PLC-5 DeviceNet Scanner Module 1771-SDN User Manual: 3 - Hardware Setup

Pages 39 to 52 of 149, from PLC-5 DeviceNet Scanner Module 1771-SDN User Manual

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-SDN

Page 39

Chapter

3

Hardware Setup What This Chapter Contains This chapter describes how to set up the hardware for the example application. The following table describes what this chapter contains and where to find specific information. For information about

Installing the 1770-KFD Interface Module

See page

Installing the 1770-KFD Interface Module

3-1

Installing the PLC-5 Processor

3-2

Installing the 1785-ENET Ethernet Module

3-5

Installing the 1771-SDN Scanner Module

3-6

Installing the Scanner Module in the Chassis

3-9

Connecting the Scanner to the DeviceNet Network

3-10

Installing the RediSTATION Operator Interface

3-11

Installing the Series 9000 Photoeye

3-12

How Your Example System Will Look

3-13

What’s Next?

3-13

Connect the RS-232 connector on the 1770-KFD interface module to one of the serial ports on your PC workstation (e.g., COM1). Connect the DeviceNet connector on the 1770-KFD module to a DeviceNet drop or trunk cable. You can make this connection in several ways; for example, using a DeviceNet Quad Tap (#1492-DN3TW), as shown on page 3-13. to PC COM 1

1770-KFD RS-232 Interface Module DeviceNet Dropline or Trunk Cable

More

1

For detailed directions on how to install the 1770-KFD interface module, see the DeviceNet RS-232 Interface Module Installation Instructions, publication 1770-5.6.

Publication 1771-UM118C-EN-P - June 2003

Page 40

3-2

Hardware Setup

Installing the PLC-5 Processor

Refer to the following figure while installing your PLC-5 processor. For additional installation requirements and detailed directions, refer to the document that shipped with your PLC-5 programmable controller. PLC-5C Processor and 1771 I/O Chassis

Locking Bar ControlNet Node Address Switches Lift Ejector Tab PLC-5/40C Processor

Battery Connector

Battery Cover

Card Guides DH+ Address Switches (on back)

Battery

Setting the I/O Chassis Backplane Switches O N

O FF

1 2 3 4

Set the backplane switches in the 1771 I/O chassis for 1-slot addressing for the example application. To do this, put switch 4 in the OFF position and switch 5 in the ON position.

5 6 7

Switches OFF

OFF

2 - slot

ON

OFF

ON

1 - slot

OFF

ON

OFF

1/2 - slot

ON

ON

Not Allowed

8

5

More

1771 I/O Chassis

Publication 1771-UM118C-EN-P - June 2003

Addressing

4

For information on setting the other backplane switches for your system, refer to the ControlNet PLC-5 Programmable Controllers User Manual Phase 1.5, publication 1785-UM022B-EN-P.

Page 41

Hardware Setup

3-3

Going Online to the PLC-5 Processor You cannot go online to the PLC-5 processor over DeviceNet. In order to download and run the example application program in chapter 6 you must use the processor’s RS-232 connector, or download and run the program via another network. Chapter 6 provides examples of downloading and running the application program via ControlNet, Ethernet, and Data Highway Plus networks. Chapter 5 provides examples of configuring the DeviceNet network over these networks. To go online to the PLC-5 processor via ControlNet: 1. Set the PLC-5C ControlNet node address using the two 10-digit rotary switches on top of the PLC-5C module. For the example application we used node address 16. ControlNet PLC-5C processor’s NET address = 16 20

2

30 40

1

00

50

0

90

60

9

10

80

70

3 4 5 6

8

7

2. Connect the PLC-5C’s ControlNet port to the ControlNet network. More

See Appendix B for information on installing and configuring the ControlNet driver. See the ControlNet 1.5 PLC-5 Programmable Controller User Manual, publication 1785-UM022B-EN-P, for further information.

Publication 1771-UM118C-EN-P - June 2003

Page 42

3-4

Hardware Setup

To go online to the PLC-5 processor via Data Highway Plus: 1. Define the DH+ station address of channel 1A by setting switch assembly SW-1 on the back of the processor. For the example application we used address 1. (Set switch 4 in the up position, and switches 1, 2, 3, 5, and 6 in the down position.) See the information on the side of the processor if you want to use another address.

TIP back view of processor Switch 4 in the “up” position side view down up

Switch 7 in the “up” position.

2. Set the baud rate to 57.6 Kbaud by placing switch 7 in the up position. More

Publication 1771-UM118C-EN-P - June 2003

See Appendix C for information on installing and configuring the Data Highway Plus driver.

