The text of a spec sheet · part 3 of 8
Stratix Ethernet Device Specifications, pages 19 to 27
Pages 19 to 27 of 72
The original document is the PDF (3.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1783-US08T
Page 19
Stratix Ethernet Device Specifications
Dimensions - Stratix 2500 Switches 1783-LMS5 Switch Dimensions 115. 0 mm (1.50 in)
38.1 mm (1.79 in.)
127.0 mm (5.0 in.)
134.5 mm 144.8 mm (5.29 in.) (5.70 in.)
32643-M
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
19
Page 20
Stratix Ethernet Device Specifications
1783-LMS8 Switch Dimensions 115. 0 mm (4.52 in)
45.7 mm (1.79 in.)
127.0 mm (5.0 in.)
134.5 mm 144.8 mm (5.29 in.) (5.70 in.)
32642-M
20
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
Page 21
Stratix Ethernet Device Specifications
Stratix 5400 Ethernet Managed Switches Cat. No.
Total Ports
RJ45 Ports(1)
Combo Ports
(PoE/PoE+)
SFP Slots
Firmware Type
CIP Sync (IEEE 1588)
NAT
DLR
1783-HMS4C4CGN
8, 4 FE + 4 GE, - Layer 2
Yes
Yes
Yes
1783-HMS8T4CGN
12
8 FE
4 GE, - Layer 2
Yes
Yes
Yes
1783-HMS8S4CGN
12, 4 GE, 8 FE
Layer 2
Yes
Yes
Yes
1783-HMS4T4E4CGN
12
4 FE
4 GE
4 FE, Layer 2
Yes
Yes
Yes
1783-HMS4S8E4CGN
16, 4 GE
8 FE
4 FE
Layer 2
Yes
Yes
Yes
1783-HMS16T4CGN
20
16 FE
4 GE, - Layer 2
Yes
Yes
Yes
1783-HMS8TG4CGN
12
8 GE
4 GE, - Layer 2
Yes
Yes
Yes
1783-HMS8SG4CGN
12, 4 GE, 8 GE
Layer 2
Yes
Yes
Yes
1783-HMS4EG8CGN
12, 8 GE
4 GE, Layer 2
Yes
Yes
Yes
1783-HMS4SG8EG4CGN
16, 4 GE
8 GE
4 GE
Layer 2
Yes
Yes
Yes
1783-HMS16TG4CGN
20
16 GE
4 GE, - Layer 2
Yes
Yes
Yes
1783-HMS8TG8EG4CGN
20
8 GE
4 GE
8 GE, Layer 2
Yes
Yes
Yes
1783-HMS8TG4CGR
12
8 GE
4 GE, - Layer 3
Yes
Yes
Yes
1783-HMS8SG4CGR
12, 4 GE, 8 GE
Layer 3
Yes
Yes
Yes
1783-HMS4EG8CGR
12, 8 GE
4 GE, Layer 3
Yes
Yes
Yes
1783-HMS4SG8EG4CGR
16, 4 GE
8 GE
4 GE
Layer 3
Yes
Yes
Yes
1783-HMS16TG4CGR
20
16 GE
4 GE, - Layer 3
Yes
Yes
Yes
1783-HMS8TG8EG4CGR
20
8 GE
4 GE
8 GE, Layer 3
Yes
Yes
Yes
(1) FE = Fast Ethernet; GE = Gigabit Ethernet.
