Kinetix 6000 Multi-axis Servo Drives User Manual: Ch6 - Configure and Start the Kinetix 6000 Drive System, pages 135 to 144

Pages 135 to 144 of 290, from Kinetix 6000 Multi-axis Servo Drives User Manual

The original document is the PDF (21 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 135

Chapter

6

Configure and Start the Kinetix 6000 Drive System

This chapter provides procedures for configuring the Kinetix® 6000 drive components with your Logix5000™ Sercos communication module. Topic

Page

Configure the Kinetix 6000M Integrated Drive-Motor System

135

Configure the Drive Modules

136

Configure the Logix5000 Sercos interface Module

142

Apply Power to the Kinetix 6000 Drive

155

Test and Tune the Axes

157

Configure Drive Parameters and System Variables

162

TIP

Configure the Kinetix 6000M Integrated Drive-Motor System

Before you begin, make sure you know the catalog number for each drive component, the Logix5000 module, and the servo motor/actuator in your motion control application.

Configuration for the Kinetix 6000M integrated drive-motor (IDM) system follows a procedure similar to what is described in this chapter. You’ll assign each IDM unit a node address and configure the IDM system in the Logix Designer application. The IPIM module does not require configuration for your IDM units to be configured in the Sercos ring. However, you can include the IPIM module in your project by connecting it to a configured Ethernet module in the Logix5000 chassis and adding it under the Ethernet module in the I/O configuration tree. An Add-On Profile is also needed to use the IPIM module in the project, but as a result you can view IPIM module status information in the configuration software and use it in your application program. The Ethernet connection is also used to upgrade the IPIM module firmware by using ControlFLASH™ software. For system configuration and startup procedures specific to the IDM system, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

135

Page 136

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Configure the Drive Modules

Follow these steps to configure the integrated axis module (IAM) and axis modules (AM). IMPORTANT

If you have one or more IDM power interface modules (IPIM) on your power rail, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003, for system configuration information specific to the Kinetix 6000M IDM system.

1. Verify that no power is applied to the IAM and AM modules and that the communication cables are plugged into the appropriate connectors. To verify communication, refer to Sercos Fiber-optic Cable Connections on page 130. To Configure

Begin With

The IAM module step 2

Any AM module step 4

Kinetix 6000M IDM system (1)

Kinetix 6000M Integrated Drive-Motor User Manual, publication 2094-UM003.

(1) Sercos fiber-optic cable connections for the Kinetix 6000M integrated drive-motor (IDM) system are on page 133.

2. Set the base node address for the IAM module by setting the Node Address switches. Valid node addresses for Sercos communication are 01…99. The left switch sets the most significant digit (MSD) and the right switch sets the least significant digit (LSD). To

Press

Increment the (MSD/LSD) node address

The plus (+) switch.

Decrement the (MSD/LSD) node address

The minus (-) switch.

Decrements MSD MSD Increments MSD

Decrements LSD LSD Increments LSD

Setting the base node address on the IAM module determines the node address for the IAM (inverter) module. Node addressing for all slot locations on the same power rail increment (from the IAM inverter) left to right. 3. Cycle control power to initialize the IAM module. IMPORTANT

136

The base node address setting takes effect only after the IAM power module is initialized.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 137

Configure and Start the Kinetix 6000 Drive System

IMPORTANT

Chapter 6

When two or more IAM modules are connected to the same Sercos interface module, each node address must be unique. Refer to the node addressing examples beginning on page 138.

4. Set the Sercos communication rate with DIP switches 2 and 3. For This Communication Rate

Set Switch 2

Set Switch 3

4 Mbps

OFF

ON

8 Mbps (1)

ON

OFF

(1) The Kinetix 6000M IDM system supports only 8 Mbps and is hardwired for this setting.

5. Set the Sercos optical power level with DIP switch 1. For This Optical Power Level

Set Switch 1

Low

OFF

High

ON

The optical power setting you use depends on the type of Sercos cable you’re using and the length of the cable. Power Setting (1)

Plastic Cable (2)

Glass Cable (3)

Low

≤ 15 m (49.2 ft)

≤ 100 m (382 ft)

High

> 15 m (49.2 ft)

> 100 m (382 ft)

(1) Other factors include attenuation caused by the use of bulkhead connectors and cable bending. (2) Catalog numbers 2090-SCxP. (3) Catalog numbers 2090-SCVG.

DIP Switches Set for 8 Mbps Applications (high power setting)

3

1

2

3 ON

ON

OFF

OFF

2

Kinetix 6000 IAM/AM Module, (AM module is shown)

1

DIP Switches Set for 4 Mbps Applications (high power setting)

Switch in OFF Position Note: Switch numbers as seen on the IAM are upside down in this orientation.

Sercos Communication Rate and Optical Power Switches

Switch numbers shown above are in ON Position Switch turned around for clarity.

