The text of a manual · part 18 of 33

Kinetix 6000 Multi-axis Servo Drives User Manual: Ch6 - Configure and Start the Kinetix 6000 Drive System, pages 145 to 154

Pages 145 to 154 of 290, from Kinetix 6000 Multi-axis Servo Drives User Manual

The original document is the PDF (21 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 145

Configure and Start the Kinetix 6000 Drive System

Chapter 6

6. Click the Sercos Interface tab and reference the table below.

Logix5000 Sercos Module

Number of Axes

1756-M03SE or 1756-L60M03SE

Up to 3

1756-M08SE

Up to 8

1756-M16SE or 1784-PM16SE

Up to 16

1768-M04SE

Up to 4

Data Rate

4 or 8 Mbps

7. Verify that the Data Rate setting matches DIP switches 2 and 3 (communication rate), as set on the IAM and AM module, or choose the Auto Detect setting. 8. From the Cycle Time pull-down menu, choose the Cycle Time according to the table below. Data Rate

4 Mbps

Number of Axes

Cycle Time

Up to 2

0.5 ms

Up to 4

1 ms

Up to 8

2 ms

No support for axes 9…16 8 Mbps (1)

Up to 4

0.5 ms

Up to 8

1 ms

Up to 16

2 ms

(1) The Kinetix 6000M IDM system supports only 8 Mbps and is hardwired for this setting.

TIP

The number of axes/module is limited to the number of axes as shown in step 6.

9. From the Transmit Power pull-down menu, choose High. The default setting is High, however this setting is dependent on the cable length (distance to next receiver) and cable type (glass or plastic). 10. Enter the Transition to Phase setting. The Transition to Phase default setting is 4 (phase 4). The Transition to Phase setting stops the ring in the phase specified. 11. Click OK. 12. Repeat step 1 through step 11 for each Logix5000 module.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

145

Page 146

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Configure the Kinetix 6000 Drive Modules Follow these steps to configure the Kinetix 6000 drive modules. 1. Right-click the Logix5000 module you just created and choose New Module. The Select Module dialog box opens.

2. Expand the Drives category and select drive components appropriate for your actual hardware configuration. IMPORTANT

In order for the Kinetix 6000 drive to communicate with the Sercos interface module (indicated by three solid-green status indicators on the Sercos module), you must be using RSLogix 5000® software, version 11.00 or later, or the Logix Designer application.

3. Click OK. The New Module dialog box opens.

4. Configure the new module. a. Type the module Name. b. Enter the Node address. Set the node address in the software to match the node setting on the drive. Refer to Configure the Drive Modules, step 2, on page 136. 146

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 147

Configure and Start the Kinetix 6000 Drive System

Chapter 6 c. Check Open Module Properties. 5. Click OK. 6. Click the Associated Axes tab.

7. Click New Axis. The New Tag dialog box opens.

8. Type the axis Name. AXIS_SERVO_DRIVE is the default Data Type. 9. Click OK. The axis appears under the Ungrouped Axes folder in the Controller Organizer. 10. Assign your axis to Node 1.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

147

Page 148

Chapter 6

Configure and Start the Kinetix 6000 Drive System

11. Click Apply. TIP

With drive firmware revision 1.80 or later, and the Logix Designer application or RSLogix 5000 software, version 13 or later, it is possible to configure the Auxiliary Axis feedback port as a Feedback Only axis. With this feature, you can configure each IAM inverter or AM module to appear as two axes/nodes on the Sercos ring. The base node is the servo axis using the motor feedback, and the base node (plus 128) is a feedback-only axis that uses the auxiliary feedback port. Auxiliary feedback is not supported by the Kinetix 6000M IDM units.

The Auxiliary Axis (Node 129) is configured identical to Node 1 by clicking New Axis and creating a new tag. 12. Click Apply if you made changes. 13. Click the Power tab.

14. From the Bus Regulator Catalog Number pull-down menu, choose the shunt option appropriate for your actual hardware configuration. If your IAM module is

Configured as an IAM module or common-bus leader IAM module (1)

Configured as a common-bus follower IAM module (2)

And your hardware configuration includes this shunt option

Then choose

Internal shunt resistors only

Internal or <none>

Bulletin 2094 (rail mounted) shunt module

2094-BSP2

Bulletin 1394 passive shunt module (connected to the 2094-BSP2 shunt module)

1394-SRxxxx

External active shunt module

Internal or <none>

N/A. Shunts are disabled on follower IAM module

CommonBus Follow

(1) Drive does not accept Internal, <none>, 2094-BSP2, or 1394-SRxxxx selection if DC bus voltage is present without having three-phase power applied. (2) Drive does not accept CommonBus Follow selection if three-phase power or DC bus power is applied.

148

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 149

Configure and Start the Kinetix 6000 Drive System

Chapter 6

To avoid damage to your Bulletin 1394 external shunt module when wired to the 2094-BSP2 shunt module, verify that the proper 230V or 460V fuse is installed prior to applying power. Refer to Kinetix Motion Accessories Specifications Technical Data, publication KNX-TD004, for more information. IMPORTANT

When configured to use the Bulletin 1394 or 2094 shunt modules, the IAM bus regulator capacity attribute displays the utilization of total shunt power available (as a percent) based on the power rail configuration. Refer to Kinetix Motion Accessories Specifications Technical Data, publication KNX-TD004, for shunt power specification and examples.