Table 13 - Technical Specifications - Stratix 5400 Switches
1783-HMS8S4CGN, 1783-HMS8SG4CGN, 1783-HMS8SG4CGR
1783-HMS4T4E4CGN
1783-HMS4S8E4CGN, 1783-HMS8TG8EG4CGN, 1783-HMS4SG8EG4CGN, 1783-HMS4EG8CGN, 1783-HMS4SG8EG4CGR, 1783-HMS8TG8EG4CGR, 1783-HMS4EG8CGR
5.0 A max @ 12…54V DC
3.7 A max @ 12…54V DC
4.3 A max @ 12…54V DC
Attribute
1783-HMS8T4CGN, 1783-HMS16T4CGN, 1783-HMS8TG4CGN, 1783-HMS8TG4CGR
Alarm relay
1 A @ 30V DC or 0.5 A @ 48V DC
Power input
3.7 A max @ 12…54V DC
Power over Ethernet (PoE) input power, Power consumption(1)
35 W @ 24V DC @ 40 ˚C (104 ˚F)
40 W @ 24V DC @ 40 ˚C (104 ˚F)
42 W @ 24V DC @ 40 ˚C (104 ˚F)
35 W @ 24V DC @ 40 ˚C (104 ˚F) PoE power at 50V: 120 W
40 W @ 24V DC @ 40 ˚C (104 ˚F) PoE power at 50V: 124 W
Power dissipation
35 W
40 W
42 W
35 W
42 W
Isolation voltage
60V (continuous), basic insulation type, all ports to ground No isolation between individual ports Type tested at 500V AC for 60 s
Wire size, ground connection
4 mm2 (10 AWG) solid or stranded copper wire
1783-HMS4C4CGN, 1783-HMS16TG4CGN, 1783-HMS16TG4CGR
4.3 A max @ 12…54V DC
44…54V DC for PoE 50…54V DC for PoE+ or a combination of PoE and PoE+
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
21
Page 22
Stratix Ethernet Device Specifications
Table 13 - Technical Specifications - Stratix 5400 Switches (continued) 1783-HMS4S8E4CGN, 1783-HMS8TG8EG4CGN, 1783-HMS4SG8EG4CGN, 1783-HMS4EG8CGN, 1783-HMS4SG8EG4CGR, 1783-HMS8TG8EG4CGR, 1783-HMS4EG8CGR
Attribute
1783-HMS8T4CGN, 1783-HMS16T4CGN, 1783-HMS8TG4CGN, 1783-HMS8TG4CGR
Wire size, DC power connection
0.82…0.52 mm2 (18…20 AWG) solid or stranded copper wire rated at 30 ˚C (86 ˚F), or greater, above the surrounding air temperature 6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.) strip length
Wire size, alarm connection
0.5…0.8 mm2 (20…18 AWG) solid or stranded, UL/CSA-rated style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire, 6.3 mm(0.25 in.) ± 0.5 mm (0.02 in.) strip length
Screw torque,ground terminal
0.51 N•m (4.5 in•lb)
Screw torque, power terminal
0.56 N•m (5.0 in•lb)
Screw torque, alarm terminal
0.23 N•m (2.0 in•lb)
Weight, approx
2.88 kg (6.35 lb)
Wiring category(2)
3 - on console ports 2 - on DC power and alarm ports 2 - on Ethernet ports
Enclosure type rating
None (open-style)
Pilot duty rating
Alarm not rated
North American temp code
T3
ATEX temp code
T3
SFP modules(3)
1783-SFP100FX 1783-SFP100LX 1783-SFP100EXC 1783-SFP100ZXC 1783-SFP100T(4) 1783-SFP1GSX(5) 1783-SFP1GLX(5) 1783-SFP1GEXE(5) 1783-SFP1GZX(5) 1783-SFP1GTE(5)
Memory card replacement
1784-SD1
(1) (2) (3) (4) (5)
22
1783-HMS4C4CGN, 1783-HMS16TG4CGN, 1783-HMS16TG4CGR
1783-HMS8S4CGN, 1783-HMS8SG4CGN, 1783-HMS8SG4CGR
1783-HMS4T4E4CGN
For PoE configurations, the power consumption values listed represent the highest values that can be configured using all ports. A general guideline is 0.5 W per 30 W PoE+ port used. Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. For SFP specifications, see page 69. The 1783-SFP100T module requires Stratix 5400 firmware revision 3.001or later. Gigabit Ethernet (GE) SFP modules work only in GE SFP slots. For a list of Stratix 5400 catalog numbers with GE SFP slots, see page 21.
