For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 83

Chapter

5

Connect the Kinetix 6000 Drive System

This chapter provides procedures for wiring your Kinetix® 6000 drive system components and making cable connections.

Basic Wiring Requirements

Topic

Page

Basic Wiring Requirements

83

Determine the Input Power Configuration

85

Set the Ground Jumper in Select Power Configurations

89

Grounding the Kinetix 6000 Drive System

95

Power Wiring Requirements

97

Power Wiring Guidelines

99

Wiring the IAM/AM Module Connectors

100

Apply the Motor Cable Shield Clamp

116

Feedback and I/O Cable Connections

117

Wiring the Feedback and I/O Connectors

122

External Shunt Module Connections

127

IPIM Module Connections

128

RBM Module Connections

129

Sercos Fiber-optic Cable Connections

130

Kinetix 6000M Integrated Drive-Motor Sercos Connections

133

Ethernet Cable Connections

134

This section contains basic wiring information for the Kinetix 6000 drive modules. ATTENTION: Plan the installation of your system so that you can perform all cutting, drilling, tapping, and welding with the system removed from the enclosure. Because the system is of the open type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged in the circuitry, which can result in damage to components. SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting and wiring of the Bulletin 2094 power rail and drive modules prior to applying power. Once power is applied, connector terminals can have voltage present even when not in use.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

83

Page 84

Chapter 5

Connect the Kinetix 6000 Drive System

IMPORTANT

This section contains common PWM servo system wiring configurations, size, and practices that can be used in a majority of applications. National Electrical Code, local electrical codes, special operating temperatures, duty cycles, or system configurations take precedence over the values and methods provided.

Building Your Own Cables IMPORTANT

Factory-made cables are designed to minimize EMI and are recommended over hand-built cables to optimize system performance. Building your own cables is not an option for the hybrid and network cables used in Kinetix 6000M integrated drive-motor systems.

Follow these guidelines when building cables for compatible motors and actuators: • Connect the cable shield to the connector shells on both ends of the cable with a complete 360° connection. • Use twisted pair cable whenever possible. Twist differential signals with each other and twist single-ended signals with the appropriate ground return. Refer to the Kinetix Motion Accessories Technical Data, publication KNX-TD004, for low-profile connector kit, drive-end (mating) connector kit, and motor-end connector kit catalog numbers.

Routing the Power and Signal Cables Be aware that when you route power and signal wiring on a machine or system, radiated noise from nearby relays, transformers, and other electronic drives can be induced into motor or encoder feedback signals, input/output communication, or other sensitive low voltage signals. This can cause system faults and communication anomalies. Refer to Electrical Noise Reduction on page 34 for examples of routing high and low voltage cables in wireways. Refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001, for more information.

84

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 85

Connect the Kinetix 6000 Drive System

Determine the Input Power Configuration

Chapter 5

Before wiring input power to your Kinetix 6000 system, you must determine the type of input power you are connecting to. The IAM module is designed to operate in both grounded and ungrounded environments. ATTENTION: When you are using a LIM module for input power, the VAC LINE input power must come from a grounded configuration. When you are not using a LIM module for input power, ungrounded, corner-grounded, and impedance-grounded power configurations are permitted, but you must set the ground jumper to the ungrounded position for proper drive operation. In addition, set the ground jumper when an active converter supplies the DC-bus voltage. Refer to Set the Ground Jumper in Select Power Configurations on page 89 for more information.

Grounded Power Configurations The grounded (WYE) power configuration lets you ground your three-phase power at a neutral point. This type of grounded power configuration is preferred. Figure 39 - Grounded Power Configuration (WYE Secondary)

L3 Transformer

L1

Circuit Protection

M1 Contactor

1 2

Three-phase Input VAC

Three-phase AC Line Filter

L2

L3 L2 L1 CONT ENCONT EN+

W V U

RX

Phase Ground Bonded Cabinet Ground

MBRK MBRK + COM PWR DBRK DBRK +

DPI

1 2 3 4 5 6

1 2 3 4 5 6

DCDC+

Transformer (WYE) Secondary

1 2 3 4 5 6 7 8 9

1 2

CTRL 2 CTRL 1 1 2 3 4

Kinetix 6000 IAM Module, Top View

TX

BAUD RATE

Connect to power rail ground stud.

Ground Grid or Power Distribution Ground

The IAM module has a factory-installed ground jumper for grounded power distribution. IMPORTANT

If you determine that you have grounded power distribution in your facility, you do not need to move the ground jumper.

