Page 101
Connect the Kinetix 6000 Drive System
Chapter 5
Wire the Input Power (IPD) Connector This example applies to any IAM module or common-bus leader IAM module. ATTENTION: Make sure the input power connections are correct when wiring the IPD connector plug and that the plug is fully engaged in the module connector. Incorrect wiring/polarity or loose wiring can cause explosion or damage to equipment. Figure 50 - IAM Module (IPD connector) Kinetix 6000 IAM Module, Top View
12
DC- + DC
34
56
L3 L2 L1
Table 64 - Input Power (IPD) Connections OPL Connector (LIM module) or Other Three-phase Input 2094-AL09 LIM Module
IPD Connector (IAM or leader IAM module)
2094-ALxxS, 2094-BLxxS, or 2094-XL75S-Cx LIM Modules
OPL Pin
Signal
OPL Pin
Signal
IPD Pin
Signal
1
L1’
4
L1’
6
L1
2
L2’
3
L2’
5
L2
3
L3’
2
L3’
4
L3
4
1
3
N/A
2
DC+
1
DC-
Table 65 - Termination Specifications IAM Module Cat. No.
Input VAC
Recommended Wire Size mm2 (AWG)
2094-AC05-Mxx-x
2.5 (14)
2094-AC09-M02-x
4.0 (12)
2094-AC16-M03-x
230V AC
10 (8)
2094-AC32-M05-x
30 (3)
2094-BC01-Mxx-x 2094-BC02-M02-x
2.5 (14)
2094-BC04-M03-x 2094-BC07-M05-x
460V AC
6 (10) 30 (3)
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Strip Length mm (in.)
Torque Value N•m (lb•in)
10 (0.38)
0.5…0.6 (4.4…5.3)
16 (0.63)
2.4…3.0 (21.6…26.5)
10 (0.38)
1.2…1.5 (10.6…13.2)
16 (0.63)
2.4…3.0 (21.6…26.5)
101
Page 102
Chapter 5
Connect the Kinetix 6000 Drive System
This example applies to a common-bus follower IAM module. ATTENTION: Make sure the common-bus power connections are correct when wiring the IPD connector plug and that the plug is fully engaged in the module connector. Incorrect wiring/polarity or loose wiring can cause explosion or damage to equipment. Figure 51 - IAM Module (IPD connector) Kinetix 6000 IAM Module, Top View
12
DC- + DC
34
56
L3 L2 L1
Table 66 - Input Power (IPD) Connections IPD Connector (IAM or follower IAM module) IPD Pin
Signal
6
N.C.
5
N.C.
4
N.C.
3 2
DC+
1
DC-
IMPORTANT
Do not connect three-phase input power to the common-bus follower IAM module.
Table 67 - Termination Specifications IAM Module Cat. No.
Recommended Wire Size mm2 (AWG)
2094-AC05-Mxx-x
2.5 (14)
2094-AC09-M02-x
4.0 (12)
2094-AC16-M03-x
230V AC
10 (8)
2094-AC32-M05-x
30 (3)
2094-BC01-Mxx-x 2094-BC02-M02-x
2.5 (14)
2094-BC04-M03-x 2094-BC07-M05-x
102
Input VAC
460V AC
6 (10) 30 (3)
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Strip Length mm (in.)
Torque Value N•m (lb•in)
10 (0.38)
0.5…0.6 (4.4…5.3)
16 (0.63)
2.4…3.0 (21.6…26.5)
10 (0.38)
1.2…1.5 (10.6…13.2)
16 (0.63)
2.4…3.0 (21.6…26.5)
Page 103
Connect the Kinetix 6000 Drive System
Chapter 5
Wire the Contactor Enable (CED) Connector This example applies to any IAM, common-bus leader IAM, or common-bus follower IAM module. Figure 52 - IAM Module (CED connector) Kinetix 6000 IAM Module, Top View
1
T CON
EN-
2
T CON
EN+
ATTENTION: Wiring the contactor enable relay is required. To avoid personal injury or damage to the drive, wire the contactor enable relay into your control string. Refer to Contactor Enable Relay on page 70. In common-bus configurations, the contactor enable (CED) connections for leader and follower drives must be wired in series to the control string. For interconnect diagrams, refer to Interconnect Diagram Notes beginning on page 188. Table 68 - Contactor Enable (CED) Connector LIM Module I/O (IOL) Connector or Other Control String 2094-ALxxS, 2094-BLxxS, or 2094-XL75S-Cx LIM Module
2094-AL09 and 2094-BL02 LIM Module
CED Pin
Signal
IO_COM1
IO_COM
1
CONT EN-
COIL_E2
COIL_A2
2
CONT EN+
Recommended Wire Size mm2 (AWG)
Strip Length mm (in.)
