The text of a spec sheet · part 4 of 8
Stratix Ethernet Device Specifications, pages 28 to 36
Pages 28 to 36 of 72
The original document is the PDF (3.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1783-US08T
Page 28
Stratix Ethernet Device Specifications
Table 18 - Certifications - Stratix 5410 Switches Certifications (when product is marked)(1)
Stratix 5410 Switches c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. UL Listed for Class I, Zone 2 Hazardous Locations, certified for U.S. and Canada. See UL File E194810. • Class 1, Zone 2, Ex nA nC IIC T4 Gc X • Class 1, Zone 2, AEx nA nC IIC T4 Gc
CE
European Union 1999/5/EC R&TTE Directive, compliant with: • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 300 440-2 V1.4.1; ERM, SRD • EN 301 489-1 V1.9.2; ERM, EMC • EN 301 489-3 V1.6.1; ERM, EMC, SRD • EN 60950-1; Information Technology Equipment European Union 2011/65/EU RoHS, compliant with: • EN 50581; Technical Documentation
RCM
Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-0; General Requirements • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • Ex nA nC IIC T4 Gc • DEMKO15ATEX1492X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
RED
Hereby, Rockwell Automation declares that the radio equipment type Stratix 5410 is in compliance with Directive 2014/53/EU. The full text of the EU Declaration of Conformity is available at the following internet address: www.rockwellautomation.com
(1) See the Product Certification link at http://www.ab.com for declarations of conformity, certificates, and other certification details.
28
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
Page 29
Stratix Ethernet Device Specifications
Dimensions - Stratix 5410 Switches To prevent the switch from overheating, observe the following minimum clearances: • Top and bottom: 44.45 mm (1.75 in.) • Sides: 50.8 mm (2.0 in.) • Front: 50.8 mm (2.0 in.) These diagrams are representative of the Stratix 5410 switches. Actual faceplates vary depending on the catalog number.
44.5 cm (17.75 in.) 1 2
3
4
5 6
1
7 8 9 10 11 12 25 26
2
4
10/100/1000 PoE+
5
8
9
12
Disp. Mode
PoE
DLR
2
PRP
1
Out
1
Speed
Duplex
GPS
4
Setup
3
EIP Net
TimeCD
13 14 15 16 17 18 19 20 21 22 23 24 27 28 EIP Mod
4.45 cm (1.75 in.)
IN
IN
OUT
OUT
GPS ANT.
DIG.TimeCode
ANA.TimeCode
25
100/1000 SFP+
28
TOD
Express Setup
Alarms PSU
13
16
17
100/1000 SFP
20
21
24
Console
Alarm
35.6 cm (14.0 in.)
32564-M
46.53 cm (18.32 in.) 1
3.18 cm (1.25 in.)
2
3
4
5
6
7
8
4
5
10/100/1000 PoE+
8
9
12
IN
Disp. Mode
IN
OUT
PoE
PRP
DLR
Duplex
Out
2 1
2 4
Alarms PSU
Speed
1 3
TimeCD
GPS
Setup
EIP Net
EIP Mod
1
9 10 11 12 25 26
13 14 15 16 17 18 19 20 21 22 23 24 27 28
OUT
GPS ANT.
DIG.TimeCode
ANA.TimeCode
25
100/1000 SFP+
28
TOD
Express Setup
13
16
17
100/1000 SFP
20
21
24
.61 cm (.24 in.)
Console
Alarm
32565-M
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
29
Page 30
Stratix Ethernet Device Specifications
3.28 cm (1.29 in.) 0.56 cm (0.22 in.) 3.63 cm (1.43 in.)
3.63 cm (1.43 in.)
53.8 cm (21.18 in.) 46.53 cm (18.32 in.)
16.59 cm (6.53 in.)
17.66 cm (6.95 in.) 32564-M
30
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
Page 31
Stratix Ethernet Device Specifications
Stratix 5700 Ethernet Managed Switches Cat. No.
