Page 46

Stratix Ethernet Device Specifications

Stratix 6000 Ethernet Managed Switches Table 27 - Technical Specifications - Stratix 6000 Switches Attribute

1783-EMS08T

1783-EMS04T

Description

Stratix 6000 managed switch • 8 ports • 1 fiber SFP slot

Stratix 6000 managed switch 4 ports

Power input

250 mA @ 24V DC (12…48V DC) CL 2/SELV

100 mA @ 24V DC (12…48V DC) CL 2/SELV

Power dissipation, max

5.8 W

2.6 W

Thermal dissipation, max

24.6 BTU/hr @ 60 °C (140 °F)

Network ports

8 RJ45 10/100 full/half duplex ports, optional SFP transceiver port

Protocols

TCP/IP, EtherNet/IP, Telnet, Http, DHCP, BOOTP, FTP, IGMP, SMTP

Indicators

16 port indicators 3 status indicators

EtherNet/IP features

MAC ID management, bandwidth alarming, port control, link status, scaled bandwidth information, and connections active

Switch features

VLAN, IGMP snooping, IGMP query V1 and V2, DHCP server, BOOTP server, QoS, port mirroring

IGMP snooping, IGMP query V1 and V2, DHCP server, BOOTP server, QoS, port mirroring

Options

1 GB fiber-optic transceiver, Inrush current, max

2.2 A

Isolation voltage

50V (continuous), basic insulation type, power to ground and power to network channels No isolation between individual network channels Routine tested at 707V AC for 1 s

Wire size, Ethernet connection(1)

RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702

Wire size, DC power connection

0.33…3.3 mm2 (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max

Wire size, ground connection

3.3 mm2 (12 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater

Screw torque, power and ground terminals

1.36 N•m (12 in•lb)

Wiring category(2)

2 - on DC power ports 2 - on communication ports

Enclosure type rating

None (open-style)

North American temp code

T4

ATEX temp code

T4

SFP modules(3)

1783-SFP1GSX 1783-SFP1GLX

4 RJ45 10/100 full/half duplex ports

8 port indicators 2 status indicators

(1) See page 71 for recommended products. (2) Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (3) SFP modules are supported only on switches with combo ports or SFP slots. For SFP specifications, see page 69.

46

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

Page 47

Stratix Ethernet Device Specifications

Table 28 - Environmental Specifications - Stratix 6000 Switches Attribute

1783-EMS04T, 1783-EMS08T

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F)

Temperature, ambient, max

60 °C (140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock)

15 g

Nonoperating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Emissions IEC 61000-6-4

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±2 kV at 5 kHz on power ports ±1 kV at 5 kHz on communication ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on AC power ports ±2 kV line-earth (CM) on communication ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Magnetic field immunity IEC 61000-4-8

30 A/m long duration and 300 A/m short duration at 50 Hz and 60 Hz

Voltage variation IEC 61000-4-29

10 ms interruption on DC supply ports

Environmental rating

IP20

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

47

Page 48

Stratix Ethernet Device Specifications

Table 29 - Certifications - Stratix 6000 Switches Certifications (when product is marked)(1)

1783-EMS08T, 1783-EMS04T c-UL-us

UL Listed Information Technology Equipment, certified for US and Canada. See UL File E151729.

c-ETL-us

ETL Listed Industrial Control Equipment, certified for US and Canada.

c-ETL-us

ETL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada

CE

European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2011/65/EU RoHS, compliant with: EN 50581; Technical documentation

RCM

Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions

Ex

EN 60079-0; General Requirements EN 60079-11; Explosive Atmospheres, Protection "i" EN 60079-15; Potentially Explosive Atmospheres, Protection "n" II 3 Ex ic nA IIC T4 Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

(1) See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Dimensions - Stratix 6000 Switches Mount the switches, as shown, in the vertical position only. We do not recommend horizontal mounting due to thermal considerations. Follow these guidelines: • Provide 50 mm (2 in.) of space on all sides for adequate heat dissipation. • Leave 100 mm (4 in.) for installation and removal if using the fiber-optic port on the bottom of the 1783-EMS08T switch. 52.07 mm (2.05 in.)