6. Repeat step 4 and step 5 for each 2094-xMxx-x AM module.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

137

Page 138

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Figure 80 - Node Addressing Example 1 1756-MxxSE Sercos interface Module SERCOS interfaceTM

CP

OK

Logix5000 Controller (ControlLogix® controller is shown) Tx (rear) Rx (front)

Transmit

Receive Sercos Fiber-optic Ring Receive

Receive Kinetix 6000 Drive System 1 (6-axis power rail)

Transmit Kinetix 6000 Drive System 2 (2-axis power rail)

Transmit

08 = AM module (axis 2) node address 07 = IAM module (axis 1) base node address

0 1

06 = Slot-filler Module slot location 05 = Shunt Module slot location 04 = AM Module (axis 4) node address 03 = AM Module (axis 3) node address 02 = AM Module (axis 2) node address 01 = IAM Module (axis 1) base node address

Base Node Address Switches

In Example 1, the Kinetix 6000 (6-axis) drive system 1 power rail contains one IAM module, three AM modules, one shunt module, and one slot-filler module. The shunt module and slot-filler modules are not assigned a Sercos node address, but the system identifies them with a slot location. Kinetix 6000 (2-axis) drive system 2 power rail contains one IAM module and one AM module. The base node address of the (system 2) IAM module must be set for an address of ≥007.

138

IMPORTANT

The node address for each axis module is determined by the base nodeaddress switch setting on the IAM module. Do not position axis modules to the right of shunt or slot-filler modules. The added distance between non-adjacent axes can increase electrical noise and impedance, and requires longer fiber-optic cable lengths.

IMPORTANT

Slot-filler modules must be used to fill any unoccupied slot on the power rail. However, you can replace slot-filler modules with AM modules or the 2094-BSP2 shunt module (maximum one 2094-BSP2 shunt module per power rail).

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 139

Configure and Start the Kinetix 6000 Drive System

Chapter 6

Figure 81 - Node Addressing Example 2 1756-MxxSE Sercos interface Module 1

1756-MxxSE Sercos interface Module 2

SERCOS interfaceTM

CP

OK

SERCOS interfaceTM

Logix5000 Controller (ControlLogix controller is shown)

CP

Tx (rear)

Logix5000 Controller (ControlLogix controller is shown)

Tx (rear)

Rx (front)

Transmit

OK

Rx (front)

Receive

Transmit

Receive

Sercos Fiber-Optic rings

Transmit

Receive Transmit

Receive Kinetix 6000 Drive System (8-axis power rail)

0 1

08 = Slot-filler module slot location 07 = AM module (axis 7) node address 06 = AM module (axis 6) node address 05 = AM module (axis 5) node address 04 = AM module (axis 4) node address 03 = AM module (axis 3) node address 02 = AM module (axis 2) node address 01 = IAM module (axis 1) base node address

Base Node Address Switches

In this example, Sercos interface module 1 controls axes 1…4 and module 2 controls axes 5…7. The slot-filler module is not assigned a Sercos node address, but the system identifies it with a slot location. You can mount the two Sercos interface modules in two separate ControlLogix chassis (as shown) or you can mount them in the same chassis. IMPORTANT

The node address for each axis module is determined by the base nodeaddress switch setting on the IAM module. Do not position axis modules to the right of shunt or slot-filler modules. The added distance between non-adjacent axes can increase electrical noise and impedance, and requires longer fiber-optic cable lengths.

IMPORTANT

Slot-filler modules must be used to fill any unoccupied slot on the power rail. However, you can replace slot-filler modules with AM modules or the 2094-BSP2 shunt module (maximum one 2094-BSP2 shunt module per power rail).

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

139

Page 140

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Figure 82 - Node Addressing Example 3 1756-MxxSE Sercos interface Module SERCOS interfaceTM

CP

OK

Logix5000 Controller (ControlLogix controller is shown)

Tx (rear) Rx (front)

Transmit

Receive Sercos Fiber-optic Ring

Receive

Transmit

Kinetix 6000 Drive System (8-axis power rail)

0 1

08 = Slot-filler module slot location 07 = AM module (axis 4) node address 06 = Not Used (AM module rightmost slot) 05 = AM module (axis 3) node address 04 = Not Used (AM module rightmost slot) 03 = AM module (axis 2) node address 02 = Not Used (IAM module rightmost slot) 01 = IAM module (axis 1) base node address

Base Node Address Switches

In this example, the Kinetix 6000 (8-axis) power rail contains a double-wide IAM module, two double-wide AM modules, one single-wide AM module, and one slot-filler module. The slot-filler module is not assigned a Sercos node address, but the system identifies it with a slot location. The leftmost slot of a double-wide module determines the node address. So, in the example above, node addresses 02, 04, and 06 (the rightmost slots of the double-wide modules) are not used.

