Kinetix 6000 Multi-axis Servo Drives User Manual: Ch5 - Connect the Kinetix 6000 Drive System, pages 128 to 134

Pages 128 to 134 of 290, from Kinetix 6000 Multi-axis Servo Drives User Manual

The original document is the PDF (21 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 128

Chapter 5

Connect the Kinetix 6000 Drive System

IPIM Module Connections

An overview of the Kinetix 6000M integrated drive-motor (IDM) system connections are shown here. • Refer to Chapter 2 on page 25, for noise zone considerations. • Refer to Appendix A, on page 212, for an interconnect diagram featuring the Kinetix 6000M integrated drive-motor (IDM) system. • Refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003, for more information when wiring your IPIM module. IMPORTANT

To improve system performance, run wires and cables in the wireways as established in Chapter 2.

Figure 71 - IPIM Module Connections 2094-SEPM-B24-S IPIM Module (top view) 2090-CHBP8S8-12AAxx Hybrid Cables (IDM unit-to-unit)

DC+

DC-

SH1 42+ 42SH2 CN+ CNOUT RTN SH3 SE1 SESE2

Cable Clamp

1 2 3 4 5 6 7 8 9 10 11 12

2090-CTHP8 Hybrid Terminator (last IDM unit only)

1 2 3 4 5 6 7 8 9

2090-CTSRP Network Terminator (last IDM unit only) 2090-CNSxPxS-AAxx Network Cables

DC Bus Connector Inter-module Communication Connector Safe Torque Off Connector Enable Input Connector

2090-CHBIFS8-12AAxx Hybrid Cable (IPIM module to first IDM unit)

• Enable Connector • Sercos Connectors (TX, RX) MDF-SBxxxxx-Qx8xB-S IDM Units 2094-SEPM-B24-S IPIM Module (front view) D

901

456

78

S10

456

23

78

901

S1

1

N

2

3

23

2090-CNSSPxS-AAxx Network Cable Ethernet Connectors (not in view)

• Digital Input Connectors (1, 2, 3) • Network Node Address Switches (S1, S10) • Status Indicators (D, N)

128

PORT 1

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

PORT 2

NETWORK

IDM Network Connector

Page 129

Connect the Kinetix 6000 Drive System

RBM Module Connections

Chapter 5

Follow these guidelines when wiring your Bulletin 2090 Resistive Brake Module (RBM). IMPORTANT

To be sure of system performance, run wires and cables in the wireways as established in Chapter 2.

If your application requires an RBM module and you are wiring to a Kinetix 6000 IAM/AM module, then refer to the following: • Cable Categories for Kinetix 6000 Systems on page 45 to establish noise zones when mounting the RBM module on your panel. • Resistive brake module to Kinetix 6000 drive interface cable (catalog number 2090-XXNRB-xxF0Px). • The example diagram below and others in Appendix G, beginning on page 269. • The installation instructions provided with your RBM module, publication 2090-IN009. Figure 72 - RBM Module Connections I/O Connections (TB3) Connector Kinetix 6000 IAM/AM Module, Top View (IAM module is shown)

Motor Power Cable Clamp (exposed shield CTRL 2 CTRL 1 W V U

L3 L2 L1

MBRK MBRK +

CONT ENCONT EN+

DBRK DBRK +

Drive Connection (TB1) Connector

1 2 3 4

DCDC+

Contactor Status Indicator RBM Module, Front View

Motor Connections (TB2) Connector

COM PWR

RX

DPI

TX

BAUD RATE

Exposed Shield Braid Under Clamp 2090-XXNRB-xxF0Px RBM/Kinetix 6000 Interface Cable

Motor Cable Shield Clamps Bulletin 2090 Motor Power Cable To Motor

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

129

Page 130

Chapter 5

Connect the Kinetix 6000 Drive System

This procedure assumes you have your Logix5000™ Sercos interface module/ PCI card and Kinetix 6000 IAM/AM modules mounted and are ready to connect the fiber-optic cables.

