Page 155

Configure and Start the Kinetix 6000 Drive System

Apply Power to the Kinetix 6000 Drive

Chapter 6

This procedure assumes that you have wired and configured your Kinetix 6000 system (with or without the LIM module) and your Sercos interface module. ATTENTION: Capacitors on the DC bus can retain hazardous voltages after input power has been removed. Before working on the drive, measure the DC bus voltage to verify it has reached a safe level or wait the full time interval as indicated in the warning on the front of the drive. Failure to observe this precaution could result in severe bodily injury or loss of life. Refer to the Line Interface Module Installation Instructions, publication 2094IN005, when troubleshooting the LIM module status indicators, and for the location of LIM module circuit breakers, connectors, and status indicators. Refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003, for connector locations and when troubleshooting the IPIM module and IDM unit status indicators. Follow these steps to apply power to the Kinetix 6000 drive system. 1. Disconnect the load to the motor. ATTENTION: To avoid personal injury or damage to equipment, disconnect the load to the motor. Make sure each motor is free of all linkages when initially applying power to the system. 2. Determine your source of control power. If Your Control Power

Then

Is sourced from a LIM module

1. Verify that CB1, CB2, and CB3 are in the OFF position. 2. Apply three-phase input power to the LIM module VAC Line connector. 3. Set CB3 to the ON position. 4. Set CB2 to the ON position. 5. Go to main step 3.

Is not sourced from a LIM module

1. Apply (95…264V AC) control power to the IAM module (CPD connector). 2. Go to main step 3.

3. Observe the IAM/AM module logic power status indicator. Seven-segment Fault Status Indicator Logic Power Status Indicator

If the Logic Power Indicator is (1)

Then

ON

Go to step 4.

Not ON

1. Check your control power connections. 2. Go back to main step 2.

(1) If your 2094 drive system includes a Kinetix 6000M IDM system, observe the drive status indicator and verify that it is on.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

155

Page 156

Chapter 6

Configure and Start the Kinetix 6000 Drive System

4. Determine your source of three-phase input power. If Your Three-phase Power

Then

Is sourced from a LIM module

1. Set CB1 to the ON position. 2. Verify the Hardware Enable Input signal (IOD-2) for each axis is at 0 volts. Remove the connection between IOD-1 and IOD-2 if one exists. (1) 3. Go to main step 5.

Is not sourced from a LIM module

1. Apply 195…265V AC (230V) or 324…528V AC (460V) input power to the IAM module (IPD connector). 2. Verify the Hardware Enable Input signal (IOD-2) for each axis is at 0 volts. Remove the connection between IOD-1 and IOD-2 if one exists. (1) 3. Go to main step 5.

(1) The hardware enable input for IDM units is on the IPIM module.

5. Observe the IAM/AM module fault status indicator. The status indicator first flashes the Sercos node address, then cycles through ring phases until final configuration (phase 4) is reached. IAM/AM Fault Status Indicator

Status

Do This

Actively cycling (phase 0)

The drive is looking for a closed Sercos ring. Wait for phase 1 or take corrective action until you reach phase 1.

Check fiber-optic connections.

Displaying a fixed 1 (phase 1)

The drive is looking for active nodes. Wait for phase 2 or take corrective action until you reach phase 2.

Check node addressing.

Displaying a fixed 2 (phase 2)

The drive is configuring nodes for communication. Wait for phase 3 or take corrective action until you reach phase 3.

Check program motor and drive configuration against installed hardware.

Displaying a fixed 3 (phase 3)

The drive is configuring device specific parameters. Wait for phase 4 or take corrective action until you reach phase 4.

Check motor catalog number against selection. (1)

Displaying a fixed 4 (phase 4)

The drive is configured and active.

Go to step 6.

Flashing an E followed by two numbers

Drive is faulted.

Go to Kinetix 6000 Drive System Error Codes on page 167.

(1) You can get diagnostic information from the module by highlighting the module name in the Logix Designer application. A Pseudo Key Failure often indicates that the motor selection does not match the motor installed.

6. Observe the status indicators on the front of the IAM/AM module. Refer to troubleshooting tables for the Drive, Comm, and Bus status indicators in IAM/AM Module Status Indicators on page 172. Refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003, for IPIM module and IDM unit status indicator troubleshooting tables. 7. Observe the three Sercos indicators on the Logix5000 Sercos module.

156

Three Sercos Indicators

Status

Do This

Flashing green and red

Establishing communication

Wait for steady green on all three indicators.