Page 43

Hardware Setup

Installing the 1785-ENET Ethernet Module

3-5

To go online to the PLC-5 processor via Ethernet, you must install a 1785-ENET module in the 1771 I/O chassis. The Ethernet module is shipped with a 58-pin connector header that attaches to the PLC-5 processor. 1. Attach the connector header to the PLC-5 processor.

Status Indicator Transmit Indicator

Attach the interface module to this end.

Connector Header

Push the exposed pins into the holes on the PLC-5 processor.

IMPORTANT

External Transceiver Fuse

Channel 3A: 15-pin AUI Connector Port

Make sure you carefully align the pins and holes before you press the connector header into the processor. If you improperly align them, you will bend the connector header pins when you press them together. Do not use excessive force on the connector header when seating it into the processor. You do not need to key the connector.

2. Use the captive screws to connect the interface module to the processor.

Publication 1771-UM118C-EN-P - June 2003

Page 44

3-6

Hardware Setup

3. Insert the interface module/processor combination in the left-most slot of the 1771 I/O chassis.

!

Be sure power to the 1771 I/O chassis is OFF.

4. Assign an IP address to the interface module. 5. Configure channel 3A for Ethernet communication. You can configure the communication channel using BOOTP software or your PLC-5 programming software. See Appendix A for information on configuring the communication channel using RSLogix 5 programming software. TIP

More

Rockwell Automation offers a BOOTP tool on http://www.ab.com

For additional installation requirements and detailed directions, refer to the document that shipped with your 1785-ENET Ethernet module. .

Installing the 1771-SDN Scanner Module

Publication 1771-UM118C-EN-P - June 2003

Refer to the following figure as you install the 1771-SDN scanner module. For additional installation requirements and detailed directions, refer to publication 1771-IN014.

Page 45

Hardware Setup

3-7

Multi-position Switches - use to set the data rate, chassis addressing mode, and scanner node address for each channel. O N

1

2

O N

O N

3

4 5

6

7

8

1

2

3

4 5

6

7

8

1

2

= ON = 1 3

4 5

6

7

= OFF = 0

8

Module Status Indicator - indicates whether the device has power and is functioning properly.

MODULE STATUS

Reset Button - resets your module. RESET = ON = 1 = OFF = 0

CHANNEL 1 NETWORK STATUS NODE/ ERROR CODE

DeviceNet

Channel 1 Status Indicator - gives diagnostic indications for Channel 1.

Data Rate Switch Settings

Chassis Address Switch Settings

Node Address and Status Display displays numeric codes that indicate scanner node address, status and/or errors for Channel 1. DeviceNet Port 1 - use the color-coded header to wire your module. Channel 1 & 2 Node Address Switch Settings

CHANNEL 2 NETWORK STATUS NODE/ ERROR CODE

DeviceNet

Channel 2 Status Indicator - gives diagnostic indications for Channel 2. Node Address and Status Display displays numeric codes that indicate scanner node address, status and/or errors for Channel 2. DeviceNet Port 2 - use the color-coded header to wire your module. Left Side of Module

Allen-Bradley 1771-SDN

Publication 1771-UM118C-EN-P - June 2003

Page 46

3-8

Hardware Setup

Setting the Channel 1 Data Rate and Node Address Switches Channel 1 = ON = 1

O N

1

2

3

4 5

6

7

= OFF = 0

8

1. Locate the switchbank labeled “Channel 1” on the left side of the module. 2. Set the DeviceNet Data Rate for Channel 1 to 500K baud for the example application by setting switch 1 to an ON (“1”) position and switch 2 to an OFF (“0”) position. 3. Set the DeviceNet node address for Channel 1 to node 0 for the example application by setting switches 3 through 8 to the OFF (“0”) position. TIP

IMPORTANT

Refer to the table on the left side of the module to set the channel to a different node address. The address range is 0 to 63.

The node address setting must not conflict with the node address of any other device on the network. Note that channel 2 is not used for the example application.

Setting the I/O Chassis Addressing Node Switches Set the I/O chassis addressing mode to 1-slot for the example application.

Configuration = ON = 1

O N

1

2

3

4

5

6

7

8

= OFF = 0

1. Locate the switchbank labeled “Configuration” on the left side of the module. 2. Set switch 7 to an OFF (“0”) position and switch 8 to an ON (“1”) position. IMPORTANT

IMPORTANT

Publication 1771-UM118C-EN-P - June 2003

Make sure switches 1 through 6 in the Configuration switchbank always remain in the OFF (“0”) position.