15. Calculate additional bus capacitance, if this applies to your application, and enter the value here (version 20.00 or later), or refer to Appendix E on page 253 to set the Add Bus Cap parameter. The Additional Bus Capacitance field applies only to the IAM module. IMPORTANT

DC common-bus applications must calculate Total Bus Capacitance and Additional Bus Capacitance and set the Add Bus Cap parameter in the leader IAM module. However, you can set the parameter as shown in step 15 or by using DriveExplorer™ software or the Logix Designer application, as shown in Appendix E. Refer to Appendix C beginning on page 227, for more information on making the calculations. Refer to Appendix E beginning on page 253, for more information on setting the Add Bus Cap parameter.

16. Click OK. 17. Repeat step 1 through step 10 for each Bulletin 2094 AM module and each IDM unit.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

149

Page 150

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Configure the Motion Group Follow these steps to configure the motion group. 1. Right-click Motion Groups in the Controller Organizer and choose New Motion Group. The New Tag dialog box opens.

2. Type the new motion group Name. 3. Click OK. The new motion group appears under the Motion Groups folder. 4. Right-click the new motion group and choose Properties. The Motion Group Properties dialog box opens.

5. Click the Axis Assignment tab and move your axes (created earlier) from Unassigned to Assigned. 6. Click the Attribute tab and edit the default values as appropriate for your application. 7. Click OK.

150

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 151

Configure and Start the Kinetix 6000 Drive System

Chapter 6

Configure Axis Properties The peak current ratings of the Kinetix 6000 AM modules (series A, B, and C) are configured at the factory as 150% of continuous current. You can program 460V (series B and C) AM modules and the equivalent IAM (inverter) modules, for up to 250% of continuous inverter current. Refer to Appendix F on page 259 to recalculate torque and acceleration or deceleration limit values, and paste them into the appropriate Axis Properties dialog box in the Logix Designer application. Follow these steps to configure Axis properties for motor feedback. 1. Right-click an axis in the Controller Organizer and choose Properties. The Axis Properties dialog box opens.

2. Click the Drive/Motor tab. 3. Click Change Catalog. The Change Catalog Number dialog box opens.

4. Select the motor catalog number appropriate for your application. To verify the motor catalog number, refer to the motor name plate. 5. Click OK.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

151

Page 152

Chapter 6

Configure and Start the Kinetix 6000 Drive System

6. On the Drive/Motor tab, check Drive Enable Input Checking. When checked (default), means a hard drive-enable input signal is required. Uncheck to remove that requirement. 7. Click Apply. 8. Click the Motor Feedback tab and verify the Feedback Type shown is appropriate for your actual hardware configuration. 9. Click the Units tab and edit default values as appropriate for your application. 10. Click the Conversion tab and edit default values as appropriate for your application.

In this example, Rotary is chosen from the Positioning Mode pull-down menu. 11. Click Apply if you made changes. 12. Click the Fault Actions tab.

13. Click Set Custom Stop Action. The Custom Stop Action Attributes dialog box opens and lets you set delay times for servo motors and RBM modules.

152

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 153

Configure and Start the Kinetix 6000 Drive System

Chapter 6

14. Configure the delay times. a. Type the Brake Engage Delay Time. b. Type the Brake Release Delay Time. c. Set the Resistive Brake Contact Delay time (0 - 1000 ms range). TIP

For recommended motor brake response times, refer to the Kinetix Rotary Motion Specifications Technical Data, publication KNX-TD001. The recommended delay time for 2090-XB33-xx and 2090-XB120-xx RBM modules is 71 ms.

d. Click Close to close the Custom Stop Action Attributes dialog box. 15. Click Apply. 16. Repeat step 1 through step 15 for each Bulletin 2094 AM module. Follow these steps to configure Auxiliary Axis properties. IMPORTANT

Auxiliary feedback is not supported by the Kinetix 6000M IDM units.

1. Right-click an auxiliary axis in the Controller Organizer and choose Properties. The Axis Properties dialog box opens on the General tab. If an axis is associated to the auxiliary axis node, set the Axis Configuration on the General tab of the Axis Properties dialog box to Feedback Only.

2. Click the Drive/Motor tab.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

153

Page 154

Chapter 6

Configure and Start the Kinetix 6000 Drive System

The Drive/Motor tab displays the amplifier being used and the Loop Configuration is Aux Feedback Only. This is the only choice if the amplifier is using the primary node for Servo (motor) configuration.

3. Click the Aux Feedback tab.

IMPORTANT

The Aux Feedback tab must be configured for the auxiliary feedback type being used. In this example, an SRM feedback device is being used.

4. From the Feedback Type pull-down menu, choose the feedback type appropriate for your auxiliary feedback motor. 5. Click OK. 6. Verify your Logix5000 program and save the file.

Download the Program After completing the Logix5000 configuration you must download your program to the Logix5000 processor.

154

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017