Sercos Fiber-optic Cable Connections

The Sercos fiber-optic ring is connected by using the Sercos receive (Rx) and transmit (Tx) connectors. Refer to page 58 to locate the Sercos connectors on your Kinetix 6000 IAM/AM module and IPIM module. Refer to the figure below to locate the connectors on your Logix5000 Sercos interface module or PCI card. Plastic cable is available in lengths up to 32 m (105.0 ft). Glass cable is available in lengths between 50 m (164.2 ft) and 200 m (656.7 ft). Figure 73 - CompactLogix, ControlLogix, and SoftLogix Sercos Connectors

F 1

45 23 6 7

The Logix Designer Application

ABCDE

OK

89

CP

ControlLogix® Controller 1756-MxxSE Sercos interface Module 0

SERCOS interfaceTM

CompactLogix™ Controller 1768-M04SE Sercos interface Module

OK CP

Front View

TX

Tx (rear) Rx (front)

Tx (rear)

Front View

RX

Rx (front)

Bottom View

SoftLogix™ Controller 1756-PM16SE Sercos interface PCI Card (as viewed from the back of your personal computer) Sercos Transmit Connector, Tx Sercos Receive Connector, Rx

Sercos Receive Connector, Rx (front) Sercos Transmit Connector, Tx (rear)

Connect the cable from transmit on the Logix5000 module to receive on the IAM/AM or IPIM module, then transmit to receive (drive to drive), and from transmit on the last drive back to receive on the Logix5000 module. ATTENTION: To avoid damage to the Sercos Rx and Tx connectors, use only finger-tight torque when attaching the fiber-optic cables to the Kinetix 6000 IAM/AM modules and IPIM module. Do not use a wrench or any other mechanical assistance. For more information, refer to Fiber-optic Cable Installation and Handling Instructions, publication 2090-IN010. SoftLogix and ControlLogix controllers are used in the following examples; however, CompactLogix controllers connect in the same manner.

130

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 131

Connect the Kinetix 6000 Drive System

Chapter 5

0 3456 72

ABCDE

Figure 74 - Fiber-optic Cable Example - SoftLogix Controller F 1

89

OK CP

Transmit Receive

TX

SoftLogix Controller 1784-PM16SE Sercos interface PCI Card

RX

Sercos fiber-optic ring Receive

Transmit

Receive

Transmit

Kinetix 6000 System

Kinetix 6000 System

In this example, two Logix5000 modules are installed in separate chassis. Figure 75 - Fiber-optic Cable Example - Two Logix5000 Controllers 1756-MxxSE Sercos interface Modules SERCOS interfaceTM

SERCOS interfaceTM

CP

OK

Tx (rear) Rx (front)

Transmit

Logix5000 Controller (ControlLogix controller is shown) Receive

CP

OK

Logix5000 Controller (ControlLogix controller is shown)

Tx (rear) Rx (front)

Transmit

Receive Transmit

Receive

Sercos Fiber-optic Ring Receive

Transmit

Kinetix 6000 System

Sercos Fiber-optic Ring

IMPORTANT

Clean the fiber-optic cable connectors prior to installation. Dust in the connectors can reduce signal strength. For more information, refer to Fiberoptic Cable Installation and Handling Instructions, publication 2090-IN010.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

131

Page 132

Chapter 5

Connect the Kinetix 6000 Drive System

When connecting 2094-BM03-x and 2094-BM05-x (double-wide) axis modules, use 2090-SCEP0-2, 0.2 m (7.0 in.) cables. When connecting 2094AMxx-x, 2094-BMP5-x, 2094-BM01-x, and 2094-BM02-x (single-wide) axis modules, use 2090-SCEP0-1, 0.1 m (5.1 in.) cables. Figure 76 - Fiber-optic Cable Example - Logix5000 Controller with Double-wide Drive Modules 1756-M16SE Sercos Interface Module Logix5000 Controller (ControlLogix controller is shown)

