For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 173

Troubleshooting the Kinetix 6000 Drive System

Chapter 7

Shunt Module Status Indicators Each of the shunt module status indicators provide specific troubleshooting information. Table 106 - General Shunt Module Troubleshooting Module

Shunt

IAM/AM

Status

Under These Conditions

Fault is latched.

Until fault condition is corrected and cleared.

Fault is cleared.

• Using MASR, MAFR, MGSR instructions or the HIM (red stop button). • Only after the DC bus is discharged (bus status indicator is flashing). • Drive must be configured with 2094-BSP2 shunt module or Bulletin 1394 external shunt module.

Disabled (for DC bus regulation).

• When the 2094-BSP2 shunt module is used on a 230V system. • When either 230V or 460V system is configured with a Bulletin 1394 external shunt module. • When configured in Common-bus Follower mode.

Enabled to discharge the DC bus.

Drive (IAM or leader IAM module) three-phase power is removed.

Disabled from discharging the DC bus.

When configured in Common-bus Follower mode.

IMPORTANT

Under some fault conditions, two reset commands can be required to clear drive and shunt module faults.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

173

Page 174

Chapter 7

Troubleshooting the Kinetix 6000 Drive System

Table 107 - Bus Status Indicator Bus Status Indicator

Status

Potential Cause

Possible Resolution

Flashing

Normal condition when control power is applied and bus voltage is less than 60V DC.

N/A

Steady Green

Normal condition when control power is applied and bus voltage is greater than 60V DC.

N/A

Off

Control power is not present.

Replace shunt module.

Internal power supply failure.

Table 108 - Temperature Fault Status Indicator Over-Temp Fault Indicator

Status

Off

Normal condition.

Potential Cause

Possible Resolution N/A

Shunt module internal temperature exceeds operating temperature specification.

Shunt module fan failed.

Replace shunt module.

Shunt module temperature exceeds rating.

• Wait for shunt module to cool. • Reset faults. • Verify IAM module bus regulator configuration.

External temperature switch is open.

• Wait for shunt module to cool. • Reset faults. • Verify IAM module bus regulator configuration.

TS jumper is not present.

Install jumper.

Steady Red External over temperature condition.

Table 109 - Shunt Fault Status Indicator Shunt Fault Indicator

Status

Potential Cause

Off

Normal condition

Steady Red

Shorted internal or external shunt resistor.

Possible Resolution N/A

Mis-wired shunt jumper or other short on RC connector. Mis-wired (shorted) external shunt wiring.

• Correct mis-wire (shorted) condition. • If anomaly persists, replace shunt module.

Table 110 - All Shunt Module Status Indicators Shunt Module Status Indicator

Status

Potential Cause

Possible Resolution

• Bus Status • Over-Temp Fault • Shunt Fault

All three status indicators flash simultaneously.

Shunt module hardware failure.

• Cycle power. • If anomaly persists, replace shunt module.

174

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 175

Troubleshooting the Kinetix 6000 Drive System

Chapter 7

These anomalies do not always result in a fault code, but can require troubleshooting to improve performance.

General System Anomalies Table 111 - General System Anomalies Condition

Axis or system is unstable.

You cannot obtain the motor acceleration/deceleration that you want.

Motor does not respond to a velocity command.

Presence of noise on command or motor feedback signal wires.

Potential Cause

Possible Resolution

The position feedback device is incorrect or open.

Check wiring.

Unintentionally in Torque mode.

Check to see what primary operation mode was programmed.

Motor tuning limits are set too high.

Run Tune in the Logix Designer application.

Position loop gain or position controller acceleration or deceleration rate is improperly set.

Run Tune in the Logix Designer application.

Improper grounding or shielding techniques are causing noise to be transmitted into the position feedback or velocity command lines, causing erratic axis movement.

Check wiring and ground.

Motor Select limit is incorrectly set (servo motor is not matched to axis module).

• Check setups. • Run Tune in the Logix Designer application.

Mechanical resonance.

Notch filter or output filter can be required (refer to Axis Properties dialog box, Output tab in the Logix Designer application).

Torque Limit limits are set too low.

Verify that current limits are set properly.

Incorrect motor selected in configuration.

Select the correct motor and run Tune in the Logix Designer application again.

The system inertia is excessive.

• Check motor size versus application need. • Review servo system sizing.

The system friction torque is excessive.

Check motor size versus application need.

Available current is insufficient to supply the correct acceleration or deceleration rate.

• Check motor size versus application need. • Review servo system sizing.

Acceleration limit is incorrect.