Steady green

Communication ready

Go to Test and Tune the Axes on page 157.

Not flashing green and red/ not steady green

Sercos module is faulted

Go to the appropriate Logix5000 manual for specific instructions and troubleshooting.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 157

Configure and Start the Kinetix 6000 Drive System

Test and Tune the Axes

Chapter 6

These procedures assume that you have configured your Kinetix 6000 drive, your Logix5000 Sercos interface module, and applied power to the system. For help with using the Logix Designer application, as it applies to testing and tuning your axes with ControlLogix, CompactLogix, or SoftLogix Sercos modules, refer to Additional Resources on page 12.

Test the Axes Follow these steps to test the axes. 1. Verify the load was removed from each axis. 2. Right-click an axis in your Motion Group folder and choose Properties. The Axis Properties dialog box opens.

3. Click the Hookup tab. 4. Type 2.0 as the number of revolutions for the test or another number more appropriate for your application. This Test

Performs this Test

Test Marker (1)

Verifies marker detection capability as you rotate the motor shaft.

Test Feedback (1)

Verifies feedback connections are wired correctly as you rotate the motor shaft. Also, lets you define polarity.

Test Command & Feedback

Verifies motor power and feedback connections are wired correctly as you command the motor to rotate. Also, lets you define polarity.

(1) If testing motor with brake, energize the brake circuit to release the brake prior to test.

5. Apply Hardware Enable Input signal (IOD-2) for the axis you are testing. ATTENTION: To avoid personal injury or damage to equipment, apply 24V ENABLE signal (IOD-2) only to the axis you are testing.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

157

Page 158

Chapter 6

Configure and Start the Kinetix 6000 Drive System

IMPORTANT

Hardware Enable input for IDM units is on the IPIM module.

6. Click the desired test (Marker/Feedback/Command & Feedback) to verify connections. The Online Command dialog box opens. Follow the on-screen test instructions. When the test completes, the Command Status changes from Executing to Command Complete.

7. Click OK. The Online Command - Apply Test dialog box opens (Feedback and Command & Feedback tests only). When the test completes, the Command Status changes from Executing to Command Complete.

8. Click OK. 9. Determine if your test completed successfully. If

Then

Your test completes successfully, this dialog box opens.

1. Click OK. 2. Remove Hardware Enable Input (1) signal (IOD-2). 3. Go to Tune the Axes on page 159.

Your test failed, this dialog box opens.

1. Click OK. 2. Verify the Bus status indicator turned solid green during the test. 3. Verify that the Hardware Enable Input (1) signal (IOD-2) is applied to the axis you are testing. 4. Verify conversion constant entered in the Conversion tab. 5. Return to main step 6 and run the test again.

(1) The hardware enable input for IDM units is on the IPIM module.

158

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 159

Configure and Start the Kinetix 6000 Drive System

Chapter 6

Tune the Axes The load observer feature (available with drive firmware revision 1.124 or later) can provide good performance without having to tune your axis. Using load observer with auto-tuned gains can maximize system performance. Refer to Appendix D beginning on page 237 for more load observer information. Follow these steps to tune the axes. 1. Verify the load is still removed from the axis being tuned. ATTENTION: To reduce the possibility of unpredictable motor response, tune your motor with the load removed first, then reattach the load and perform the tuning procedure again to provide an accurate operational response. 2. Click the Tune tab.

3. Type values for Travel Limit and Speed. In this example, Travel Limit = 5 and Speed = 10. The actual value of programmed units depend on your application. 4. From the Direction pull-down menu, choose a setting. Forward Uni-directional is default. 5. Check Tune boxes as appropriate for your application. 6. Apply Hardware Enable Input signal (IOD-2) for the axis you are tuning. ATTENTION: To avoid personal injury or damage to equipment, apply 24V ENABLE signal (IOD-2) only to the axis you are tuning.

IMPORTANT

Hardware Enable input for IDM units is on the IPIM module.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

159

Page 160

Chapter 6

Configure and Start the Kinetix 6000 Drive System

7. Click Start Tuning to auto-tune your axis. The Online Command - Tune Servo dialog box opens. When the test completes, the Command Status changes from Executing to Command Complete.

8. Click OK. The Tune Bandwidth dialog box opens.

Actual bandwidth values (Hz) depend on your application and can require adjustment once motor and load are connected. 9. Record your bandwidth data for future reference. 10. Click OK. The Online Command - Apply Tune dialog box opens. When the test completes, the Command Status changes from Executing to Command Complete.