140

IMPORTANT

The node address for each axis module is determined by the base nodeaddress switch setting on the IAM module. Do not position axis modules to the right of shunt or slot-filler modules. The added distance between non-adjacent axes can increase electrical noise and impedance, and requires longer fiber-optic cable lengths.

IMPORTANT

Slot-filler modules must be used to fill any unoccupied slot on the power rail. However, you can replace slot-filler modules with AM modules or the 2094-BSP2 shunt module (maximum one 2094-BSP2 shunt module per power rail).

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 141

Configure and Start the Kinetix 6000 Drive System

Chapter 6

Figure 83 - Node Addressing Example 4 1756-MxxSE Sercos Interface Module

Sercos Fiber-optic Ring

0.1 m (5.1 in.)

SERCOS interfaceTM

Logix5000 Controller (ControlLogix controller is shown)

OK

CP

Receive

Transmit

Tx (rear) Rx (front)

Transmit

Receive

Kinetix 6000 System (5-axis power rail) 0 1

05 = Slot-filler module slot location 04 =AM module (axis 3) node address 03 = AM module (axis 2) node address 02 = IPIM module slot location 01 = IAM module (axis 1) base node address

Base Node Address Switches

MDF-SBxxxxx IDM Unit 78

D

23

N

20 = IDM unit 1 21 = IDM unit 2 22 = IDM unit 3 23 = IDM unit 4

23

23

78

S10

78

901

901

S10

456

456

78

901

S10

78

901

901

78

S1

456

S1

78

901

901

S1

78

456

901

78

456

2

456

1

3

456

23

23

23

23

23

S10

456

456

901

78

23

S1

23

456

901

Network Node Address Switches (covers removed)

In this example, the Kinetix 6000 (5-axis) power rail contains two single-wide axis modules and one IDM system. Neither the slot-filler or IPIM module is assigned a Sercos node address, but the system identifies them with a slot location. Node addressing on the power rail is no different than the previous examples. Node address 02 and 05 are available for any of the IDM units, but to avoid confusion, the node addressing for the IDM units was started at 20. Unlike the axis modules, each IDM unit has switches that determine its node address. In this example, the IDM unit node addressing is sequential, but that’s optional. IMPORTANT

Creating a duplicate node address between the axis modules mounted on the power rail and the IDM system (in the same Sercos ring) generates error code E50. Each node address on the Sercos ring must be unique within the range of 01…99. Axes on the same power rail as the IPIM module do not have to be in the same Sercos ring as the IDM units.

IMPORTANT

Slot-filler modules must be used to fill any unoccupied slot on the power rail. However, you can replace slot-filler modules with AM modules or the 2094-BSP2 shunt module (maximum one 2094-BSP2 shunt module per power rail).

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

141

Page 142

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Configure the Logix5000 Sercos interface Module

This procedure assumes that you have wired your Kinetix 6000 system and have configured the communication rate and optical power switches. For help with using the Logix Designer application as it applies to configuring the ControlLogix, CompactLogix™, or SoftLogix™ Sercos modules, refer to Additional Resources on page 12.

Configure the Logix5000 Controller Follow these steps to configure the Logix5000 controller. 1. Apply power to your Logix5000 chassis containing the Sercos interface module/PCI card and open your Logix Designer application. 2. From the File menu, choose New. The New Controller dialog box opens.

3. Configure the new controller. a. From the Type pull-down menu, choose the controller type. b. From the Revision pull-down menu, choose the revision. c. Type the file Name. d. From the Chassis Type pull-down menu, choose the chassis. e. Enter the Logix5000 processor slot. 4. Click OK. 5. From the Edit menu, choose Controller Properties.

142

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 143

Configure and Start the Kinetix 6000 Drive System

Chapter 6

The Controller Properties dialog box opens.

6. Click the Date/Time tab. 7. Check Enable Time Synchronization. This assigns the controller as the Grandmaster clock. The motion modules set their clocks to the module you assign as the Grandmaster. IMPORTANT

You can assign only one module in the Logix5000 chassis as the Grandmaster clock.

8. Click OK.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

143

Page 144

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Configure the Logix5000 Module Follow these steps to configure the Logix5000 module. 1. Right-click I/O Configuration in the Controller Organizer and choose New Module. The Select Module dialog box opens.

2. Expand the Motion category and select 1756-MxxSE, 1756L60M03SE, 1768-M04SE, or 1784-PM16SE as appropriate for your actual hardware configuration. In this example, the 1756-M16SE module is selected. 3. Click OK. The New Module dialog box opens.

4. Configure the new module. a. Type the module Name. b. Enter the Logix5000 Sercos module slot (leftmost slot = 0). c. Check Open Module Properties. 5. Click OK. Your new module appears under the I/O Configuration folder in the Controller Organizer and the Module Properties dialog box opens.

144

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017