For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 92

Chapter 5

Connect the Kinetix 6000 Drive System

Figure 44 - Setting the Ground Jumper (230V Series A and C IAM modules) Top Screw

P17 P16 2094-ACxx-Mxx-x IAM Module (230V)

P15

Ground jumper set for ungrounded configuration.

Ground jumper set for grounded configuration (default setting).

Front Panel (opened)

IMPORTANT

92

Bottom Screw

Use the default jumper setting or remove the jumper entirely for grounded power configurations. Move the jumper, as shown above, for ungrounded power.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 93

Connect the Kinetix 6000 Drive System

Chapter 5

Figure 45 - Setting the Ground Jumper (460V Series A IAM modules) Top Screw 2094-BC01-MP5-x, 2094-BC01-M01-x, or 2094-BC02-M02-x IAM Module (460V)

P13 P14 P12

Ground jumper set for ungrounded configuration.

Ground jumper set for grounded configuration (default setting).

Front Panel (opened)

Bottom Screw

Top Screw 2094-BC04-M03-x or 2094-BC07-M05-x IAM Module (460V)

P12 P13 P14

Ground jumper set for grounded configuration (default setting). Ground jumper set for ungrounded configuration.

Front Panel (opened) Bottom Screw

IMPORTANT

Use the default jumper setting or remove the jumper entirely for grounded power configurations. Move the jumper, as shown above, for ungrounded power.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

93

Page 94

Chapter 5

Connect the Kinetix 6000 Drive System

Figure 46 - Setting the Ground Jumper (460V Series B and C IAM modules) P16 P17 (behind P18) Top Screw

P18

2094-BC01-MP5-S, 2094-BC01-M01-S, 2094-BC02-M02-S, 2094-BC04-M03-S, or 2094-BC07-M05-S IAM Module (460V)

P19

Ground jumper set for grounded configuration (default setting).

Ground jumper set for ungrounded configuration.

P18 P19 Front Panel (opened)

94

Bottom Screw

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 95

Connect the Kinetix 6000 Drive System

Grounding the Kinetix 6000 Drive System

Chapter 5

All equipment and components of a machine or process system must have a common earth ground point connected to chassis. A grounded system provides a ground path for short circuit protection. Grounding your modules and panels minimize shock hazard to personnel and damage to equipment caused by short circuits, transient overvoltages, and accidental connection of energized conductors to the equipment chassis. ATTENTION: The National Electrical Code contains grounding requirements, conventions, and definitions. Follow all applicable local codes and regulations to safely ground your system. For CE grounding requirements, refer to Agency Compliance on page 22.

Ground the Power Rail to the System Subpanel The 2094-PRx and 2094-PRSx power rail ships with a braided ground strap, 100 mm (3.9 in.), that connects to the bonded cabinet ground bus. Connect the other end to either the power rail ground stud or mounting bracket ground stud, if mounting brackets are used. Figure 47 - Connecting the Braided Ground Strap Examples Braided Ground Strap

2094 Power Rail (2094-PRSx shown)

PRS

PR PR

Bonded Cabinet Ground Bus LIM

Ground Grid or Power Distribution Ground

Line Interface Module on 2094 Mounting Brackets (2094-ALxxS shown)

Ground Stud

LIM

2094 Mounting Bracket (2094-XNBRKT-1)

Ground Stud PRS

PR/PRS

PR PR

2094 Power Rail on 2094 Mounting Brackets (2094-PRSx shown)

2094 Mounting Bracket (2094-XNBRKT-1)

LIM

Bonded Cabinet Ground Bus

PR

Braided Ground Strap

PRS LIM

Ground Stud Braided Ground Strap

Bonded Cabinet Ground Bus

Ground Grid or Power Distribution Ground

Ground Grid or Power Distribution Ground

For power rail dimensions, refer to the Kinetix 6000 Power Rail Installation Instructions, publication 2094-IN003.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

95

Page 96

Chapter 5

Connect the Kinetix 6000 Drive System

For mounting bracket dimensions, refer to the 2094 Mounting Brackets Installation Instructions, publication 2094-IN008. IMPORTANT

When 2094 mounting brackets are used to mount the power rail or LIM module over the AC line filter, the braided ground strap must be removed from the power rail and attached to a mounting bracket ground stud.