11. Click OK.

160

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 161

Configure and Start the Kinetix 6000 Drive System

Chapter 6

12. Determine if your test completed successfully. If

Then

Your test completes successfully, this dialog box opens.

1. Click OK. 2. Remove the Hardware Enable Input (1) signal (IOD-2) applied earlier. 3. Go to step 13.

Your test failed, this dialog box opens.

1. Click OK. 2. Make an adjustment to motor velocity. 3. Refer to the appropriate Logix5000 motion module user manual for more information. 4. Return to step 7 and run the test again.

(1) The hardware enable input for IDM units is on the IPIM module.

13. Repeat Test and Tune the Axes for each axis.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

161

Page 162

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Configure Drive Parameters and System Variables

This section provides information for accessing and changing parameters not accessible through the Logix Designer application. IMPORTANT

Drive parameters for the Kinetix 6000M IDM system are not accessible through the HIM module or DriveExplorer software.

Tools for Changing Parameters Most parameters are accessible through the Logix Designer application. Alternatives include the DPI compatible Human Interface Module (HIM) and DriveExplorer software. Table 98 - Software For Changing Parameters Method Software (1) HIM module (3)

Description

Cat. No.

Firmware Revision

DriveExplorer software (2)

9306-4EXP02ENE

2.01 or later

Serial to SCANport™ adapter

1203-SSS (Series B)

3.004 or later

Full numeric LCD HIM

20-HIM-A3

N/A

(1) Refer to Set the Additional Bus Capacitance Parameter on page 231, for more information on changing parameter values by using DriveExplorer software and 1203-SSS adapter. (2) Refer to DriveExplorer Getting Results Manual, publication 9306-GR001, for instructions. (3) Compatible catalog numbers include all 20-HIM-Ax.

Change Parameters with DriveExplorer Software To navigate with DriveExplorer software, refer to the example dialog box below. In this example, the IAM I/O group folder is open, the Analog Outputs parameter group is selected, and the parameter elements are displayed in the box to the right. IMPORTANT

Parameters are read-only when the Sercos ring is active. You must break the Sercos ring to change parameters. To save changes, perform a nonvolatile save (NVS) prior to cycling power.

Figure 84 - DriveExplorer Software Example

162

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 163

Configure and Start the Kinetix 6000 Drive System

Chapter 6

Change Parameters with the HIM Module When using the HIM module to monitor or change parameters, use the up and down arrows (∧ and ∨) to arrive at selections. Refer to the instructions that came with your HIM module for more information. Follow these steps to monitor or change parameters with the HIM module. 1. Select parameter, and press ↵. 2. Select I/O AM1 Group (for IAM module), and press ↵. 3. Select Analog Outputs, and press ↵. a. Analog Output 1 is displayed, and press ↵. b. For Analog Output 2 use arrows to select, and press ↵. 4. Press Sel. 5. Enter parameter number, and press ↵.

Monitor System Variables with Analog Test Points There are two analog output test points accessible from the IOD 26-pin connector on the IAM and AM module. Table 99 - IAM/AM I/O 26-pin (IOD) Connector IOD Pin

Description

Signal

23

Analog output 0

DAC0

24

Analog output common

DAC_COM

25

Analog output 1

DAC1

26

Analog output common

DAC_COM

Figure 85 - Pin Orientation for 26-pin I/O (IOD) Connector

Pin 26

Pin 19 Pin 10

Pin 18 Pin 9

Pin 1

Refer to Analog Outputs on page 69 for signal specifications.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

163

Page 164

Chapter 6

Configure and Start the Kinetix 6000 Drive System

Parameters begin with a variable to identify a specific axis by slot number, as follows: • IAM module = 0 for parameters 0…999 • 1st AM module = 1 for parameters 1000…1999 • 2nd AM module = 2 for parameters 2000…2999 and so on • 7th AM module = 7 for parameter 7000…7999 Table 100 - Monitor System Variables Controlling Parameter

Analog Output

Parameter Number (1)

Default Value

1 x681

2 x683

Scale Parameter (1)

Parameter Number (1)

Default Value xx40 x682

0.0060 xx84 x684

0.1000

(1) x = slot number

The value entered in Scale Parameter scales the analog output so that you can get a full scale reading of the specific parameter for the dynamic range or values you are testing. For linear scaling specifications, refer to the table on page 69. Table 101 - Monitor Dynamic System Variables Attribute

Parameter Number (1)

Velocity feedback xx40

Velocity commanded xx36

Torque feedback xx84

Torque commanded xx80

(1) x = slot number.

164

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017