118 mm (4.64 in.)

107 mm (4.21 in.)

1 2

12 cm (0.47 in.) 12 mm (0.47 in.)

48

27.7 mm (1.09 in.)

SFP Module Installed

88.9 mm (3.50 in.)

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

Page 49

Stratix Ethernet Device Specifications

Stratix 8000 and Stratix 8300 Ethernet Managed Switches Table 30 - Technical Specifications - Stratix 8000 and Stratix 8300 Switches Attribute

1783-MS06T

1783-MS10T

1783-RMS06T

1783-RMS10T

Description

Stratix 8000 managed switch, Layer 2, 6 ports

Stratix 8000 managed switch, Layer 2, 10 ports

Stratix 8300 managed switch, Layer 3, 6 ports

Stratix 8300 managed switch, Layer 3, 10 ports

Inrush current, max

2.0 A

Power input, max

2 A max @ 18…60V DC, CL 2/SELV

Alarm relay, max

1 A max @ 30V DC, CL 2/SELV

Power consumption, max (Expansion module power not included)

15.1 W

15.7 W

15.1 W

15.7 W

Power dissipation

15.1 W

15.7 W

15.1 W

15.7 W

Isolation voltage

75V (continuous), basic insulation type, power to ground, power to network channels, and power to alarm No isolation between individual Ethernet ports No isolation between console port and system Type tested at 1000V AC for 60 s

RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to Wire size, Ethernet connection(1) ISO/IEC 24702 Wire size, DC power and alarm connections

0.5…0.8 mm2 (20…18 AWG) solid or stranded copper wire rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max

Wire size, ground connection

3.3…5.3 mm2 (12…10 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater

Screw torque, power and alarm terminals

0.23 N•m (2.0 in•lb)

Wiring category(2)

2 - on alarm ports 2 - on power ports 2 - on Ethernet ports

Enclosure type rating

None (open-style)

Pilot duty rating

Not rated

North American temp code

T4

IEC temp code

T4

SFP modules(3)

1783-SFP100FX 1783-SFP100LX 1783-SFP100EXC 1783-SFP100ZXC 1783-SFP100T(4) 1783-SFP1GSX 1783-SFP1GLX 1783-SFP1GEXE 1783-SFP1GZX 1783-SFP1GTE

1783-SFP100FX 1783-SFP100LX 1783-SFP100EXC 1783-SFP100ZXC 1783-SFP1GSX 1783-SFP1GLX 1783-SFP1GEXE 1783-SFP1GZX 1783-SFP1GTE

Memory card

1783-MCF

1783-RMCF

(1) (2) (3) (4)

See page 71 for recommended products. Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. SFP modules are supported only on switches with combo ports or SFP slots. For SFP specifications, see page 69. The 1783-SFP100T module requires Stratix 8000 firmware revision 12.001or later.

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

49

Page 50

Stratix Ethernet Device Specifications

Table 31 - Environmental Specifications - Stratix 8000 and Stratix 8300 Switches Attribute

1783-MS06T, 1783-MS10T, 1783-RMS06T, 1783-RMS10T

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-40…+60 °C (-40…+140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

20 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Emissions CISPR11 (IEC 61000-6-4)

Class A

ESD immunity IEC 61000-4-2

8 kV contact discharges 15 kV air discharges

Radiated RF immunity IEC 61000-4-3

20V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 1000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 2.5 kHz and ±2 kV at 5 kHz on power ports ±4 kV at 2.5 kHz and ±2 kV at 5 kHz on alarm ports ±4 kV at 2.5 kHz and ±2 kV at 5 kHz on Ethernet ports

Surge transient immunity IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports ±1 kV line-line (DM) and ±2 kV line-earth (CM) on alarm ports ±2 kV line-earth (CM) on Ethernet ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Magnetic field immunity IEC 61000-4-8