Torque Value N•m (lb•in)
2.5 (14) (1)
10 (0.38)
0.5…0.6 (4.4…5.3)
(1) The actual gauge of the contactor enable wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local codes.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
103
Page 104
Chapter 5
Connect the Kinetix 6000 Drive System
Wiring the Safe Torque-off (STO) Connector This example applies to any IAM or AM module equipped with the torque-off (STO) connector. Figure 53 - IAM/AM Module (STO connector)
Kinetix 6000 IAM/AM Module (AM module is shown)
1
1 2
3 4
5 6
7 8
Motion-allowed Jumper 9
Safe Torque-off (STO) Connector
Wiring Plug Header
Each IAM and AM module ships with the (9-pin) wiring-plug header and motion-allowed jumper installed in the safe torque-off connector. With the motion-allowed jumper installed, the safe torque-off feature is not used. Pinouts for the torque-off (STO) connector are shown on page 60. IMPORTANT
Pins STO-8 and STO-9 (24V+) are used by only the motion-allowed jumper. When wiring to the wiring-plug header, the 24V supply must come from an external source.
Table 69 - Safe Torque-off (STO) Connector STO Pin
Signal
1
FDBK2+
2
FDBK2-
3
FDBK1+
4
FDBK1-
5
SAFETY ENABLE2+
6
SAFETY ENABLE-
7
SAFETY ENABLE1+
8
24V +
9
24V_COM
Recommended Wire Size mm2 (AWG)
0.75 (18) (stranded wire with ferrule)
Strip Length mm (in.)
Torque Value N•m (lb•in)
7.0 (0.275)
0.235 (2.0)
1.5 (16) (solid wire)
To wire the safe torque-off connector in single axis or multi-axis configurations, refer to the Kinetix Safe Torque-off Feature Safety Reference Manual, publication GMC-RM002.
104
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 105
Connect the Kinetix 6000 Drive System
Chapter 5
Wire the Motor Power (MP) Connector Connections to the motor power (MP) connector include rotary motors, linear motors, and motor driven actuators. ATTENTION: Make sure the motor power connections are correct when wiring the MP connector plug and that the plug is fully engaged in the module connector. Incorrect wiring/polarity or loose wiring can cause explosion or damage to equipment. This example applies to AM modules and the inverter section of IAM modules. Figure 54 - IAM/AM Module (MP connector) Kinetix 6000 IAM/AM Module (IAM module is shown)
4
W U
1
2
3
V
Pivot-open Slide-open Cable Shield Clamp
Cable Shield Terminations Factory-supplied Bulletin 2090 motor power cables for motors and actuators are shielded, and the braided cable shield must terminate at the drive during installation. A small portion of the cable jacket must be removed to expose the shield braid. The exposed area must be clamped (with the clamp provided) on top of the IAM or AM modules and the power wires terminated in the motor power (MP) connector plug. SHOCK HAZARD: To avoid hazard of electrical shock, make sure shielded power cables are grounded at a minimum of one point for safety.
IMPORTANT
For TL-Series™ motors, also connect the 152 mm (6.0 in.) termination wire to the closest earth ground. Refer to Pigtail Terminations on page 106 for more information.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
105
Page 106
Chapter 5
Connect the Kinetix 6000 Drive System
Pigtail Terminations TL-Series motors have a short pigtail cable that connects to the motor, but is not shielded. The preferred method for grounding the TL-Series power cable on the motor side is to expose a section of the cable shield and clamp it directly to the machine frame. The motor power cable also has a 150 mm (6.0 in.) shield termination wire with a ring lug that connects to the closest earth ground. Use this method in addition to the cable clamp. The termination wire can be extended to the full length of the motor pigtail if necessary, but it is best to connect the supplied wire directly to ground without lengthening. Figure 55 - Pigtail Terminations Motor Power Cable
Cable Braid Clamped to Machine Frame. (1)
Connectors
Pigtail Cable TL-Series Motor
Machine Frame
150 mm (6.0) Termination
(1)
(1)
(1) Remove paint from machine frame to be sure of proper HF-bond between machine frame and motor case, shield clamp, and ground stud.
