Page 119

Appendix

C

Installing and Configuring the DH+ Communications Driver

The examples using Data Highway Plus (DH+) in this manual were performed with a 1784-KTX communication interface card installed in the personal computer that was used as the programming terminal. This appendix describes how to install and configure the 1784-KTX card.

Installing the 1784-KTX Communication Interface Card

Perform the following steps to install the 1784-KTX card in your personal computer. Refer to the following figure.

3456

3456

01 EF 2

01 EF 2

3456

KTX Card

789A

BCD

789A

BCD

01 EF 2

01 EF 2

More

For more information, see the KTX Communication Interface Card User Manual, publication number 1784-6.5.22.

789A

BCD

BCD

3456

SW3 SW4 789A

CH2 CH1

CH1 3456

3456

SW4 789A

BCD

SW3 789A

01 EF 2

(shown in IRQ5 position)

BCD

01 EF 2

3 4 5 7 9 10 11 12 15

D

7

Channel 1 Address shown in D700: position

1. Set the interrupt jumpers on the communication card (IRQ5 in this example). 2. Set the switches on the card (D700 in this example). 3. Insert the communication interface card into a vacant 16-bit ISA or EISA expansion slot and tighten the screw to secure the card.

1

Publication 1771-UM118C-EN-P - June 2003

Page 120

C-2

Installing and Configuring the DH+ Communications Driver

Configuring the 1784-KTX Communications Driver

After installing the card in the computer, you must run RSLinx to configure the communications driver. 1. Start the RSLinx software. 2. From the Communications menu select Configure Drivers. The Configure Drivers window will appear:

3. From the list of Available Drivers, select the 1784-KT/KTX(D)/PKTX(D) driver from the pull-down list and click on Add/New. 4. When prompted for a name for the new driver, select the default name assigned by the system, AB_KT-1. The device’s configuration window will open:

Publication 1771-UM118C-EN-P - June 2003

Page 121

Installing and Configuring the DH+ Communications Driver

C-3

5. Enter the following configuration: Device Type Network Station Name Station Number Board Address Interrupt(1) DH+ Speed (1)

KTX(D) DH+ RSLinx 0 D700 None 57.6K

Must match switch settings on card

6. Click on OK to save your settings. 7. Close RSLinx.

Publication 1771-UM118C-EN-P - June 2003

Page 122

C-4

Installing and Configuring the DH+ Communications Driver

Notes

Publication 1771-UM118C-EN-P - June 2003