Page 55

Stratix Ethernet Device Specifications

Dimensions - Stratix 8000 and Stratix 8300 Switches This illustration shows dimensions for the 1783-MS10T switch and the 1783-MX08T expansion module. Dimensions for the other switches are the same as the 1783-MS10T switch. Dimensions for the other expansion modules are the same as the 1783-MX08T expansion module. Airflow around the switch and through the vents is unrestricted. To prevent the switch from overheating, these minimum clearances must be met: • Top and bottom: 105 mm (4.13 in.) • Left and right: 90 mm (3.54 in.) • Front: 65 mm (2.56 in.) Switch and Expansion Module

Switch and Expansion Module (mated) 9.71 cm (3.82 in.)

15.3 cm (6.03 in.)

24.3 cm (9.57 in.)

14.8 cm (5.83 in.)

33.27 cm (13.1 in.)

9.81 cm (3.87 in.)

11.1 cm (4.38 in.)

Switch (side view)

Switch and Expansion Modules (mated)

11.75 cm (4.63 in.) 31801-M

For panel-mounting, the height of the center of the mounting holes on both the top and bottom latches measures 8.73 mm (0.34 in.) above the top surface (or below the bottom surface) of the switch. On the switch base unit, the tab hole center-to-center spacing is 6.83 cm (2.69 in.). For expansion modules, the tab hole center-to-center spacing is 4.36 cm (1.72 in.).

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

55

Page 56

Stratix Ethernet Device Specifications

Stratix 5100 Wireless Access Point/Workgroup Bridge Table 38 - Technical Specifications - Stratix 5100 Wireless Access Point/Workgroup Bridge Attribute

1783-WAPBK9 United States

1783-WAPAK9 Canada/Latin America

1783-WAPEK9 European Union

1783-WAPZK9 Australia/New Zealand

1783-WAPCK9 China

Dimensions (LxWxD)

22.04 x 22.04 x 4.67 cm (8.68 x 8.68 x 1.84 in.)

22.04 x 22.04 x 4.67 cm (8.68 x 8.68 x 1.84 in.)

22.04 x 22.04 x 4.67 cm (8.68 x 8.68 x 1.84 in.)

22.04 x 22.04 x 4.67 cm (8.68 x 8.68 x 1.84 in.)

22.04 x 22.04 x 4.67 cm (8.68 x 8.68 x 1.84 in.)

Weight

1.22 kg (2.7 lb)

1.22 kg (2.7 lb)

1.22 kg (2.7 lb)

1.22 kg (2.7 lb)

1.22 kg (2.7 lb)

Power input

48V DC, 350 mA

48V DC, 350 mA

48V DC, 350 mA

48V DC, 350 mA

48V DC, 350 mA

Power consumption

12.95 W

12.95 W

12.95 W

12.95 W

12.95 W

Power dissipation

12.95 W

12.95 W

12.95 W

12.95 W

12.95 W

Antennas

External

External

External

External

External

Power adapter

AIR-PWR-B Input: 100…240 50/60 Hz VAC Output: 48V DC, 380 mA

AIR-PWR-B Input: 100…240 50/60 Hz VAC Output: 48V DC, 380 mA

AIR-PWR-B Input: 100…240 50/60 Hz VAC Output: 48V DC, 380 mA

AIR-PWR-B Input: 100…240 50/60 Hz VAC Output: 48V DC, 380 mA

AIR-PWR-B Input: 100…240 50/60 Hz VAC Output: 48V DC, 380 mA

Table 39 - Environmental Specifications - Stratix 5100 Wireless Access Point/Workgroup Bridge Attribute

1783-WAPBK9

1783-WAPAK9

1783-WAPEK9

1783-WAPZK9

1783-WAPCK9

Temperature, operating

-20…+55 °C (-4…+131 °F)

-20…+55 °C (-4…+131 °F)

-20…+55 °C (-4…+131 °F)