Total Ports
RJ45 Ports(1) Combo Ports
(PoE/PoE+)
SFP Slots
Firmware Type
CIP Sync NAT (IEEE 1588)
DLR
Conformal Coating
1783-BMS4S2SGL
6, - - 4 FE + 2 GE
Lite, - - - 1783-BMS4S2SGA
6, - - 4 FE + 2 GE
Full, - - - 1783-BMS06SL
6
4 FE, - 2 FE
Lite, - - - 1783-BMS06SA
6
4 FE, - 2 FE
Full, - - - 1783-BMS06TL
6
6 FE, - - Lite, - - - 1783-BMS06TA
6
6 FE, - - Full, - - - 1783-BMS06SGL
6
4 FE, - 2 GE
Lite, - - - 1783-BMS06SGA
6
4 FE, - 2 GE
Full, - - - 1783-BMS06TGL
6
4 FE + 2 GE, - - Lite, - - - 1783-BMS06TGA
6
4 FE + 2 GE, - - Full, - - - 1783-BMS10CL
10
8 FE
2 FE, - Lite, - - - 1783-BMS10CA
10
8 FE
2 FE, - Full, - - - 1783-BMS10CGL
10
8 FE
2 GE, - Lite, - - - 1783-BMS10CGA
10
8 FE
2 GE, - Full, - - - 1783-BMS10CGP
10
8 FE
2 GE, - Full
Yes, Yes, 1783-BMS10CGN
10
8 FE
2 GE, - Full
Yes
Yes
Yes, 1783-BMS12T4E2CGL
18
12 FE
2 GE
4 FE, Lite, - Yes, 1783-BMS12T4E2CGP
18
12 FE
2 GE
4 FE, Full
Yes, Yes, 1783-BMS12T4E2CGNK 18
12 FE
2 GE
4 FE, Full
Yes
Yes
Yes
Yes
1783-BMS20CL
20
16 FE
2 FE, 2 FE
Lite, - Yes, 1783-BMS20CA
20
16 FE
2 FE, 2 FE
Full, - Yes, 1783-BMS20CGL
20
16 FE
2 GE, 2 FE
Lite, - Yes, 1783-BMS20CGP
20
16 FE
2 GE, 2 FE
Full
Yes, Yes, 1783-BMS20CGN
20
16 FE
2 GE, 2 FE
Full
Yes
Yes
Yes, 1783-BMS20CGPK
20
16 FE
2 GE, 2 FE
Full
Yes, Yes
Yes
(1) FE = Fast Ethernet; GE = Gigabit Ethernet.
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
31
Page 32
Stratix Ethernet Device Specifications
Table 19 - Technical Specifications - Stratix 5700 Switches 1783-BMS10CL, 1783-BMS10CA, 1783-BMS10CGL, 1783-BMS10CGA
1783-BMS20CL, 1783-BMS20CA, 1783-BMS10CGN, 1783-BMS20CGL, 1783-BMS10CGP 1783-BMS20CGP, 1783-BMS20CGN, 1783-BMS20CGPK
Attribute
1783-BMS06SL, 1783-BMS06SA, 1783-BMS06TL, 1783-BMS06TA, 1783-BMS06SGL, 1783-BMS06SGA, 1783-BMS06TGL, 1783-BMS06TGA
Alarm relay
1 A @ 30V DC or 0.5 A @ 48V DC
Power input
0.5…2.0 A max @ 12…48V DC Class 2/SELV
Power consumption
9.5 W @ 24V DC @ 40 °C (104 °F) 15 W max
12.5 W @ 24V DC/ 40 °C (104 °F) 17 W max
Power dissipation
15 W
17 W
Isolation voltage
50V (continuous), basic insulation type, DC power ports to ground, DC power ports to Ethernet ports, and DC power ports to alarm ports No isolation between individual Ethernet ports No isolation between console port and system Type tested at 850V DC for 60 s
60V (continuous), basic insulation type, DC power ports to ground, alarm ports to ground, and DC power ports to alarm ports No isolation between console port and system Type tested at 707V DC for 60 s
Wire size, Ethernet connection(1)
RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702, Wire size, DC power connection
0.5…0.8 mm2 (20…18 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max, 6.3 mm (0.25 in.) ±0.5 mm (0.02 in.) strip length
Wire size, alarm connection
0.5…0.8 mm2 (20…18 AWG) solid or stranded, UL/CSA-rated style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire, 6.3 mm (0.25 in.) ±0.5 mm (0.02 in.) strip length
Wire size, ground connection
4.0 mm2 (12 AWG) min, stranded copper wire
Screw torque, power and alarm terminals
0.23 N•m (2.0 in•lb)
0.23 N•m (2.0 in•lb)
Screw torque, ground terminal, max
0.96 N•m (8.5 in•lb)
0.4 N•m (3.5 in•lb)
Weight, approx
1.11 kg (2.45 lb)
Wiring category(2)
3 - on console and alarm ports 2 - on DC power ports 2 - on Ethernet ports
Enclosure type rating
None (open-style)
Pilot duty rating
Alarm not rated
North American temp code
T4
IEC temp code
T4
32
1.25 kg (2.75 lb)
1783-BMS4S2SGL, 1783-BMS4S2SGA
0.5…3.0 A max @ 12…48V DC Class 2/SELV
0.5…2.0 A max @ 12…48V DC Class 2/SELV
15 W @ 24V DC/ 40 °C (104 °F) 20 W max
21 W @ 24V DC/40 °C (104 °F) 30 W max
12.5 W @ 24V DC/40 °C (104 °F) 14 W max
20 W
30 W
14 W
1.38 kg (3.05 lb)
2.04 kg (4.50 lb)
1.22 kg (2.69 lb) 3 - on console ports 2 - on DC power and alarm ports
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
Page 33
