than the highest scheduled address on your network.
(2)
Modify as necessary for your system.
6. Click on OK to save your settings. 7. Close RSLinx.
Publication 1771-UM118C-EN-P - June 2003
Page 118
B-4
Installing and Configuring the ControlNet Communications Driver
Notes
Publication 1771-UM118C-EN-P - June 2003