-20…+55 °C (-4…+131 °F)

-20…+55 °C (-4…+131 °F)

Temperature, nonoperating/storage

-30…+85 °C (-22…+185 °F)

-30…+85 °C (-22…+185 °F)

-30…+85 °C (-22…+185 °F)

-30…+85 °C (-22…+185 °F)

-30…+85 °C (-22…+185 °F)

Relative humidity

10…90% noncondensing

10…90% noncondensing

10…90% noncondensing

10…90% noncondensing

10…90% noncondensing

Table 40 - Certifications - Stratix 5100 Wireless Access Point/Workgroup Bridge Catalog Number

Certifications (when product is marked)(1)

1783-WAPBK9 Regulatory Domain `B’

FCC ID: LDK102080

This device complies with Part 15 of FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operations.

1783-WAPAK9 Regulatory Domain `A’

Industry Canada: 2461B-102080

RSS-210 - License Exempt Radio Apparatus: Category I Equipment

1783-WAPEK9 Regulatory Domain `E’

CE

For use in the EU, Iceland, Liechtenstein, Norway, Switzerland, Turkey and all other Countries that recognize the EU Directive 1999/5/EC.

1783-WAPZK9 Regulatory Domain `Z’

For use in Australia, New Zealand and all other Countries that recognize the Radiocommunications (Short Range Devices) Standard. E134

1783-WAPCK9 Regulatory Domain `C’

CMIIT ID: 2014AJ2894

For use in China and all other Countries that recognize The Bureau of Radio Administration of MIIT (Fixed Radio Devices).

(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

56

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

Page 57

Stratix Ethernet Device Specifications

Dimensions - Stratix 5100 Wireless Access Point/Workgroup Bridge 220.98 mm (8.7 in.)

53.59 mm (2.11 in.) 2.11

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

57

Page 58

Stratix Ethernet Device Specifications

Stratix 5900 Services Router Table 41 - Technical Specifications - Stratix 5900 Services Router Attribute

1783-SR

Input voltages

5V, 4 A Class 2 Requires LITEON PA-1220-1SA2 power adapter (100...240V AC, 50/60Hz, 0.8A)

Power consumption, max

11 W

Power dissipation

11 W

Isolation voltage

Not rated

Weight

1.5 kg (3.2 lb)

Wiring category(1)

3 - on power ports 2 - on Ethernet ports

Enclosure type rating

Meets IP41 (2)

Router AC Power Adapter Input voltage

85…264V AC 100…240V AC nom

Power consumption, max

25 W

Output power, max

20 W (5V DC, 4 A)

(1) Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (2) AC power adapter is not IP41 rated. Installation must include protection of the adapter and power plug from water.

Table 42 - Environmental Specifications - Stratix 5900 Services Router Attribute

1783-SR

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…+60 °C (-13…+140 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-64 (Test Fh, Operating)

1.12 Grms random

Operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock)

15 g

Nonoperating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock)

15 g

Emissions CISPR22 (IEC 61000-6-4)

Class B

ESD immunity IEC 61000-4-2

8 kV contact discharges 15 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

58

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

Page 59

Stratix Ethernet Device Specifications

Table 42 - Environmental Specifications - Stratix 5900 Services Router (continued) Attribute

1783-SR

EFT/B immunity IEC 61000-4-4

±500 kV at 5 kHz on Ethernet ports

Surge transient immunity IEC 61000-4-5

±1 kV line-earth (CM) on shielded Ethernet port

Conducted RF immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Environmental rating

IP30

Table 43 - Certifications - Stratix 5900 Services Router Certifications (when product is marked)(1)

1783-SR c-UL-us

UL Listed Information Technology Equipment, certified for US and Canada. See UL File E136709.