Verify limit settings and correct them, as necessary.

Velocity Limit limits are incorrect.

Verify limit settings and correct them, as necessary.

The axis cannot be enabled for 1.5 seconds after disabling.

Disable the axis, wait for 1.5 seconds, and enable the axis.

Enable signal has not been applied or the enable wiring is incorrect.

• Check the controller. • Check the wiring.

The motor wiring is open.

Check the wiring.

The motor thermal switch has tripped.

• Check for a fault. • Check the wiring.

The motor has malfunctioned.

Repair or replace the motor.

The coupling between motor and machine has broken (for example, the motor moves, but the load/machine does not).

Check and correct the mechanics.

Primary operation mode is set incorrectly.

Check and properly set the limit.

Velocity or current limits are set incorrectly.

Check and properly set the limits.

Recommended grounding per installation instructions have not been followed.

• Verify grounding. • Route wire away from noise sources. • Refer to System Design for Control of Electrical Noise, publication GMC-RM001.

Line frequency present.

• Verify grounding. • Route wire away from noise sources.

Variable frequency can be velocity feedback ripple or a disturbance caused by gear teeth or ballscrew balls, for example. The frequency can be a multiple of the motor power transmission components or ballscrew speeds resulting in velocity disturbance.

• Decouple the motor for verification. • Check and improve mechanical performance, for example, the gearbox or ballscrew mechanism.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

175

Page 176

Chapter 7

Troubleshooting the Kinetix 6000 Drive System

Table 111 - General System Anomalies (continued) Condition

No rotation

Motor overheating

Abnormal noise

Erratic operation - Motor locks into position, runs without control or with reduced torque.

176

Potential Cause

Possible Resolution

The motor connections are loose or open.

Check motor wiring and connections.

Foreign matter is lodged in the motor.

Remove foreign matter.

The motor load is excessive.

Verify the servo system sizing.

The bearings are worn.

Return the motor for repair.

The motor brake is engaged (if supplied).

• Check brake wiring and function. • Return the motor for repair.

The motor is not connect to the load.

Check coupling.

The duty cycle is excessive.

Change the command profile to reduce acceleration or deceleration or increase time.

The rotor is partially demagnetized causing excessive motor current.

Return the motor for repair.

Motor tuning limits are set too high.

Run Tune in the Logix Designer application.

Loose parts are present in the motor.

• Remove the loose parts. • Return motor for repair. • Replace motor.

Through bolts or coupling is loose.

Tighten bolts.

The bearings are worn.

Return motor for repair.

Mechanical resonance.

Notch filter can be required (refer to Axis Properties dialog box, Output tab in the Logix Designer application).

Motor power phases U and V, U and W, or V and W reversed.

Check and correct motor power wiring.

Sine, Cosine or Rotor leads are reversed in the feedback cable connector.

Check and correct motor feedback wiring.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 177

Troubleshooting the Kinetix 6000 Drive System

Logix5000/Drive Fault Behavior

Chapter 7

These fault actions are configurable from the Axis Properties dialog box, Fault Actions tab in the Logix Designer application. Table 112 - Drive Fault Action Definitions Drive Fault Action

Definition

Shutdown

The drive disables the axis as defined in Logix5000/Drive Fault Behavior, Table 113. In addition, the axis in Logix Designer enters the Shutdown state, which disables any axes that are using this axis as a camming or gearing master. In addition, the AxisHomedStatus tag for the faulted axis is cleared. Shutdown is the most severe action to a fault and it is usually reserved for faults that could endanger the machine or operator if power is not removed as quickly as possible.

Disable Drive

The drive disables the axis as defined in Logix5000/Drive Fault Behavior, Table 113.

Stop Motion

The axis decelerates at the maximum deceleration rate (set in the Logix Designer application>Axis Properties>Dynamics tab). Once the axis has come to a stop, the servo loops remain enabled but no further motion can be generated until the fault is reset. This is the gentlest stopping mechanism in response to a fault. It is usually used for less severe faults.

Status Only

The drive continues to operate. Status is provided by the seven-segment fault status indicator, drive status indicator, and DPI (if used). The application program must handle any motion faults. In general, use this setting in applications where the standard fault actions are not appropriate.

Only selected faults are programmable. In the Logix5000/Drive Fault Behavior table on page 178, the controlling attribute is given for programmable fault actions. All faults that are not configurable have a fault action of Shutdown. Figure 86 - Axis Properties - Fault Actions Tab

Drive Fault Action/Attribute for Motor Overtemp fault (E04).

