Configuring the DeviceNet Network
What This Chapter Contains This chapter describes how to configure the DeviceNet network using RSLinx and RSNetWorx for DeviceNet software. The following table describes what this chapter contains and where to find specific information.
Installing the Software
For information about
See page
Installing the Software
4-1
Using RSLinx to Configure the DeviceNet Driver
4-2
Using RSNetWorx for DeviceNet to Configure the Scanlist
4-4
What’s Next?
4-17
Install the RSLinx and RSNetWorx software. 1. Insert the CD in the CD-ROM drive. Note: The CD-ROM supports Windows Autorun. Once inserted into the CD-ROM drive, if you have Autorun configured, the installation will automatically start at the first setup screen. If Autorun is not configured for your CD-ROM drive, go to step 2. 2. From the Start menu, choose Run. You will see the Run pop-up window. 3. Type d:/setup (if it doesn’t appear automatically), where d: is your CD-ROM driver letter. 4. Click on OK. You see the progress bar, followed by the welcome screen.
1
Publication 1771-UM118C-EN-P - June 2003
Page 54
4-2
Configuring the DeviceNet Network
Using RSLinx to Configure the DeviceNet Driver
After you install the software, you use RSLinx to configure your DeviceNet driver and RSNetWorx for DeviceNet to configure the network. 1. Start the RSLinx software.
2. From the Communications menu, select Configure Drivers. The Configure Drivers window will appear.
3. From the list of Available Drivers, select DeviceNet Drivers and click on Add/New. You will see the following list of drivers:
4. Select the Allen-Bradley 1770-KFD driver.
Publication 1771-UM118C-EN-P - June 2003
Page 55
Configuring the DeviceNet Network
4-3
The Allen-Bradley 1770-KFD Driver Configuration window will appear.
Your driver setup will vary according to your system setup (COM port, Data Rate, Node Address). Choose the appropriate settings for your system. We set the DeviceNet Port Setup Data Rate to 500K for the example application.
5. Configure the driver using the example above as a guide and click on OK. The software will take a few seconds to configure the driver. When it is done the following prompt will appear:
6. Select the default driver name 1770-KFD-1 and click on OK. 7. Close RSLinx. You will use the driver you just configured to browse and configure the network with RSNetWorx for DeviceNet.
Publication 1771-UM118C-EN-P - June 2003
Page 56
4-4
Configuring the DeviceNet Network
Using RSNetWorx for DeviceNet to Configure the Scanlist
Setting Up an Online Connection Follow the procedure below to set up an online connection to the DeviceNet network using the 1770-KFD driver. 1. Start RSNetWorx.
2. From the File menu, select New. If you have RSNetWorx for ControlNet installed on your computer you may see the following window. Otherwise, proceed to step 4.
3. Highlight DeviceNet Configuration and click on OK. 4. Click on the Online button
Publication 1771-UM118C-EN-P - June 2003 on the toolbar.
Page 57
Configuring the DeviceNet Network
4-5
The Browse for network window will appear. You will see the drivers you have configured on your system.
5. Select the 1770-KFD-1, DeviceNet driver and click on OK. You will be prompted to upload or download devices before going online.
6. Click on OK to go online and upload the network. RSNetWorx for DeviceNet will begin browsing for network devices. When the software is finished browsing, the network displayed on your screen should look similar to the one shown below.
Publication 1771-UM118C-EN-P - June 2003
Page 58
4-6
Configuring the DeviceNet Network
TIP
RSNetWorx for DeviceNet performs a one-shot browse when you go online or choose the browse feature. The software will poll for devices once and display the results. If a node which was online later goes offline, there will be no “live” indication in RSNetWorx. You must manually perform a browse to detect the missing node. To perform the browse, press the button.
Setting the 1771-SDN Node Address Once the devices are uploaded, their node addresses appear to the right of their icons. For the example application, the 1771-SDN scanner module should have a node address of “0” (or “00”). If you need to change a module’s node address, use the following procedure. TIP
You can use this procedure to change the node address of other devices on the network (e.g., the Photoeye). You can also change the network data rate (baud rate) of some devices. Power must be cycled for baud rate changes to take effect.
If “00” appears to the right of the 1771-SDN icon and you do not need to change the node address or baud rate of any device, skip the remainder of this section and go to “Configuring the I/O Devices” on page 4-9.
IMPORTANT
The network must not be active when performing node commissioning on the 1771-SDN module. Make sure the processor is in Program mode. (Note that this applies only to the 1771-SDN. You may commission other devices with the processor in Run mode.)
Publication 1771-UM118C-EN-P - June 2003
Page 59
Configuring the DeviceNet Network
4-7
To change the node address of a device perform the following steps: 1. From the Tools menu select Node Commissioning.
2. Click on the Browse button. You will see the Device Selection window.
3. Select the 1770-KFD-1 driver.
Publication 1771-UM118C-EN-P - June 2003
Page 60
4-8
Configuring the DeviceNet Network
The devices on the network will appear in the right panel.
4. Select the device from the right panel and click on OK. You will see the Node Commissioning window with the current settings for the device. Your window will look similar to the one shown below.
5. In the New Device Settings: Node Address box, enter the new node address (e.g., a 0 as shown above). 6. Click on Apply. 7. Click on Exit to close the window.
Publication 1771-UM118C-EN-P - June 2003
Page 61
Configuring the DeviceNet Network
4-9
Configuring the I/O Devices Next you must add the RediSTATION and the photoeye to the 1771-SDN’s scanlist, configure and/or verify their parameters, and map them to the PLC-5 processor’s memory. 1. Double-click on the 1771-SDN module icon.
The following window will appear:
2. Select the Module tab.
Publication 1771-UM118C-EN-P - June 2003