CE

European Union 1999/5/EC R&TTE Directive, compliant with: • EN 55022; ITE Emissions • EN 55024; ITE Immunity • EN 60950; ITE Safety European Union 2011/65/EU RoHS, compliant with: • EN 50581; Technical documentation

C-Tick

Australian Radiocommunications Act, compliant with: • ACMA EMC Std 08

CCC

GB 4943. 1, GB 9254, YD/T993

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Dimensions - Stratix 5900 Services Router 44 mm (1.73 in.) 206 mm (8.1 in.)

196 mm (7.7 in.)

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

59

Page 60

Stratix Ethernet Device Specifications

Stratix 5950 Security Appliance Table 44 - Technical Specifications - Stratix 5950 Security Appliance Attribute

1783-SAD4T0SBK9, 1783-SAD4T0SPK9, 1783-SAD2T2SBK9, 1783-SAD2T2SPK9

Power consumption

24 W

Power dissipation

24 W

Enclosure type rating

None (open-style)

Voltage and current ratings

12…48V DC, 2.0 A Max – User Supply Alarm relay: 30V DC, 1 A or 48V DC, 0.5 A

Isolation voltage

60V (continuous), Basic Insulation Type, all ports to Ground. No isolation between individual ports.

Wire size, Ethernet connection

RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702

Wire size, ground connection

4 mm2 (12…10 AWG) solid or stranded copper wire

Wire size, alarm connection

0.8…1.0 mm2 (18…16 AWG) solid or stranded, UL/CSA-rated style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire (such as Belden part number 9318), 6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.) strip length

Wire size, DC power connection

0.8…1.0 mm2 (18…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max, 6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.) strip length

Insulation stripping length

6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.)

Wire type

Copper

Pilot duty rating

Alarm: Not rated

Wiring category(1)

3 - on Console ports 2 -on Power and Alarm ports 2 - on Ethernet ports

Voltage variation IEC 61000-4-29

30 % dip for 10 ms on DC supply ports 60 % dips for 100 ms and 1 s on DC supply ports 100 % dips for 10 ms and 5 s on DC supply ports

Alarm relay

30V DC, 1 A, or 48V DC, 0.5 A

Screw torque, ground terminal

0.4 N•m (3.5 Ib•in)

Screw torque, power terminal

0.56 N•m (5 Ib•in)

Screw torque, alarm terminal

0.56 N•m (5 Ib•in)

North American temp code

T4

ATEX temp code

T4

SFP modules

1783-SFP100FX 1783-SFP100LX 1783-SFP1GSX 1783-SFP1GLX

Memory card replacement

1784-SD1

(2)

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (2) For SFP specifications, see page 69.

60

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

Page 61

Stratix Ethernet Device Specifications

Table 45 - Environmental Specifications - Stratix 5950 Security Appliance Attribute

1783-SAD4T0SBK9, 1783-SAD4T0SPK9, 1783-SAD2T2SBK9, 1783-SAD2T2SPK9

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-40…+60 °C (-40…+140 °F)

Temperature, ambient, max

For UL certified enclosed equipment: 60 °C (140 °F)

Temperature, surrounding air, max

For UL certified enclosed equipment: 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…+85 °C (-40…+185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

1 g @ 5…150 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

15 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Emissions

IEC 61000-6-4

ESD Immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF Immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B Immunity IEC 61000-4-4

±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on signal ports ±2 kV at 5 kHz on communications ports

Surge Transient Immunity IEC 61000-4-5

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±500V line-line(DM) and ±1 kV line-earth(CM) on signal ports ±2 kV line-earth(CM) on communications ports

Conducted RF Immunity IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Damped Oscillatory Wave Immunity IEC 61000-4-18

±500V line-line(DM) and ±1 kV line-earth(CM) on signal ports ±1 kV line-line(DM) and ±2.5 kV line-earth(CM) on power ports ±500V line-earth(CM) on communication ports

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

61

Page 62

Stratix Ethernet Device Specifications

Table 46 - Certifications - Stratix 5950 Security Appliance Certifications (when product is marked)(1)

