Troubleshooting the Kinetix 6000 Drive System
This chapter provides troubleshooting tables for your Kinetix® 6000 drive system components.
Safety Precautions
Topic
Page
Safety Precautions
165
Interpret Status Indicators
166
General System Anomalies
175
Logix5000/Drive Fault Behavior
177
Observe these safety precautions when troubleshooting your Kinetix 6000 drive. ATTENTION: Capacitors on the DC bus can retain hazardous voltages after input power has been removed. Before working on the drive, measure the DC bus voltage to verify it has reached a safe level or wait the full time interval as indicated in the warning on the front of the drive. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: Do not attempt to defeat or override the drive fault circuits. You must determine the cause of a fault and correct it before you attempt to operate the system. Failure to correct the fault could result in personal injury and/or damage to equipment as a result of uncontrolled machine operation. ATTENTION: Provide an earth ground for test equipment (oscilloscope) used in troubleshooting. Failure to ground the test equipment could result in personal injury.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
165
Page 166
Chapter 7
Troubleshooting the Kinetix 6000 Drive System
Interpret Status Indicators
Refer to these troubleshooting tables to identify faults, potential causes, and the appropriate actions to resolve the fault. If the fault persists after attempting to troubleshoot the system, please contact your Rockwell Automation sales representative for further assistance.
Kinetix 6000M IDM System Error Codes The IAM module reports a single, generic IPIM Fault whenever a fault occurs on any IPIM in the same backplane as the IAM module. All IPIM faults result in an open contactor. The Logix5000™ Axis Tag for this fault is IPIMFault. The IPIM module is not a Sercos device, so the IAM module reports any IPIM faults to the Logix5000 motion subsystem. IPIM faults are reset by performing a fault reset on the IAM module. Issuing a fault reset command to the IAM module also generates a fault reset to all the IPIM modules in the same backplane as the IAM. Detailed information about the IPIM fault status can be obtained by messaging to the IAM module. Connecting the IPIM module into the Logix5000 environment as an EtherNet/IP device does not disable fault reporting through the IAM module. Only the IAM fault reporting lets the Logix5000 motion sub-system take action based on the IPIM module fault status. IPIM faults are also reported over the Ethernet connection. However, IPIM faults must be reset by applying a fault reset instruction to the IAM module. The integration of the IPIM module into the Logix5000 environment through the EtherNet/IP network provides additional capabilities you can choose to take advantage of in your program. Refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003, for more information on troubleshooting the IDM drive-motor system.
166
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 167
Troubleshooting the Kinetix 6000 Drive System
Chapter 7
Kinetix 6000 Drive System Error Codes The following list of problematic symptoms (no error code shown) and faults with assigned error codes is designed to help you resolve anomalies. When a fault is detected, the seven-segment status indicator displays an E followed by the flashing of the two-digit error code, one digit at a time. This is repeated until the error code is cleared. Table 102 - Seven-segment Status Indicator Error Codes Error Code
Fault Message - Logix Designer (HIM)
Anomaly or Symptom
Potential Cause
Possible Resolution
No AC power or auxiliary logic power.
Verify AC control power is applied to the Kinetix 6000 system.
Internal power supply malfunction.
Call your Rockwell Automation sales representative to return module for repair.
Motor wiring error.
• Check motor wiring. • Run Hookup test in the Logix Designer application.
Incorrect motor chosen.
Verify the proper motor is selected.
Digital I/O not working correctly
I/O power supply disconnected.
Verify connections and I/O power source.
A blown fuse was detected on the inverter PCB
Blown fuse.
Call your Rockwell Automation sales representative to return module for repair.
• High motor ambient temperature and/or • Excessive current
• Operate within (not above) the continuous torque rating for the ambient temperature 40 °C (104 °F) maximum. • Lower ambient temperature, increase motor cooling.
Motor wiring error.
Check motor wiring at MF connector on the IAM/ AM module.