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
Page 23
Stratix Ethernet Device Specifications
Table 14 - Environmental Specifications - Stratix 5400 Switches Attribute
Stratix 5400 Switches
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-40…+70 °C (-40…+158 °F)
Temperature, surrounding air, max
70 °C (158 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…90% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
1 g @ 5…150 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
15 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions IEC 61000-6-4
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
20V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 20V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±3 kV at 5 @ 100 kHz on DC power ports ±3 kV at 5 @ 100 kHz on alarm ports ±3 kV at 5 @ 100 kHz on Ethernet ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on DC power ports ±1 kV line-line (DM) and ±2 kV line-earth (CM) on alarm ports ±2 kV line-earth(CM) on Ethernet ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Magnetic field immunity IEC 61000-4-8
300 A/m long duration and 1000 A/m short duration at 50 @ 60 Hz
Magnetic pulse immunity IEC 61000-4-9
300 A/m pulse
Voltage variation IEC 61000-4-29
10 ms interruption on DC power ports
Damped oscillatory wave immunity IEC 61000-4-18
±1 kV line-line (DM) and ±2.5 kV line-earth (CM) on power and alarm ports ±2.5 kV line-earth (CM) on Ethernet ports
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
23
Page 24
Stratix Ethernet Device Specifications
Table 15 - Certifications - Stratix 5400 Switches Certifications (when product is marked)(1)
Stratix 5400 Switches c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. UL Listed for Class I, Zone 2 Hazardous Locations, certified for U.S. and Canada. See UL File E194810. Ex nA nC IIC T3 Gc X AEx nA nC IIC T3 Gc
CE
European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2011/65/EU RoHS, compliant with: • EN 50581; Technical Documentation
RCM
Australian Radiocommunications Act, compliant with: ACMA EMC Std 08
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • II 3 G Ex nA nC IIC T3 Gc • DEMKO14ATEX1423X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at http://www.ab.com for declarations of conformity, certificates, and other certification details.
Dimensions - Stratix 5400 Switches To prevent the switch from overheating, observe the following minimum clearances: • Top and bottom: 50.8 mm (2.0 in.) • Sides: 50.8 mm (2.0 in.) • Front: 50.8 mm (2.0 in.) These diagrams are representative of the Stratix 5400 switches. Actual faceplates vary depending on the catalog number. 1.75 cm (0.69 in.)
15.54 cm (6.12 in.)
12.92 cm (5.09 in.)
R
15.54 cm (6.12 in.)
16.45 cm (6.48 in.)
1.24 cm (0.49 in.)
24
13.03 cm (5.13 in.)
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
Page 25
Stratix Ethernet Device Specifications
Stratix 5410 Ethernet Managed Switches CIP Sync (IEEE 1588)
NAT
Power supply(3)
Conformal Coating
12 GE + 4 GE only Layer 2
Yes
Yes
Low DC, 12 GE
12 GE + 4 GE only Layer 2
Yes
Yes
AC/High DC, 28
12 GE
12 GE + 4 TEN
Layer 2
Yes
Yes
Low DC
Yes
1783-IMS28NAC
28
12 GE
12 GE + 4 TEN
Layer 2
Yes
Yes
AC/High DC
Yes
1783-IMS28GRDC
28
12 GE
12 GE + 4 GE only Layer 3
Yes
Yes
Low DC, 1783-IMS28GRAC
28
12 GE
12 GE + 4 GE only Layer 3
Yes
Yes
AC/High DC, 1783-IMS28RDC
28
12 GE
12 GE + 4 TEN
Layer 3
Yes
Yes (Layer 2)
Low DC
Yes
28
12 GE
12 GE + 4 TEN
Layer 3
Yes
Yes (Layer 2)
AC/High DC
Yes
Cat. No.
Total Ports
(PoE/PoE+)
SFP Slots(2)
1783-IMS28GNDC
28
12 GE
1783-IMS28GNAC
28
1783-IMS28NDC
1783-IMS28RAC
Firmware Type
(1)
Optional Power Supplies 1783-IMXDC
Low DC
1783-IMXAC
AC/High DC
(1) The switch supports an optional second power supply of any voltage type to provide redundancy and additional power for PoE devices. One power supply provides 60 W for PoE/PoE+. Two power supplies provide 185 W for PoE/PoE+. (2) GE = 100 Megabit/1 Gigabit Ethernet; GE only = 1 Gigabit Ethernet; TEN = 1/10 Gigabit Ethernet (3) One power supply ships pre-installed in each Stratix 5410 switch.