Stratix Ethernet Device Specifications
Table 19 - Technical Specifications - Stratix 5700 Switches (continued) 1783-BMS10CL, 1783-BMS10CA, 1783-BMS10CGL, 1783-BMS10CGA
Attribute
1783-BMS06SL, 1783-BMS06SA, 1783-BMS06TL, 1783-BMS06TA, 1783-BMS06SGL, 1783-BMS06SGA, 1783-BMS06TGL, 1783-BMS06TGA
SFP modules(3)
1783-SFP100FX 1783-SFP100LX 1783-SFP100EXC 1783-SFP100ZXC 1783-SFP100T(4) 1783-SFP1GSX(5) 1783-SFP1GLX(5) 1783-SFP1GEXE(5) 1783-SFP1GZX(5) 1783-SFP1GTE(5)
Memory card
1784-SD1
Industry standards
Substation KEMA (IEEE 1613, IEC 61850 - 3) IEEE 1613 Electric Power Stations Communications Networking IEC 61850-3 Electric Substations Communications Networking
(1) (2) (3) (4) (5)
1783-BMS20CL, 1783-BMS20CA, 1783-BMS10CGN, 1783-BMS20CGL, 1783-BMS10CGP 1783-BMS20CGP, 1783-BMS20CGN, 1783-BMS20CGPK
1783-BMS4S2SGL, 1783-BMS4S2SGA
See page 71 for recommended products. Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. SFP modules are supported only on switches with combo ports or SFP slots. For SFP specifications, see page 69. The 1783-SFP100T module requires Stratix 5700 firmware revision 8.001or later. Gigabit Ethernet (GE) SFP modules work only in GE SFP slots. For a list of Stratix 5700 catalog numbers with GE SFP slots, see page 31.
Table 20 - Environmental Specifications - Stratix 5700 Switches
Attribute
1783-BMS06SL, 1783-BMS06SA, 1783-BMS06TL, 1783-BMS06TA, 1783-BMS06SGL, 1783-BMS06SGA, 1783-BMS06TGL, 1783-BMS06TGA, 1783-BMS10CL, 1783-BMS10CA, 1783-BMS10CGL, 1783-BMS10CGA, 1783-BMS10CGN, 1783-BMS10CGP, 1783-BMS20CL, 1783-BMS20CA, 1783-BMS20CGL, 1783-BMS20CGP, 1783-BMS20CGN, 1783-BMS20CGPK
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-40…+60 °C (-40…+140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
55 g
1783-BMS4S2SGL, 1783-BMS4S2SGA
50 g
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
33
Page 34
Stratix Ethernet Device Specifications
Table 20 - Environmental Specifications - Stratix 5700 Switches (continued)
Attribute
1783-BMS06SL, 1783-BMS06SA, 1783-BMS06TL, 1783-BMS06TA, 1783-BMS06SGL, 1783-BMS06SGA, 1783-BMS06TGL, 1783-BMS06TGA, 1783-BMS10CL, 1783-BMS10CA, 1783-BMS10CGL, 1783-BMS10CGA, 1783-BMS10CGN, 1783-BMS10CGP, 1783-BMS20CL, 1783-BMS20CA, 1783-BMS20CGL, 1783-BMS20CGP, 1783-BMS20CGN, 1783-BMS20CGPK
Emissions CISPR11 (IEC 61000-6-4)
Class A
ESD immunity IEC 61000-4-2
8 kV contact discharges 15 kV air discharges
Radiated RF immunity IEC 61000-4-3
20V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 20V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz 20V/m with 200 Hz 50% pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 1000…2700 MHz 20V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz and ±2 kV at 100 kHz on DC power ports ±4 kV at 2.5 kHz, ±2 kV at 5 kHz, and ±1 kV at 100 kHz on alarm ports ±4 kV at 2.5 kHz, ±2 kV at 5 kHz, and ±1 kV at 100 kHz on Ethernet ports
±4 kV at 2.5, 5, and 100 kHz on DC power ports ±4 kV at 2.5, 5, and 100 kHz on alarm ports
±1 kV line-line (DM) and ±2 kV line-earth (CM) on DC power ports ±2 kV line-earth (CM) on Ethernet ports
±1 kV line-line (DM) and ±2 kV line-earth (CM) on DC power ports ±1 kV line-line (DM) and ±2 kV line-earth (CM) on alarm ports
Surge transient immunity IEC 61000-4-5
1783-BMS4S2SGL, 1783-BMS4S2SGA
6 kV contact discharges 8 kV air discharges
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Magnetic field immunity IEC 61000-4-8, 300A/m long duration at 50 and 60 Hz 1000A/m short duration at 50 and 60 Hz
Magnetic pulse immunity IEC 61000-4-9, 300A/m pulse
Voltage variation IEC 61000-4-29
10 ms interruption on DC power ports
Damped oscillatory wave immunity IEC 61000-4-18
±1 kV line-line (DM) and ±2.5 kV line-earth (CM) on power ports
Environmental rating
IP30
34
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