Incorrect motor selection.
Verify the proper motor has been selected.
Motor cables shorted.
Verify continuity of motor power cable and connector.
Motor winding shorted internally.
Disconnect motor power cables from the motor. If the motor is difficult to turn by hand, consider replacing the motor.
Kinetix 6000 drive temperature too high.
• Check for clogged vents or defective fan. • Make sure cooling is not restricted by insufficient space around the unit.
Operation above continuous power rating and/ or product environmental ratings.
• • • •
Kinetix 6000 drive has a short circuit, overcurrent, or failed component.
Remove all power and motor connections, and preform a continuity check from the DC bus to the U, V, and W motor outputs. If a continuity exists, check for wire fibers between terminals, or send drive in for repair.
Dedicated overtravel input is inactive.
• Check wiring. • Verify motion profile. • Verify axis configuration in software.
Power (PWR) indicator not ON
No Error Code Displayed
E00
E04
E05
BusUndervoltage Fault (Blown fuse)
MotorOvertemp Fault (Motor Overtemp)
DriveOvercurrent Fault (Power Fault)
Motor jumps when first enabled
Motor thermal switch tripped
Self-protection of the Intelligent Power Module (IPM) is indicating a major power related fault condition.
E06
HardOvertravel Fault (+/- Hard Overtravel)
Axis moved beyond the physical travel limits in the positive/negative direction.
E07
MotFeedbackFault (Motor Feedback Loss)
The feedback wiring is open, shorted, or missing.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Verify ambient temperature is not too high. Operate within the continuous power rating. Reduce acceleration rates. Reduce deceleration rates.
• Check motor encoder wiring. • Run Hookup test in the Logix Designer application.
167
Page 168
Chapter 7
Troubleshooting the Kinetix 6000 Drive System
Table 102 - Seven-segment Status Indicator Error Codes (continued) Error Code
E09
Fault Message - Logix Designer (HIM)
BusUndervoltage Fault (Bus Undervoltage)
Anomaly or Symptom With three-phase power present, the DC bus voltage is below limits. DC bus voltage fell below the undervoltage limit while an axis on the follower power rail was enabled.
Potential Cause
• DC bus voltage for 460V system is below 275V • DC bus voltage for 230V system is below 137V
Possible Resolution • Verify voltage level of the incoming AC power. • Check AC power source for glitches or line drop. • Install an uninterruptible power supply (UPS) on your AC input. Disable follower axis before removing power.
Excessive regeneration of power.
E10
DriveOvervoltage Fault (Bus Overvoltage)
The DC bus voltage is above limits.
When the motor is driven by an external mechanical power source, it can regenerate too much peak energy through the drive power supply. The system faults to save itself from an overload.
• Change the deceleration or motion profile. • Use a larger system (motor and Kinetix 6000 drive). • Install shunt module.
• DC bus voltage for 460V system is over 820V • DC bus voltage for 230V system is over 410V
Verify input is within specifications.
Improper connections.
• Verify the Hall wiring at the MF connector on the IAM/AM module. • Verify 5V power supply to the encoder.
E11
MotFeedbackFault (Illegal Hall State)
State of Hall feedback inputs is incorrect.
E16
Softovertravel Fault (+/- Software Overtravel)
Axis position exceeded maximum software setting.
• Verify motion profile. • Verify overtravel settings are appropriate.
E18
OverSpeedFault (Overspeed Fault)
Motor speed has exceeded 150% of maximum rated speed. The 100% trip point is dictated by the lesser of the user velocity limits or the motor rated base speed.
• Check cables for noise. • Check tuning.
Position error limit was exceeded.
• • • • •
Increase the feed forward gain. Increase following error limit or time. Check position loop tuning. Verify sizing of system. Verify mechanical integrity of system within specification limits.
E19
PositionErrorFault (Follow Error)
E20
MotFeedbackFault (Mtr Fdbk AQB)
Motor Encoder State Error
E21
AuxFeedbackFault (Aux Feedback Comm)
Communication was not established with an intelligent encoder.