The chassis addressing mode setting for the 1771 I/O chassis (page 3-2) must match the I/O chassis address setting of the scanner. If the switches do not match, data will be lost in the data transfer between the PLC-5 processor and the scanner module.

Page 47

Hardware Setup

3-9

Installing the Scanner Module in the Chassis

ATTENTION

!

Do not install the 1771-SDN Scanner Module with the chassis power supply on. Turn off the chassis power supply. You will disrupt backplane communication and may damage your module.

1. Select a slot for the 1771-SDN module in the chassis. You may use any slot except the leftmost slot, which is reserved for the PLC-5 processor. For the example application, we installed the scanner in slot 1. 2. Insert the 1771-SDN Scanner module into the slot.

Apply firm, even pressure to seat the module in the I/O chassis backplane connectors. More

For additional installation requirements and detailed directions, refer to the document that shipped with your 1771-SDN scanner module.

Publication 1771-UM118C-EN-P - June 2003

Page 48

3-10

Hardware Setup

Connecting the Scanner to the DeviceNet Network Do not wire your module with power applied to your network. You may short circuit your network or disrupt communication.

ATTENTION

!

To connect to the DeviceNet network: 1. Connect the DeviceNet drop line to the linear plug provided with the scanner. Match the wire insulation colors to the colors shown on the label. Module label shows wiring color scheme MODULE STATUS

RESET

CHANNEL 1 NETWORK STATUS

Front of Scanner Module

NODE/ ERROR CODE

RED

DeviceNet

WHITE CHANNEL 2 NETWORK STATUS NODE/ ERROR CODE

DeviceNet

BARE BLUE BLACK

2. Locate the DeviceNet port connector for Channel 1 on the front of the module. 3. Insert the linear plug into the five-pin header for Channel 1.

Channel 1 Port Connector

Dedicated DeviceNet Drop Line

Publication 1771-UM118C-EN-P - June 2003

Page 49

Hardware Setup

Installing the RediSTATION Operator Interface

3-11

Begin installing the RediSTATION by removing the six screws fastening the cover and setting the DIP switches inside as follows: Set this position

To this value:

1 2 3 4 5 6

1 1 1 0 0 0

On On On Off Off Off

(node address1)

7 8

0 1

Off On

(data rate2)

9 10

0 0

Off Off

The DeviceNet address is 000111 (node 7). The data rate is 10 (500k bps). The output fault rate is 0 (outputs turned off). The output flash rate is 0 (outputs tuned off). 1 2

More

See Chapter 2 of the RediSTATION Operator Interface User Manual, publication 2705-UM001A-EN-P, for complete information about setting the DIP switches to configure the node address, data rate, output flash rate, and output fault state. Refer to the following illustration as you connect the RediSTATION to the network. TIP

You do not need to disconnect incoming power from the DeviceNet network before connecting the RediSTATION.

The DeviceNet cable connects directly to the mini connector on the top of the RediSTATION enclosure or through the conduit opening (open style).

DeviceNet Cable mini connector open style

Publication 1771-UM118C-EN-P - June 2003

Page 50

3-12

Hardware Setup

Connect the photoeye to the network and configure the photoeye as follows:

Installing the Series 9000 Photoeye

• Node Address: 9 • Operating Mode: Light Operate (default) • Baud Rate: 500 kb Top View of Series 9000 Photoeye Programming Pushbutton Sensitivity Adjustment

Yellow - Output Green - Margin Red/Green - Status

More

For detailed directions, see the instructions that came with your photoeye. For a detailed example of node commissioning using RSNetWorx, refer to page 4-7 of this manual.

Publication 1771-UM118C-EN-P - June 2003

Page 51

Hardware Setup

How Your Example System Will Look

3-13

When you have finished installing all the devices, your example system should look similar to the one shown below:

PC running Windows NT or Windows 95/98, containing RSNetWorx for DeviceNet software

Series 9000 Photoelectric Sensor Node 9 1770-KFD Communication Module

PC Serial Port

1492-DN3TW Quad Tap Node 62 Node 0

PLC-5 Processor with 1771-SDN module in 1771 I/O chassis

IMPORTANT

What’s Next?

24V Node 7

RediSTATION Operator Interface

Make sure each end of your DeviceNet trunk cable is properly terminated with a resistor. Refer to the DeviceNet Cable Planning and Installation Manual, publication DN-6.7.2 for detailed information.

The next step is to configure the 1771-SDN module and perform I/O data mapping using RSNetWorx for DeviceNet software.

Publication 1771-UM118C-EN-P - June 2003

Page 52

3-14

Hardware Setup

Notes