30 A/m long duration and 300 A/m short duration at 50 Hz and 60 Hz

Oscillatory surge withstand IEEE C37.90.1

2.5 kV

Voltage variation IEC 61000-4-29

10 ms interruption on DC supply ports

Environmental rating

IP20

50

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

Page 51

Stratix Ethernet Device Specifications

Table 32 - Certifications - Stratix 8000 and Stratix 8300 Switches Certifications (when product is marked)(1) 1783-MS06T, 1783-MS10T, 1783-RMS06T, 1783-RMS10T c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2011/65/EU RoHS, compliant with: • EN 50581; Technical Documentation

C-Tick

Australian Radiocommunications Act, compliant with: • AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA nC IIC T4 Gc X

KC

Korean Certification of Broadcasting and Communications Equipment, compliant with: • Framework Act on Telecommunications and Radio Waves Act

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

(1) See the Product Certification link at http://www.ab.com for declarations of conformity, certificates, and other certification details.

Optional Expansion Modules - Stratix 8000 and Stratix 8300 Switches Cat. No.

Description

1783-MX08T

Expansion module with 8 10/100 Base-T copper Ethernet ports

1783-MX08F

Expansion module with 8 100 Base-F fiber-optic Ethernet ports

1783-MX04S

Expansion module with 4 100 FX fiber-optic SFP slots

1783-MX08S

Expansion module with 8 100 FX fiber-optic SFP slots

1783-MX04E

Expansion module with 4 PoE ports

1783-MX04T04E

Ethernet expansion module with 4 10/100 Base-T copper Ethernet ports and 4 PoE ports

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

51

Page 52

Stratix Ethernet Device Specifications

Table 33 - Technical Specifications - Stratix 8000 and Stratix 8300 Expansion Modules Attribute

1783-MX08T

1783-MX08F

1783-MX04S

1783-MX08S

Description

Expansion module 8 ports, copper

Expansion module 8 ports, fiber

Expansion module 4 SFP ports, fiber

Expansion module 8 SFP ports, fiber

Backplane power

3.3V DC, 1.7 A max

3.3V DC, 3.6 A max

3.3V DC, 2.5 A max

3.3V DC, 4.0 A max

Power consumption, max

2.8 W

10.1 W

7.6 W

12.2 W

Power dissipation

2.8 W

10.1 W

7.6 W

12.2 W, Isolation voltage

75V (continuous), basic insulation type, expansion backplane to network channels No isolation between individual Ethernet ports Type tested at 1000V AC for 60 s

Wire size, Ethernet connection(1)

RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702, Wiring category(2)

2 - on Ethernet ports, Enclosure type rating

None (open-style)

North American temp code

T4

IEC temp code

T4

SFP modules(3)

(1) (2) (3) (4)

1783-SFP100FX 1783-SFP100LX 1783-SFP100EXC 1783-SFP100ZXC 1783-SFP100T(4), See page 71 for recommended products. Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. For SFP specifications, see page 69. The 1783-SFP100T module requires Stratix 8000 firmware revision 12.001or later.

Table 34 - Technical Specifications - Stratix 8000 and Stratix 8300 Fiber Expansion Module Attribute

1783-MX08F

Ethernet data rate

100 Mbps

Connecting mode

Full-duplex

Optical wavelength

1310 nm

Optical cable length, max

Graded index multimode fiber; 2000 m

Optical link budget

8 dB with 62.5/125 μm multimode cable 4 dB with 50/125 μm multimode cable

Connector type

IEC 61754-20 LC connector

52

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

Page 53

Stratix Ethernet Device Specifications

Table 35 - Technical Specifications - Stratix 8000 and Stratix 8300 Power over Ethernet Expansion Modules Attribute