Verify auxiliary encoder wiring.
E30
MotFeedbackFault (Motor Feedback Comm)
Communication was not established with an intelligent encoder.
• Verify motor selection. • Verify the motor supports automatic identification. • Verify motor encoder wiring.
E31
DriveHardFault
Excessive motor shaft movement during power up, Sercos ring phase-up, or after a fault reset.
Make sure there is no motor shaft movement during power up, Sercos ring phase-up, or during a fault reset.
E34
168
GroundShortFault (Ground Fault)
Excessive ground current in the converter was detected.
The motor encoder encountered an illegal transition.
• Use shielded cables with twisted pair wires. • Route the feedback away from potential noise sources. • Check the system grounds. • Replace the motor/encoder.
Wiring error.
• Check motor power wiring. • Check input power wiring.
Motor internal ground short.
Replace motor.
Internal malfunction.
Disconnect motor power cable from drive and enable drive with current limit set to 0. If fault clears, then a wiring error or motor internal anomaly exists. If fault remains, call your sales representative.
Grounded control power terminal (applies to 230V systems only)
• Remove ground from control power input. • Source control power from three-phase input power (refer to diagram on page 192).
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 169
Troubleshooting the Kinetix 6000 Drive System
Chapter 7
Table 102 - Seven-segment Status Indicator Error Codes (continued) Error Code
Fault Message - Logix Designer (HIM)
Anomaly or Symptom
Potential Cause
Possible Resolution
E35
DriveUndervoltage Fault (Precharge Fault)
Converter precharge cycle failed.
Low AC input voltage.
Check input AC voltage on all phases.
Internal malfunction.
Call your sales representative.
Excessive heat exists in the power circuitry.
• Reduce acceleration rates. • Reduce duty cycle (ON/OFF) of commanded motion. • Increase time permitted for motion. • Use larger IAM converter module. • Check for clogged vents or defective fan. • Make sure cooling is not restricted by insufficient space around the unit.
E36
DriveOvertemp Fault (System Overtemperature)
Converter thermal switch tripped.
E37
PowerPhaseLoss Fault (Phase Loss Flt)
• One or more phases of the input AC power is missing. • Axis was enabled when main (three-phase) power was removed. • common-bus follower axis was enabled when DC bus power was removed.
• Check input AC voltage on all phases. • Disable axis before removing power.
E38
SercosFault (Sercos Ring Flt)
The Sercos ring is not active after being active and operational.
Cable disconnected.
Check that fiber-optic cable is present and connected properly.
Self-sensing Commutation Start-up Error
Motion required for self-sensing start-up commutation was obstructed.
• Verify that there are no impediments to motion at startup, such as hard limits. • Increase self-sensing current if high friction or load conditions exist. • Check motor or encoder wiring by using wiring diagnostics.
E39
DriveHardFault (Self Sense Flt)
E43
DriveEnableInput Fault (Drive Enable Flt)
Missing Drive Enable Input Signal
• An attempt was made to enable the axis • Disable the Drive Enable Input fault. through software while the Drive Enable • Verify that Drive Enable hardware input is hardware input was inactive. active whenever the drive is enabled through • The Drive Enable input transitioned from software. active to inactive while the axis was enabled.
E49
DriveHardFault (Safe-off HW Flt)
Safe torque-off function mismatch. Drive does not allow motion.
• Loose wiring at STO connector. • Cable/header not seated properly in STO connector. • Safe torque-off circuit missing +24V DC.
E50
SercosFault (Sercos Same ADDR)
Duplicate node address detected on Sercos ring.
Verify that each Sercos drive is assigned a unique node address.
E54
DriveHardFault (Ifbk HW Fault)
Current feedback hardware fault detected.
Replace the module.
E55
OverSpeedFault
The velocity error limit has been exceeded.