Sercos Fiber-optic Ring SERCOS interfaceTM

CP

OK

0.2 m 0.1 m (7.1 in.) (5.1 in.) Tx (rear) Rx (front)

Kinetix 6000 System (5-axis power rail)

In this example, the second Kinetix 6000 system is mounted in a separate cabinet and connected with bulkhead adapters. IMPORTANT

To avoid signal loss, do not use bulkhead adapters to connect glass cables. Use only bulkhead adapters for making plastic-to-plastic cable connections.

Figure 77 - Fiber-optic Cable Example - Logix5000 Controller with Bulkhead Adapters 1756-MxxSE Sercos Interface Module

Cabinet

SERCOS interfaceTM

CP

Logix5000 Controller (ControlLogix controller is shown)

OK

Tx (rear) Rx (front)

Transmit

Sercos Fiber-optic Bulkhead Adapter

Receive Sercos Fiber-optic Ring Receive

Sercos Ring

Transmit

Receive

Transmit

Sercos Fiber-optic Bulkhead Adapter Kinetix 6000 System

132

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Kinetix 6000 System

Page 133

Connect the Kinetix 6000 Drive System

Kinetix 6000M Integrated Drive-Motor Sercos Connections

Chapter 5

The Kinetix 6000 Sercos ring includes the Kinetix 6000M integrated drivemotor (IDM) units and IDM power interface modules (IPIM). Fiber-optic connections are made from drive-to-drive and drive-to-IPIM module. IDM network connections continue from the IPIM module to the IDM units. Because the Kinetix 6000M (IPIM) module has fiber-optic cable connectors positioned identical to the Kinetix 6000 (2094-BMxx-S) drives, the IPIM module uses the same fiber-optic cable lengths as the drive modules. Figure 78 - Fiber-optic Cable Example - Logix5000 Controller with Kinetix 6000M (IPIM) Module 1756-M16SE Sercos Interface Module

Logix5000 Controller (ControlLogix controller is shown)

Sercos Fiber-optic Ring

0.1 m (5.1 in.)

SERCOS interfaceTM

CP

OK

Tx (rear) Rx (front)

Kinetix 6000 System (4-axis power rail)

2094-SEPM-B24-S IPIM Module 2094-BMxx-x Single-wide AM Modules

In this example, all the drive modules and the IPIM module are on the same Sercos ring. The ring begins and ends at the 1756-M16SE Sercos module. IDM units (not shown for simplicity) connected to the IPIM module, are also part of this Sercos ring. For more Kinetix 6000 IDM system examples including the IDM units, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

133

Page 134

Chapter 5

Connect the Kinetix 6000 Drive System

Ethernet Cable Connections

This procedure assumes you have your ControlLogix or CompactLogix EtherNet/IP module and Bulletin 2094 control modules mounted and are ready to connect the Ethernet network cables. The EtherNet/IP network is connected by using the PORT 1 and/or PORT 2 connectors. Table 97 - EtherNet/IP Connector Location Drive Family

Cat. No.

EtherNet/IP Network

Refer to

Kinetix 6000M

2094-SEPM-B24-S

Monitoring, diagnostics, and firmware upgrades page 59

Figure 79 - ControlLogix and CompactLogix Ethernet Port Locations CompactLogix 5370 L1, L2, and L3 Controllers 1769-L36ERM controller is shown.

ControlLogix Controller 1756-ENxTR EtherNet/IP module is shown. LNK1 LNK2 NET OK

ControlLogix Ethernet Ports The 1756-EN2T modules have only one port, 1756-EN2TR and 1756-EN3TR modules have two.

2

Front Views

00:00:BC:2E:69:F6 1 (Front) 2 (Rear)

1

Bottom Views

Port 1, Front Port 2, Rear

134