Refer to Power Wiring Examples beginning on page 189 for input power interconnect diagrams with and without the LIM module.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

85

Page 86

Chapter 5

Connect the Kinetix 6000 Drive System

Figure 40 - Corner-grounded Power Configuration (Delta Secondary)

M1 Contactor

1 2

Circuit Protection

L2

W

DC+ L3 L2 L1 CONT ENCONT EN+

V U 1 2 3 4 5 6 7 8 9

Three-phase AC Line Filter

DC-

RX

MBRK MBRK + COM PWR DBRK DBRK +

1 2 3 4 5 6

L3

1 2 3 4 5 6

Transformer

1 2

Transformer (Delta) Secondary

CTRL 2 CTRL 1 1 2 3 4

Kinetix 6000 IAM Module, Top View

TX

DPI

BAUD RATE

L1 Bonded Cabinet Ground

Connect to power rail ground stud.

Ground Grid or Power Distribution Ground

Figure 41 - Impedance-grounded Power Configuration (WYE Secondary)

L3 Transformer

Three-phase AC Line Filter

L2 L1

Circuit Protection

M1 Contactor

1 2

Three-phase Input VAC

L3 L2 L1 CONT ENCONT EN+

W V U

RX

Phase Ground Bonded Cabinet Ground

MBRK MBRK + COM PWR DBRK DBRK +

DPI

1 2 3 4 5 6

1 2 3 4 5 6

DCDC+

Transformer (WYE) Secondary

1 2 3 4 5 6 7 8 9

1 2

CTRL 2 CTRL 1 1 2 3 4

Kinetix 6000 IAM Module, Top View

TX

BAUD RATE

Connect to power rail ground stud.

Ground Grid or Power Distribution Ground

IMPORTANT

Even though impedance-grounded and corner-grounded power configurations have a ground connection, treat them as ungrounded when installing Kinetix 6000 drive systems.

Refer to Appendix A on page 187, for input-power interconnect diagrams with and without the LIM module.

86

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 87

Connect the Kinetix 6000 Drive System

Chapter 5

Ungrounded Power Configurations The ungrounded power configuration (Figure 42) does not provide a neutral ground point. Ungrounded, impedance-grounded, and corner-grounded power configurations are allowed, but you must move a jumper (internal to the IAM module) across a 120 kΩ resistor. The IAM module ground jumper (default configuration) is set for grounded power distribution. IMPORTANT

If you determine that you have ungrounded, impedance-grounded, or corner-grounded power distribution in your facility, you must move the ground jumper (configured for grounded power) to the ungrounded power position inside the IAM module. Refer to Set the Ground Jumper in Select Power Configurations on page 89 for more information.

Figure 42 - Ungrounded Power Configuration

L3 L2 L1 CONT ENCONT EN+

W V U

RX

Chassis Ground

Bonded Cabinet Ground

Connect to power rail ground stud.

MBRK MBRK + COM PWR DBRK DBRK +

DPI

1 2 3 4 5 6

Circuit M1 Protection Contactor

1 2

L1

DCDC+

1 2 3 4 5 6 7 8 9

L2

Three-phase Input VAC

CTRL 2 CTRL 1

1 2 3 4 5 6

L3

Transformer

1 2

Transformer (Delta) Secondary

1 2 3 4

Kinetix 6000 IAM Module, Top View

TX

BAUD RATE

Ground Grid or Power Distribution Ground

ATTENTION: Ungrounded systems do not reference each phase potential to a power distribution ground. This can result in an unknown potential to earth ground. Refer to Appendix A on page 187, for input-power interconnect diagrams with and without the LIM module.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

87

Page 88

Chapter 5

Connect the Kinetix 6000 Drive System

When the IAM module is used in a DC common-bus configuration, the IAM module is known as a leader IAM or follower IAM module. The IAM (noncommon bus) and leader IAM module have identical three-phase input power connections. The leader IAM module is responsible for discharging the DC bus, and for providing common-bus follower drives with DC bus precharge, bus regulation, phase-loss detection, and ground fault detection. Follower IAM modules do not have three-phase input power connections, but have DC bus connections from a leader IAM module.

DC Common Bus Configurations

Table 57 - IAM Module Terminology and Use This Module

Is Wired

And is

IAM

With three-phase input power.

Not wired in Common-bus mode.