Table 16 - Technical Specifications - Stratix 5410 Switches Attribute
1783-IMS28NDC, 1783-IMS28RDC, 1783-IMS28GNDC, 1783-IMS28GRDC
Alarm relay
30V DC, 1 A or 48V DC, 0.5 A
Power input
24…60V DC, 10 A
PoE output
1783-IMS28NAC, 1783-IMS28RAC, 1783-IMS28GNAC, 1783-IMS28GRAC
100…240V AC, 2 A, 50…60 Hz (per slot) or 100…250V DC, 2 A (per slot)
54V DC, 15.4 W max (1)
PoE+ output
54V DC, 30 W max One power supply installed: No PoE ports on: 74 W @ 24V DC @ 40˚C (104˚F), 76 W max 4 PoE ports on, 148 W max: 145 W @ 24V DC @ 40˚C (104˚F)
Power consumption(2)
Two power supplies installed: PoE power consumption alone (12 ports PoE): 210 W@ 24V DC @ 40˚C (104˚F); 215 W max
One power supply installed: No PoE ports on: 74 W @ 120V,60Hz / 230V, 50Hz AC @ 40˚C (104˚F), 76W max 4 PoE ports on, 148 W max: 145W @ 120V,60Hz / 230V, 50Hz AC @ 40˚C (104˚F) Two power supplies installed: PoE power consumption alone (12 ports PoE): 210 W@120V, 60Hz/230V, 50 Hz AC @ 40˚C (104˚F); 215 W max
Complete system power, including 12 ports PoE: 291 W max Complete system power, including 12 ports PoE: 291 W max Power dissipation
100 W
100 W
Isolation voltage
60V (continuous), basic insulation type Type tested at 3000 V DC for 60 s AC input power to alarm output AC input power to Ethernet ports AC input power to console port AC input power to ground
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
25
Page 26
Stratix Ethernet Device Specifications
Table 16 - Technical Specifications - Stratix 5410 Switches (continued) Attribute
1783-IMS28NDC, 1783-IMS28RDC, 1783-IMS28GNDC, 1783-IMS28GRDC
Wire size, Ethernet connection
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702
Wire size, ground connection
13.3 mm2 (6 AWG) solid or stranded copper wire
Wire size, alarm connection
Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702
Wire size, power supply
3.3mm2 (12 AWG) twisted-pair copper wire
Wiring category(3)
3 - on console ports 2 - on power and alarm ports 2 - on Ethernet ports
Wire type
Copper
Pilot duty rating
Alarm not rated
North American temp code
T4
ATEX temp code
T4
Screw torque, power supply mount
0.904…1.13 N•m (8…10 in•lb)
Screw torque, power terminal
0.96 N•m (± 0.06 N•m) or 8.5 in•lb (± 0.5 in•lb)
Screw torque, ground terminal
3.39 N•m (± 0.23 N•m) or 30 in•lb (± 2 in•lb)
Weight, approx, switch with power supply, power supply blank, and SD card
7.30 kg (16.1 lb)
Weight, approx, power supply only
1.179 kg (2.6 lb)
Weight, approx, accessory kit
0.18 kg (0.4 lb)
Enclosure type rating
None (open-style)
SFP modules(4)
1783-SFP100FX 1783-SFP100LX 1783-SFP100EXC 1783-SFP100ZXC 1783-SFP100T(5) 1783-SFP1GSX 1783-SFP1GLX 1783-SFP1GEXE 1783-SFP1GZX 1783-SFP10GSRE 1783-SFP10GLRE 1783-SFP1GTE
Memory card replacement
1784-SD1
(1) (2) (3) (4) (5)
26
1783-IMS28NAC, 1783-IMS28RAC, 1783-IMS28GNAC, 1783-IMS28GRAC
1.3mm2 (16 AWG) twisted-pair copper wire
A second power supply is required to support PoE+. For PoE configurations, the power consumption values listed represent the highest values that can be configured using all ports. A general guideline is 0.5 W per 30 W PoE+ port used. Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. SFP modules are supported only on switches with combo ports or SFP slots. For SFP specifications, see page 69. The 1783-SFP100T module requires Stratix 5410 firmware revision 3.001or later.
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
Page 27
Stratix Ethernet Device Specifications
Table 17 - Environmental Specifications - Stratix 5410 Switches Attribute
Stratix 5410 Switches
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-40…+60 °C (-40…+140 °F)
Temperature, ambient, max
60 °C (140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
1 g @ 5…150 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
15 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions IEC 61000-6-4
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Magnetic field immunity IEC 61000-4-8
30 A/m long duration and 300 A/m short duration at 50 Hz and 60 Hz
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on signal ports ±2 kV at 5 kHz on communication ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±500V line-line(DM) and ±1 kV line-earth(CM) on signal ports ±2 kV line-earth(CM) on communication ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Voltage variation IEC 61000-4-11
30% dips for 10 ms and 500 ms on AC supply ports 60% dips for 100 ms, 200 ms, and 1 s on AC supply ports 100% dips for 10 ms and 5 s on AC supply ports
Damped oscillatory wave immunity IEC 61000-4-18
±500V line-line(DM) and ±1 kV line-earth (CM) on signal ports ±1 kV line-line(DM) and ±2.5 kV line-earth (CM) on power ports ±500V line-earth(CM) on communication ports
Environmental rating
IP30
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
27