1783-SAD4T0SBK9, 1783-SAD4T0SPK9, 1783-SAD2T2SBK9, 1783-SAD2T2SPK9 c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584 UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. UL Listed for Class I, Zone 2 Hazardous Locations, certified for U.S. and Canada. See UL File E194810. • Class 1, Zone 2, Ex nA nC IIC T4 Gc X • Class 1, Zone 2, AEx nA nC IIC T4 Gc

CE

European Union 1999/5/EC R&TTE Directive, compliant with: • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions European Union 2011/65/EU RoHS, compliant with: • EN 50581; Technical documentation

RCM

EN 61000-6-4; Industrial Emissions

Ex

EN 60079-0; General Requirements EN 60079-15; Potentially Explosive Atmospheres, Protection "n" Ex nA nC IIC T4 Gc DEMKO 15 ATEX 1595X

(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Dimensions - Stratix 5950 Security Appliance 106.68 mm (4.2 in.)

R

129.54 mm (5.10 in.)

159.26 mm (6.27 in.) 32593-M

62

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

Page 63

Stratix Ethernet Device Specifications

Embedded Switch Technology Table 47 - Technical Specifications - EtherNet/IP Taps Attribute

1783-ETAP

1783-ETAP1F

1783-ETAP2F

Description

EtherNet/IP tap 3 copper ports

EtherNet/IP tap • 2 copper ports • 1 fiber port

EtherNet/IP tap • 1 copper port • 2 fiber ports

Tap type

Copper

Fiber, single-port

Fiber, dual-port

Current consumption, max

125 mA @ 24V DC

200 mA @ 24V DC

260 mA @ 24V DC

DC power supply voltage rating

24V DC (20.4…27.6V DC) CL 2/SELV

Isolation voltage

30V (continuous), basic insulation type, network channels to power and network channels to network channels Type tested at 1250V DC for 60 s

Type tested at 853V AC for 60 s

Power consumption, max

3W

4.8 W

6.24 W

Power dissipation

3W

4.8 W

6.24 W

Wire size, Ethernet connection(1)

RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702

Wire size, DC power connection

One 0.33…3.3 mm2 (22…12 AWG) or two 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max

Screw torque, power terminal

0.6…0.8 N•m (5…7 in•lb)

Wiring category(2)

1 - on power ports 2 - on communication ports

Enclosure type rating

None (open-style)

North American temp code

T5

T4A

T4

IEC temp code

T5

T4

T4

(1) See page 71 for recommended products. (2) Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 48 - Technical Specifications - EtherNet/IP Tap Fiber Connections Attribute

1783-ETAP1F, 1783-ETAP2F

Fiber transceiver type

100Base-FX IEEE802.3u

Optical wavelength

1310 nm no cap

Transmitter launch power at Beginning of Life (BOL), min Allow -1 dB at End of Life (EOL)

-19 dBm into 62.5/125 μm fiber, N/A = 0.275 -22.5 dBm into 50/125 μm fiber, N/A = 0.20

Receiver sensitivity, min

-31.8 dBm

Receiver sensitivity, max

-14 dBm

Fiber channel power budget at rated BER (2 connected taps, either 1783-ETAP1F or 1783-ETAP2F)

12.8 dB for 62.5/125 μm multimode fiber 9.3 dB for 50/125 μm multimode fiber

Fiber connection, glass

62.5/125 μm and 50/125 μm multimode fiber

Fiber connection, simplex or duplex

Jacket type and jacket diameter is dependent on connector selection

Fiber connection, graded index (GI)

Per IEC 60794-1-1, IEC 60793-2-10 category A1 fibers

Connector type

IEC 61754-20 LC connector, maximum insertion loss 0.75 dB per connection

Channel length, max

2 km (1.24 mi) (1)

(1) The channel (connectors and cable) must not exceed the allowable power budget.

Rockwell Automation Publication 1783-TD001T-EN-P - July 2018

63