Ground Multiple Subpanels In this figure, the chassis ground is extended to multiple subpanels. Figure 48 - Subpanels Connected to a Single Ground Point

Follow NEC and applicable local codes. Bonded Ground Bus

Ground Grid or Power Distribution Ground

High-frequency (HF) bonding is not illustrated. For HF bonding information, refer to Bonding Multiple Subpanels on page 36.

96

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 97

Connect the Kinetix 6000 Drive System

Power Wiring Requirements

Chapter 5

Wire must be copper with 75 °C (167 °F) minimum rating. Phasing of main AC power is arbitrary and earth ground connection is required for safe and proper operation. For IPIM module power wiring requirements, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003. Refer to Power Wiring Examples on page 189 for interconnect diagrams. IMPORTANT

The National Electrical Code and local electrical codes take precedence over the values and methods provided.

Table 60 - IAM Power Wiring Requirements Kinetix 6000 Drive Cat. No.

Connects to Terminals Description

Pin

Signal

IPD-1 IPD-2 IPD-3 IPD-4 IPD-5 IPD-6

DCDC+

2094-AC05-Mxx-x 2094-AC09-M02-x 2094-AC16-M03-x

(1)

DC bus and VAC input power

L3 L2 L1

2094-AC32-M05-x 2094-BC01-Mxx-x 2094-BC02-M02-x 2094-BC04-M03-x

Recommended Wire Strip Length Size mm (in.) 2 mm (AWG) 6…2.5 (10…14) 6…4 (10…12) 30…10 (3…8) 30 (3)

DC bus (1) and VAC input power

2094-BC07-M05-x Control input power 2094-xCxx-Mxx-x Contactor Enable

IPD-1 IPD-2 IPD-3 IPD-4 IPD-5 IPD-6

DCDC+

CPD-1

CTRL 2

CPD-2

CTRL 1

CED-1

CONT EN-

CED-2

CONT EN+

L3 L2 L1

10…2.5 (8…14) 10…6 (8…10) 30 (3) 4…2.5 (12…14) 4…2.5 (12…14) (2)

Torque Value N•m (lb•in)

10 (0.38)

0.5…0.6 (4.4…5.3)

16 (0.63)

2.4…3.0 (21.6…26.5)

10 (0.38)

1.2…1.5 (10.6…13.2)

16 (0.63)

2.4…3.0 (21.6…26.5)

10 (0.38)

0.5…0.6 (4.4…5.3) 0.5…0.6 (4.4…5.3)

(1) Keep DC common-bus connections (leader IAM to follower IAM module) as short as possible. (2) The actual gauge of the contactor enable wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local codes.

ATTENTION: To avoid personal injury and/or equipment damage, make sure installation complies with specifications regarding wire types, conductor sizes, branch circuit protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline provisions for safely installing electrical equipment. ATTENTION: To avoid personal injury and/or equipment damage, make sure motor power connectors are used for connection purposes only. Do not use them to turn the unit on and off. ATTENTION: To avoid personal injury and/or equipment damage, make sure shielded power cables are grounded to prevent potentially high voltages on the shield.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

97

Page 98

Chapter 5

Connect the Kinetix 6000 Drive System

Table 61 - IAM/AM Power Wiring Requirements Kinetix 6000 Drive Cat. No.

Connects to Terminals Description

2094-AC05-Mxx-x, 2094-AC09-M02-x, 2094-BC01-Mxx-x, 2094-BC02-M02-x, 2094-AMP5-x, 2094-AM01-x, 2094-AM02-x, 2094-BMP5-x, 2094-BM01-x, 2094-BM02-x 2094-AC16-M03-x, 2094-AC32-M05-x, 2094-BC04-M03-x, 2094-AM03-x, 2094-AM05-x, 2094-BM03-x

Pin

Signal

IAM or AM (230 or 460V) 2094-xCxx-Mxx-S and 2094-xMxx-S

Strip Length mm (in.)

Torque Value N•m (lb•in)

10 (0.38)

0.5…0.6 (4.4…5.3)

10…1.5 (8…16)

10 (0.38)

1.2…1.5 (10.6…13.2)

30…2.5 (3…14)

16 (0.63)

2.4…3.0 (21.6…26.5)

0.75 (18)

10 (0.38)

0.22…0.25 (1.9…2.2)

7.0 (0.275)

0.235 (2.0)

Recommended Wire Size mm2 (AWG)

Torque Value N•m (lb•in)

10 (8) (1)

1.2…1.5 (10.6…13.2)

0.75 (18)

0.22…0.25 (1.9…2.2)

Motor power cable depends on motor/ drive combination.