1783-MX04E

1783-MX04T04E

Description

Expansion module 4 ports, Power over Ethernet

Expansion module • 4 ports, copper • 4 ports, Power over Ethernet

Backplane power

3.3V DC, 0.94 A max

3.34V DC, 1.08 A max

Power over Ethernet input power

48V DC for PoE 54V DC for PoE+ for a combination of PoE and PoE+ 2.5 A max

48V DC for PoE 54V DC for PoE+ for a combination of PoE and PoE+ 2.4 A max

Power consumption(1)

3 W @ 24V DC @ 40˚C (104˚F), 7.3 W max PoE power at 44V: 62 W max

3.5 W @ 24V DC @ 40˚C (104˚F), 7.9 W max PoE power at 44V: 62 W max

Power dissipation

7.3 W

7.9 W

Isolation voltage

60V (continuous), basic insulation type, expansion backplane to network ports, expansion backplane to power ports, and power ports to network ports No isolation between individual network ports Type tested at 1570V DC for 60 s

Wire size, Ethernet connection(2)

RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702

Wiring category(3)

2 - on Ethernet ports 2 - on power ports

Enclosure type rating

None (open-style)

North American temp code

T4

IEC temp code

T4

SFP modules, (1) For PoE configurations, the power consumption values listed represent the highest values that can be configured using all ports. A general guideline is 0.5 W per 30 W PoE+ port used. (2) See page 71 for recommended products. (3) Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 36 - Environmental Specifications - Stratix 8000 and Stratix 8300 Expansion Modules Attribute

1783-MX08T

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-40…+60 °C (-40…+140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

1783-MX08F

1783-MX04S, 1783-MX08S

1783-MX04E, 1783-MX04T04E

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry -40…+85 °C (-40…+185 °F) Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

20 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

15 g

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

53

Page 54

Stratix Ethernet Device Specifications

Table 36 - Environmental Specifications - Stratix 8000 and Stratix 8300 Expansion Modules (continued) 1783-MX08F

1783-MX04S, 1783-MX08S

Attribute

1783-MX08T

1783-MX04E, 1783-MX04T04E

Emissions CISPR11 (IEC 61000-6-4)

Group 1, Class A

ESD immunity IEC 61000-4-2

8 kV contact discharges 15 kV air discharges

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

20V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 1000…2700 MHz

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 2.5 kHz and ±2 kV at 5 kHz on Ethernet ports

Surge transient immunity IEC 61000-4-5, ±2 kV at 5 kHz on power ports and ±2 kV at 5 kHz on Ethernet ports

±2 kV line-earth (CM) on Ethernet ports, ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±2 kV line-earth(CM) on communication ports

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Magnetic field immunity IEC 61000-4-8

30 A/m long duration and 300 A/m short duration at 50 Hz and 60 Hz

30 A/m long duration and 300 A/m short duration at 50 Hz

Magnetic pulse immunity IEC 61000-4-9, 300 A/m pulse

Oscillatory surge withstand IEEE C37.90.1

2.5 kV

Damped oscillatory wave immunity IEC 61000-4-18, - ±1 kV line-line(DM) and ±2.5 kV line-earth(CM) on power ports

Table 37 - Certifications - Stratix 8000 and Stratix 8300 Expansion Modules Certifications (when product is marked)(1)

1783-MX08T, 1783-MX08F, 1783-MX04S, 1783-MX08S, 1783-MX04E, 1783-MX04T04E c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. UL Listed for Class I, Zone 2 Hazardous Locations, certified for U.S. and Canada. See UL File E194810. AEx/Ex nA IIC T4 Gc X

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2011/65/EU RoHS, compliant with: • EN 50581; Technical Documentation

C-Tick

Australian Radiocommunications Act, compliant with: • AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection "n" • EN 60079-0; General Requirements • II 3 G Ex nA IIC T4 Gc X

KC

Korean Certification of Broadcasting and Communications Equipment, compliant with: • Framework Act on Telecommunications and Radio Waves Act

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

(1) See the Product Certification link at http://www.ab.com for declarations of conformity, certificates, and other certification details.

54

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018