106
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 107
Connect the Kinetix 6000 Drive System
Chapter 5
MP-Series Motor and Actuator Connectors Bulletin MPL motors equipped with circular DIN connectors (specified by 4 or 7 in the catalog number) are not compatible with cables designed for motors equipped with bayonet connectors (specified by 2 in the catalog number). The motors with bayonet connectors are being discontinued. Table 70 - MP-Series (Bulletin MPL) Motor Catalog Numbers Motor Cat. No. /SpeedTec DIN Connectors
Motor Cat. No. /Threaded DIN Connectors
Motor Cat. No. /Bayonet Connectors
MPL-A/B15xxx-xx7xAA MPL-A/B2xxx-xx7xAA
MPL-A/B15xxx-xx4xAA MPL-A/B2xxx-xx4xAA
N/A
MPL-A/B3xxx-xx7xAA, MPL-A/B4xxx-xx7xAA, MPL-A/B45xxx-xx7xAA, MPL-A/B5xxx-xx7xAA
N/A
MPL-A/B3xxx-xx2xAA, MPL-A/B4xxx-xx2xAA, MPL-A/B45xxx-xx2xAA, MPL-A/B5xxx-xx2xAA
MPL-B6xxx-xx7xAA, MPL-B8xxx-xx7xAA, MPL-B9xxx-xx7xAA
N/A
MPL-B6xxx-xx2xAA, MPL-B8xxx-xx2xAA, MPL-B9xxx-xx2xAA
Bayonet connectors can be mounted facing the motor shaft or end plate and provide a separate connector for power, feedback, and brake connections. Circular DIN connectors rotate up to 180° and combine power and brake wires in the same connector, eliminating the brake connector. Figure 56 - Bayonet and Circular DIN Motor Connectors Bayonet Connectors
Side View
Feedback/Power/Brake Connectors
Feedback/Power Connectors
Threaded (M4) Connectors
Side View
Power and Brake Connector
Feedback Connector
SpeedTec (M7) Connectors Feedback Connector
Power and Brake Connector
Side View
MP-Series™ (Bulletin MPAR and MPAS) linear actuators and MP-Series (Bulletin MPS) stainless-steel motors have also transitioned from threaded (M4) to SpeedTec (M7) connectors.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
107
Page 108
Chapter 5
Connect the Kinetix 6000 Drive System
Motor Power Wiring Examples The procedure for wiring motor power varies slightly, depending on the motor family. The cables compatible with your motor or actuator depend on the connectors installed on the motor or actuator. Refer to MP-Series Motor and Actuator Connectors on page 107 for more information on circular DIN and bayonet connectors. Table 71 - Motor Power Cable Compatibility - Bayonet Connectors Motor/Actuator
Connector Motor/Actuator Cat. No. Type
MP-Series (Bulletin MPL) Bayonet
MPL-A/B3xxx-xx2xAA, MPL-A/B4xxx-xx2xAA, MPL-A/B45xxx-xx2xAA, MPL-A/B5xxx-xx2xAA, MPL-B6xxx-xx2xAA, MPL-B8xxx-xx2xAA, MPL-B960B-xx2xAA, MPL-B960C-xx2xAA, MPL-B980B-xx2xAA, and MPL-B980C-xx2xAA
Motor Power Cables (with brake wires)
Motor Power Cables (without brake wires)
2090-XXxPMP-xxSxx (1) N/A
MPL-B960D-xx2xAA, MPL-B980D-xx2xAA
2090-MCNPMP-6Sxx
1326AB (M2L/S2L)
1326AB-Bxxxx-M2L/S2L
2090-XXxPMP-xxSxx (1)
F-Series
F-xxxx
2090-XXNPHF-xxSxx
1326AB (resolver)
P-LOK
1326AB-Bxxxx-21
1326-CPx1T-L-xxx (continuous-flex)
N/A
(1) For Bulletin MPL or 1326AB motors equipped with bayonet connectors. These cables are available as standard (catalog number 2090-XXNPMP-xxSxx) and continuous-flex (catalog number 2090-XXTPMP-xxSxx).