Check the cables for noise.
E60
DriveHardFault (Unknown Axis)
Illegal ID bits detected
Replace the module.
E61
AuxFeedbackFault (Aux Fdbk AQB)
Auxiliary Encoder State Error
• Use shielded cables with twisted pair wires. • Route the feedback away from potential noise sources. • Check the system grounds. • Replace the motor/encoder.
E62
AuxFeedbackFault (Aux Fdbk Loss)
The feedback wiring is open, shorted, or missing.
Check the motor feedback cable connectors/wiring to the IAM/AM module and servo motor.
E63
AuxFeedbackNoise (Aux Fdbk Noise)
Noise on auxiliary feedback cable.
E64
MotorFeedbackNoise (Mtr Fdbk Noise)
Noise on motor feedback cable.
• Verify grounding. • Route feedback cable away from noise sources. • Refer to System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.
Motor has exceeded velocity error limit
The auxiliary encoder encountered an illegal transition.
Recommended grounding, per installation instructions, has not been followed.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
• Verify wire terminations, cable/header connections, and +24V. • Reset error and run proof test. • If error persists, return the drive to Rockwell Automation.
169
Page 170
Chapter 7
Troubleshooting the Kinetix 6000 Drive System
Table 102 - Seven-segment Status Indicator Error Codes (continued) Error Code
Fault Message - Logix Designer (HIM)
Anomaly or Symptom
Potential Cause
Possible Resolution
E65
No Fault Message (condition indicated by on-screen message) (Hookup Fault)
Hookup procedure failed
Motor or feedback device malfunction.
• Check motor power/feedback wiring. • Refer to on-screen message for resolution.
E66
No Fault Message (condition indicated by on-screen message) (Atune Flt)
Autotune procedure failed
Motor or feedback device malfunction.
• Check motor power/feedback wiring. • Refer to on-screen message for resolution. • Perform Hookup in the Logix Designer application. • Consult application help screen.
E67
DriveHardFault (Task init)
Operating system failed
Software initialization fault detected due to hardware failure.
• Cycle power. • If fault persists, replace module.
E68
DriveHardFault (SCANport™ Comm)
DPI communication failed
The DPI device or cable is faulty.
Check DPI connections.
E69
DriveHardFault (Objects Init)
Nonvolatile memory is corrupt due to control board hardware failure.
Load default parameters, save to nonvolatile memory, and recycle power or reset the drive.
E70
DriveHardFault (NV Mem Init)
Nonvolatile memory is corrupt due to control board software error.
Load default parameters, save to nonvolatile memory, and recycle power or reset the drive.
E71
DriveHardFault (Memory Init)
RAM or nonvolatile memory validation failure
• Cycle power. • If fault persists, replace module.
E72
E73
E74
DriveOvertemp Fault (Drive Overtemp)
Communicate (Backplane Comm)
DriveOvercurrent Fault (Bus OverCurrent)
Inverter thermal switch tripped
The IAM or an AM module fan failed.
Replace the failed module.
The cabinet ambient temperature is above rating.
Check the cabinet temperature.
The machine duty cycle requires an RMS current exceeding the continuous rating of the controller.
Change the command profile to reduce speed or increase time.
The airflow access to the Kinetix 6000 system is limited or blocked.
Check airflow and re-route cables away from the Kinetix 6000 system.
Power rail CAN communication failed.
Check module for proper mount.
Power rail connection shorted or open.
Check power rail and module for foreign objects.
Motor or transmission malfunction.
• Check for proper motor sizing. • Check/replace transmission device. • Check/replace motor.
IAM module not sized properly.
• Check for proper IAM module sizing. • Install larger kW rated IAM module.
DC link current exceeds rating.
E75
DriveOvervoltage Fault (Shunt Time Out)
The IAM/AM module, or shunt module has exceeded its shunt resistor continuous rating.
• Use a properly sized shunt or modify duty cycle of the application. • System uses internal shunt and requires external shunt for additional capacity.