±1 kV line-line (DM) and ±2.5 kV line-earth (CM) on DC power ports at 1 MHz and 100 kHz ±1 kV line-line (DM) and ±2.5 kV line-earth (CM) on alarm ports at 1 MHz and 100 kHz
Page 35
Stratix Ethernet Device Specifications
Stratix 5700 Power over Ethernet Switches Table 21 - Technical Specifications - Stratix 5700 Power over Ethernet Switches Attribute
1783-BMS12T4E2CGL, 1783-BMS12T4E2CGP, 1783-BMS12T4E2CGNK
Ethernet data rate
10/100 Mbps
Alarm relay
30V DC, 1 A or 48V DC, 0.5 A
Power input
12...48V DC, 0.5…3.0 A max , Class 2/SELV
Power over Ethernet input power Power consumption
(1)
48V DC for PoE; 54V DC for PoE+ or a combination of PoE and PoE+ 15 W @ 24V DC 40 °C (104 °F), 30 W max
Power dissipation
30 W
Isolation voltage
60V (continuous), basic insulation type, DC power ports to ground, and PoE power ports to ground No isolation between individual Ethernet ports No isolation between PoE power and Ethernet ports No isolation between console port and system Type tested at 1585V DC for 60 s
Wire size, Ethernet connection(2)
RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702
Wire size, DC power connection
0.5…0.8 mm2 (20…18 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max, 6.3 mm (0.25 in.) ±0.5 mm (0.02 in.) strip length
Wire size, alarm connection
0.5…0.8 mm2 (20…18 AWG) solid or stranded, UL/CSA-rated style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire, 6.3 mm (0.25 in.) ±0.5 mm (0.02 in.) strip length
Wire size, ground connection
4.0 mm2 (12 AWG) min, stranded copper wire
Screw torque, power and alarm terminals 0.23 N•m (2.0 in•lb) Screw torque, ground terminals, max
0.96 N•m (8.5 in•lb)
Weight, approx
1.11 kg (2.45 lb)
Wiring category(3)
3 - on console and alarm ports 2 - on DC power ports 2 - on Ethernet ports
Pilot duty rating
Alarm not rated
Enclosure type rating
None (open-style)
North American temp code
T4
IEC temp code
T4
SFP modules(4)
1783-SFP100FX 1783-SFP100LX 1783-SFP100EXC 1783-SFP100ZXC 1783-SFP100T(5) 1783-SFP1GSX(6) 1783-SFP1GLX(6) 1783-SFP1GEXE(6) 1783-SFP1GZX(6) 1783-SFP1GTE(6)
Memory card
1784-SD1
Industry standards
Substation KEMA (IEEE 1613, IEC 61850 - 3) IEEE 1613 Electric Power Stations Communications Networking IEC 61850-3 Electric Substations Communications Networking
(1) (2) (3) (4) (5) (6)
For PoE configurations, the power consumption values listed represent the highest values that can be configured using all ports. A general guideline is 0.5 W per 30 W PoE+ port used. See page 71 for recommended products. Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. SFP modules are supported only on switches with combo ports or SFP slots. For SFP specifications, see page 69. The 1783-SFP100T module requires Stratix 5700 firmware revision 8.001or later. Gigabit Ethernet (GE) SFP modules work only in GE SFP slots. For a list of Stratix 5700 catalog numbers with GE SFP slots, see page 31.
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018
35
Page 36
Stratix Ethernet Device Specifications
Table 22 - Environmental Specifications - Stratix 5700 Power over Ethernet Switches Attribute
1783-BMS12T4E2CGL, 1783-BMS12T4E2CGP, 1783-BMS12T4E2CGNK
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-40…+60 °C (-40…+140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR11 (IEC 61000-6-4)
Class A
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 1000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on DC power ports ±4 kV at 5 kHz on alarm ports ±4 kV at 5 kHz on Ethernet ports
Surge transient immunity IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on DC power ports ±2 kV line-earth (CM) on Ethernet ports
Conducted RF immunity IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Damped oscillatory wave immunity IEC 61000-4-18
±1 kV line-line (DM) and ±2.5 kV line-earth (CM) on power ports
36
Rockwell Automation Publication 1783-TD001T-EN-P - July 2018