Table 72 - Motor Power Cable Compatibility - Threaded DIN and Circular Plastic Connectors Motor/Actuator
Connector Motor/Actuator Cat. No. Type
MP-Series (Bulletin MPL) MP-Series (Bulletin MPS) MP-Series (Bulletin MPAS)
108
Motor Power Cables (without brake wires)
MPL-A/B15xxx-xx4xAA, MPL-A/B2xxx-xx4xAA Circular (threaded) DIN
MP-Series (Bulletin MPAR) TL-Series (Bulletin TLY)
Motor Power Cables (with brake wires)
MPS-A/Bxxxx MPAS-A/Bxxxx
2090-XXNPMF-xxSxx (standard) or 2090-CPWM4DF-xxAFxx 2090-CPBM4DF-xxAFxx (continuous-flex) (continuous-flex)
MPAR-A/B1xxx and MPAR-A/B2xxx (series A) Circular Plastic
TLY-Axxxx-H
2090-CPBM6DF-16AAxx (standard)
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
2090-CPWM6DF-16AAxx (standard)
Page 109
Connect the Kinetix 6000 Drive System
Chapter 5
Table 73 - Motor Power Cable Compatibility - SpeedTec DIN Connectors Motor/Actuator
Connector Motor/Actuator Cat. No. Type
MP-Series (Bulletin MPL)
MPL-A/B15xxx-xx7xAA, MPL-A/B2xxx-xx7xAA, MPL-A/B3xxx-xx7xAA, MPL-A/B4xxx-xx7xAA, MPL-A/B45xxx-xx7xAA, MPL-A/B5xxx-xx7xAA, MPL-B6xxx-xx7xAA, MPL-B8xxx-xx7xAA MPL-B9xxx-xx7xAA
MP-Series (Bulletin MPM)
MPM-A/Bxxxx
MP-Series (Bulletin MPF)
MPF-A/Bxxxx
MP-Series (Bulletin MPS) RDD-Series™
Circular (SpeedTec) DIN
MPS-A/Bxxxx RDD-Bxxxx
LDC-Series™
LDC-Cxxxx
MP-Series (Bulletin MPAS)
MPAS-A/Bxxxx
MP-Series (Bulletin MPAI)
MPAI-A/Bxxxx
MP-Series (Bulletin MPAR)
MPAR-A/B3xxx, MPAR-A/B1xxx and MPAR-A/B2xxx (series B)
LDL-Series™
LDL-xxxxxxx
Motor Power Cables (1) (with brake wires)
Motor Power Cables (1) (without brake wires)
2090-CPBM7DF-xxAAxx (standard) or 2090-CPBM7DF-xxAFxx (continuous-flex)
2090-CPWM7DF-xxAAxx (standard) or 2090-CPWM7DF-xxAFxx (continuous-flex)
(1) You must remove the motor-side o-ring when using 2090-CPxM7DF-xxAxxx cables.
These cables contain only the three-phase power wires. The motors/actuators either have no brake or a separate connector for brake connections. Thermal switch wires are included in the feedback cable. Refer to Axis Module/Rotary Motor Wiring Examples beginning on page 198 for interconnect diagrams. Figure 57 - Motor Power Terminations (cables without brake wires)
Motor Cable Shield Clamp
CTRL 2 CTRL 1
U
L3 L2 L1
2
W V
DC+
1
DC-
3
4
Motor Power (MP) Connector Plug
MBRK MBRK + COM PWR DBRK DBRK +
CONT ENCONT EN+
RX
DPI
TX
BAUD RATE
Kinetix 6000 IAM/AM Module (IAM module is shown)
The cable shield clamp shown above is mounted to an IAM module. Cables attach to the clamp on each AM module in the same way.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
109