Leader IAM

With three-phase input power, but has DC common-bus connections to a follower IAM module.

Wired in Common-bus mode.

Follower IAM

Without three-phase input power, but has DC common-bus connections from a leader IAM module.

Wired in Common-bus mode and configured by using the Logix Designer application.

IMPORTANT

Use Kinetix 6000 drive firmware revision 1.85 and the Logix Designer Application or RSLogix 5000® software, version 15 or later, for common-bus power configurations.

The Kinetix 6000 leader IAM module can operate with non-Kinetix 6000 follower drives, as can the Kinetix 6000 follower IAM module operate with non-Kinetix 6000 common-bus leader drives. However, non-Kinetix 6000 leader and follower drives must meet the same functional requirements as the Kinetix 6000 leader and follower IAM modules. IMPORTANT

Any non-Kinetix 6000 common-bus leader IAM module that does not provide precharge is required to add an additional external precharge circuit before connecting to any Kinetix 6000 common-bus follower IAM module.

Figure 43 - Typical DC Common-bus Configuration

RX

BAUD RATE

RX

N.C. N.C. N.C.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

DPI

MBRK -

TX

RX BAUD RATE

MBRK + COM PWR DBRK DBRK +

TX

BAUD RATE

RX

COM PWR DBRK DBRK +

1 2 3 4

1 2 3 4

MBRK MBRK +

1 2 3 4 5 6

CONT ENCONT EN+

MBRK MBRK + COM PWR DBRK DBRK +

1 2 3 4

1 2 3 4 TX

L3 L2 L1

W V U

1 2 3 4 5 6

DBRK +

1 2 3 4 5 6

1 2 3 4

1 2 3 4 1 2 3 4 5 6

1 2 3 4 5 6 BAUD RATE

PWR

W V U

1 2 3 4 5 6 7 8 9

TX

COM DBRK -

2094-xMxx-x AM Modules or 2094-SEPM-B24-S IPIM Modules

1 2 3 4 5 6 7 8 9

RX BAUD RATE

DBRK +

MBRK MBRK +

W V U 1 2 3 4 5 6 7 8 9

TX

PWR

DCDC+

1 2

88

DPI

COM DBRK -

CTRL 2 CTRL 1

1 2 3 4 5 6

RX

Kinetix 6000 DC Common Bus Connections

MBRK MBRK +

1 2

1 2

CONT ENCONT EN+

MBRK MBRK + COM PWR DBRK DBRK +

W V U 1 2 3 4 5 6 7 8 9

L3 L2 L1

W V U

W V U 1 2 3 4 5 6 7 8 9

DCDC+

1 2 3 4 5 6 7 8 9

CTRL 2 CTRL 1

1 2 3 4 5 6

Three-phase Input Power

1 2

Bonded Cabinet Ground

2094-xCxx-Mxx-x Common-bus Follower IAM Module

2094-xMxx-x AM Modules or 2094-SEPM-B24-S IPIM Modules

1 2 3 4 5 6

2094-xCxx-Mxx-x Common-bus Leader IAM Module

TX

BAUD RATE

Page 89

Connect the Kinetix 6000 Drive System

Chapter 5

Common Bus Fusing Requirements When using a Kinetix 6000 leader IAM module, DC-bus fuses are required only when wiring to more than one Kinetix 6000 follower IAM module. When wiring multiple follower IAM modules, terminal blocks are required to extend the DC common-bus power to additional drives. Install fuses in both lines of the DC bus between the DC bus terminal block and each follower IAM module. Base these fuse ratings on the DC input current of each follower IAM module. When using a non-Kinetix 6000 common-bus leader drive, DC bus fuses are required in both lines of the DC bus, between the common-bus leader drive and follower IAM module. Base these fuse ratings on the common-bus leader drive DC output current. When using more than one follower IAM module, install fuses in both lines of the DC bus between the non-Kinetix 6000 common-bus leader and the terminal block as well as between the DC bus terminal block and each follower IAM module. Refer to Circuit Breaker/Fuse Options on page 28, for recommended circuit breaker/fuse sizes. Refer to DC Common Bus Wiring Examples on page 193 for interconnect diagrams.

Set the Ground Jumper in Select Power Configurations

Setting the ground jumper is required when using an ungrounded, cornergrounded, and impedance-grounded power configurations. Setting the ground jumper is also required when the Bulletin 8720MC regenerative power supply or any active converter provides DC-bus power. Setting the jumper involves removing the IAM module from the power rail, opening the IAM module, and moving the jumper. IMPORTANT

If you have grounded power distribution, you do not need to set the ground jumper. Go to Grounding the Kinetix 6000 Drive System on page 95.