E76
DriveHardFault (CAN Init)
DPI hardware initialization fault detected.
• Reset System. • If fault persists, replace system module.
E77
DriveHardFault (Module Mismatch)
Either 230V AM module is installed on power rail with 460V IAM module, or 460V AM module is installed on power rail with 230V IAM module.
Replace mismatched module.
E78
DriveHardFault (Sercos Init)
Control hardware fault detected.
• Cycle power. • If fault persists, replace module.
170
Control board hardware failure.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 171
Troubleshooting the Kinetix 6000 Drive System
Chapter 7
Table 102 - Seven-segment Status Indicator Error Codes (continued) Error Code
E79
Fault Message - Logix Designer (HIM)
DriveOvervoltage Fault (Shunt Module Flt)
Anomaly or Symptom
Potential Cause
Possible Resolution
Over-temperature fault indicator on Bulletin 2094 shunt module is steady red.
Refer to Temperature Fault Status Indicator on page 174.
Shunt-fault indicator on Bulletin 2094 shunt module is steady red.
Refer to Shunt Fault Status Indicator on page 174.
Bulletin 2094 shunt module is missing from power rail.
• Install missing module on power rail. • Fill empty slot with slot-filler module.
E80
DriveHardFault (CPLD Flt)
Control hardware fault detected.
Replace module.
E81
DriveHardFault (Common Bus Flt)
Follower IAM module detected AC input power being applied.
Remove AC input power connections from follower IAM module.
E90
DriveHardFault (Precharge Timeout Flt)
Precharge resistor power exceeds the resistor rating.
Wait for resistor to cool.
E95
IPIMFault (IPIM Module Flt)
A fault has occurred in one or more IPIM modules on the power rail.
Refer to the troubleshooting chapter in the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
171
Page 172
Chapter 7
Troubleshooting the Kinetix 6000 Drive System
IAM/AM Module Status Indicators Table 103 - Drive Status Indicator Drive Status Indicator
Drive Status
Possible Resolution
Off
Normal, no faults
N/A
Steady red
Drive faulted
Refer to seven-segment error code and Kinetix 6000 Drive System Error Codes troubleshooting on page 167.
Table 104 - Comm Status Indicator Comm Status Indicator
Off
Flashing green
Steady green
Drive Status
No communication (1)
Establishing communication
Communication ready
Potential Cause
Possible Resolution
Loose fiber-optic connection.
Verify proper fiber-optic cable connections.
Broken fiber-optic cable.
Replace fiber-optic cable.
Receive fiber-optic cable connected to Sercos transmit connector and vice versa.
Check proper Sercos fiber-optic cable connections.
System is still in the process of establishing Sercos communication.
Wait for steady green indicator.
Node address setting on the drive module does not match Sercos controller configuration.
Verify proper node switch setting.
No faults or failures.
N/A
(1) Refer to Fiber-optic Cable Installation and Handling Instructions, publication 2090-IN010, for more information.
Table 105 - Bus Status Indicator Bus Status Indicator
Bus Status
Condition
No power or DC bus is not present.
• Normal when bus power is not applied. • Fault exists, refer to seven-segment error code and Kinetix 6000 Drive System Error Codes troubleshooting on page 167.
Bus power is present in follower IAM.
• Follower IAM module is not configured as CommonBus Follow in the Logix Designer application. • After DC bus voltage is applied, a 2.5 second delay before the indicator begins flashing green is normal operation to provide the common-bus leader module time to complete precharge.
Flashing green
Bus power is present, axis disabled. No faults.
Normal when: • 24V is not applied to Hardware Enable Input (IOD-2). • MSO instruction is not commanded in the Logix Designer application.
Steady green
Bus power is present, axis enabled. No faults.
Normal when: • 24V is applied to Hardware Enable Input (IOD-2). • MSO instruction is commanded in the Logix Designer application.