Motor power

6…1.5 (10…16)

MP-4 MP-3 MP-2 MP-1

W V U

2094-BC07-M05-x, 2094-BM05-x IAM or AM (230 or 460V) 2094-xCxx-Mxx-x and 2094-xMxx-x

Recommended Wire Size mm2 (AWG)

Brake power

BC-6 BC-5 BC-4 BC-3 BC-2 BC-1

MBRKMBRK+ COM PWR DBRKDBRK+

Safe torque-off

STO-1 STO-2 STO-3 STO-4 STO-5 STO-6 STO-7 STO-8 STO-9

FDBK2+ FDBK2FDBK1+ FDBK1SAFETY ENABLE2+ SAFETY ENABLESAFETY ENABLE1+ 24V + 24V_COM

0.75 (18) (stranded wire with ferrule) 1.5 (16) (solid wire)

Table 62 - Shunt Module Power Wiring Requirements Connects to Terminals Drive Module Cat. No.

2094-BSP2 Shunt module (200/400V-class)

Description

1394-SRxxxx External passive shunt module

Thermal switch

Pin

Signal

RC-1

DC+

RC-2

INT

RC-3

COL

TS-1

TS1

TS-2

TS2

(1) 105 °C (221 °F), 600V.

98

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 99

Connect the Kinetix 6000 Drive System

Power Wiring Guidelines

Chapter 5

Use these guidelines as a reference when wiring the power connectors on your IAM and AM drive modules. For IPIM module power wiring guidelines, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003. IMPORTANT

For connector locations of the Kinetix 6000 drive modules, refer to 2094 IAM/AM Module Connector Data on page 58. When tightening screws to secure the wires, refer to the tables beginning on page 97 for torque values. When removing insulation from wires, refer to the tables beginning on page 97 for strip lengths.

IMPORTANT

To improve system performance, run wires and cables in the wireways as established in Establishing Noise Zones on page 37.

Follow these steps when wiring the connectors on your IAM and AM drive modules. 1. Prepare the wires for attachment to each connector plug by removing insulation equal to the recommended strip length. IMPORTANT

Use caution not to nick, cut, or otherwise damage strands as you remove the insulation.

2. Route the cable/wires to your IAM and AM drive modules. 3. Insert wires into connector plugs. Refer to connector pinout tables in Chapter 4 or the interconnect diagrams in Appendix A. 4. Tighten the connector screws. 5. Gently pull on each wire to make sure it does not come out of its terminal; reinsert and tighten any loose wires. 6. Insert the connector plug into the module connector.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

99

Page 100

Chapter 5

Connect the Kinetix 6000 Drive System

Wiring the IAM/AM Module Connectors

This section provides examples and wiring tables to assist you in making connections to the IAM and AM modules.

Wire the Control Power (CPD) Connector This example applies to any IAM, leader IAM, or follower IAM module. Figure 49 - IAM Module (CPD connector) Kinetix 6000 IAM Module, Top View

L2

1

CTR

2

IMPORTANT

L1

CTR

The 2094-AL75S, 2094-BL75S, and 2094-XL75S-C2 LIM modules can supply input power for up to eight axes. The 2094-XL75S-C1 LIM module can supply up to sixteen axes. The IPIM module control power load must be calculated for Kinetix 6000M systems and the LIM module control power input must have a sufficient current rating. If no LIM module can support the current requirement, then discrete components must be used. The National Electrical Code and local electrical codes take precedence over the values and methods provided. Implementation of these codes is the responsibility of the machine builder. Refer to Control Power on page 77 for more information and IAM Module (without LIM module) on page 192 for the interconnect drawing.

Table 63 - Control Power (CPD) Connector CPL Connector (LIM module) or Other Single-phase Input

CPD Connector (IAM module)

2094-ALxxS, 2094-BLxxS, or 2094-XL75S-Cx LIM Module

2094-AL09 and 2094-BL02 LIM Module

CPL Pin

Signal

CPL Pin

Signal

CPD Pin

Signal

1

CTRL 1

2

L1

1

CTRL 2

2

CTRL 2

1

L2/N

2

CTRL 1

100

Recommended Wire Size mm2 (AWG)

Strip Length mm (in.)

Torque Value N•m (lb•in)

2.5 (14)

10 (0.38)

0.5…0.6 (4.4…5.3)

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017