ATTENTION: Because the unit no longer maintains line-to-neutral voltage protection, risk of equipment damage exists when you move the ground jumper. Setting the ground jumper is best done when the IAM module is removed from the power rail and placed face-up on a solid surface equipped as a grounded static-safe workstation. ATTENTION: This drive contains electrostatic discharge (ESD) sensitive parts and assemblies. You are required to follow static-control precautions when you install, test, service, or repair this assembly. If you do not follow ESD control procedures, components can be damaged. If you are not familiar with static control procedures, refer to Guarding Against Electrostatic Damage, publication 8000-4.5.2, or any other applicable ESD awareness handbook.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

89

Page 90

Chapter 5

Connect the Kinetix 6000 Drive System

When using ungrounded input power in common-bus configurations, use this table to determine where to set the ground jumper. Table 58 - Ground Jumper to Set Leader Drive

Follower Drive

Set the Jumper in This Drive

Kinetix 6000 IAM module

Kinetix 6000 IAM module

Leader drive

Kinetix 6000 IAM module

Non-Kinetix 6000 drive

Leader drive

Non-Kinetix 6000 drive

Kinetix 6000 IAM module

Follower drive (if no setting exists in the leader drive)

ATTENTION: Risk of equipment damage exists. The facility ground configuration must be accurately determined. Do not move the ground jumper for grounded power configurations (default). Move the ground jumper for ungrounded, corner-grounded, and impedance-grounded power, or when an active converter supplies the DC-bus voltage. Table 59 - Ground Jumper Configurations Ground Configuration

Example Diagram

Ground Jumper Configuration

Benefits of Correct Configuration

Grounded (wye)

Figure 39 on page 85

Grounded power (default setting)

• • • •

UL and EMC compliance Reduced electrical noise Most stable operation Reduced voltage stress on components and motor bearings

• AC-fed ungrounded • Corner grounded • Impedance grounded

Figure 42 on page 87 Figure 40 on page 86 Figure 41 on page 86

Set for ungrounded power

• Helps avoid severe equipment damage when ground faults occurs • Reduced leakage current

DC-bus from active converter

Figure 92 on page 196

Set the Ground Jumper ATTENTION: To avoid personal injury, the ground jumper access area must be kept closed when power is applied. If power was present and then removed, wait at least 5 minutes for the DC-bus voltage to dissipate and verify that no DC-bus voltage exists before accessing the ground jumper. Follow these steps to set the ground jumper for ungrounded power. 1. Remove the IAM module from the power rail. For detailed instructions, refer to Remove Kinetix 6000 Drive Modules on page 182. 2. Remove the top and bottom front-panel screws. Refer to the figures beginning on page 92 (230V IAM module) or page 93 (460V IAM module) for an illustration of your actual hardware.

90

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 91

Connect the Kinetix 6000 Drive System

Chapter 5

3. Swing the front panel open to the right, as shown, and locate the ground jumper. IMPORTANT

Do not attempt to remove the front panel from the IAM module. The front panel status indicators and switches are also connected to the IAM module with a ribbon cable. The ribbon cable acts like a hinge and lets you swing the front panel open to access the ground jumper.

4. Move the ground jumper. Configuration

IAM Module (series A) 2094-ACxx-Mxx-x (230V)

(1)

Grounded (default)

Ungrounded

P15 and P16

P15 and P17

P13 and P14

P13 and P12

P14 and P13

P14 and P12

2094-BC01-MP5-x (460V) 2094-BC01-M01-x (460V) 2094-BC02-M02-x (460V) 2094-BC04-M03-x (460V) 2094-BC07-M05-x (460V) (1) Applies to series A and C (230V) drives.

IAM Module (series B and C)

Configuration Grounded (default)

Ungrounded

P16 and P17

P18 and P19

2094-BC01-MP5-S (460V) 2094-BC01-M01-S (460V) 2094-BC02-M02-S (460V) 2094-BC04-M03-S (460V) 2094-BC07-M05-S (460V)

5. Replace the IAM module front panel and two screws. Apply 1.6 N•m (14 lb•in) torque. 6. Mount the IAM module back on the power rail. For detailed instructions, refer to Replace Kinetix 6000 Drive Modules on page 183.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

91