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

177

Page 178

Chapter 7

Troubleshooting the Kinetix 6000 Drive System

Table 113 - Logix5000/Drive Fault Behavior Logix5000 Fault Message (HIM Message)

Error Code

Description

Drive Fault Action/ Attribute

Logix Designer Programmable Fault Action?

BusUndervoltageFault (Blown fuse)

E00

A blown fuse was detected in the inverter pcb.

Coast/Disable (open contactor enable relay)

No

MotorOvertempFault (Motor Overtemp)

E04 (1)

The motor thermal switch was tripped. Firmware I2t protection does not generate a fault, rather it dynamically folds back current when 110% of motor rating is reached. Setting the Motor Thermal fault action to Status Only or Stop Motion bypasses the foldback behavior and allows the fault to occur.

N/A

Yes Motor Thermal

DriveOvercurrentFault (Power Fault)

E05

An instantaneous over-current was detected in the inverter power section.

Coast/Disable (open contactor enable relay)

No

HardOvertravelFault (+/- Hard Overtravel)

E06

Axis moved beyond the physical travel limits in the positive/negative direction. This fault can be configured for status only.

Decel/Disable

Yes Hard Overtravel

MotFeedbackFault (Motor Feedback Loss)

E07

The feedback wiring is open, shorted or missing.

Coast/Disable

No

Coast/Disable (open contactor enable relay)

No

With 3-phase present, the DC bus voltage is below limits. The trip point is 275V and 137V DC for 460V/230V drives respectively.

BusUndervoltageFault (Bus Under Voltage)

E09

DriveOvervoltageFault (Bus Overvoltage)

E10

The DC bus voltage is above limits. The trip point is 820V and 410V DC for 460V/ 230V drives respectively.

Coast/Disable (open contactor enable relay)

No

MotFeedbackFault (Illegal Hall State)

E11

State of Hall feedback inputs in incorrect.

Coast/Disable

No

SoftovertravelFault (+/- Software Overtravel)

E16

Axis position exceeded maximum software setting in the positive/negative direction. This fault can be configured for status only.

Decel/Disable

Yes Soft Overtravel

OverSpeedFault (Overspeed Fault)

E18

Axis speed has reached 150% of the maximum rated setting. The 100% trip point is dictated by the lesser of the user velocity limits or the motor rated base speed.

Coast/Disable

No

PositionErrorFault (Follow Error)

E19

Axis position error limit has been exceeded. This fault can be configured for status only.

Decel/Disable

Yes Position Error

MotFeedbackFault (Mtr Fdbk AQB)

E20

Motor encoder has encountered an illegal state transition.

Coast/Disable

No

AuxFeedbackFault (Aux Feedback Comm)

E21

Communication was not established with an intelligent (Stegmann) encoder on the Auxiliary feedback port.

Decel/Disable

No

MotFeedbackFault (Motor Feedback Comm)

E30

Communication was not established with an intelligent (Stegmann) encoder on the Motor feedback port.

Decel/Disable

No

DriveHardFault

E31

Excessive motor shaft movement during power up, Sercos ring phase-up, or after a fault reset.

Coast/Disable

No

GroundShortFault (Ground Fault)

E34

Excessive ground current in the converter was detected.

Coast/Disable (open contactor enable relay)

No

DriveUndervoltageFault (Precharge Fault)

E35

The converter precharge cycle has failed.

Coast/Disable (open contactor enable relay)

No

DriveOvertempFault (System Overtemperature)

E36 (2)

Converter internal temperature limit exceeded.

Coast/Disable (open contactor enable relay)

No

178

DC bus voltage is below limits when any axis on common-bus follower power rail was enabled.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 179

Troubleshooting the Kinetix 6000 Drive System

Chapter 7

Table 113 - Logix5000/Drive Fault Behavior (continued) Logix5000 Fault Message (HIM Message)

Error Code

Description

Drive Fault Action/ Attribute

One or two phases of the input AC power are missing.

Coast/Disable (open contactor enable relay)

• All phases of the input AC power are missing. • Axis was enabled when main (three-phase) power was removed. • Common-bus follower axis was enabled when DC bus power was removed.

Decel/Disable

Logix Designer Programmable Fault Action?

PowerPhaseLossFault (Phase Loss Flt)

E37

SercosFault (Sercos Ring Flt)

E38

The Sercos ring is not active after being active and operational.

Decel/Disable

No

DriveHardFault (Self Sense Flt)

E39

Self-sensing commutation fault detected.

Coast/Disable

No

DriveEnableInputFault (Drive Enable Flt)

E43

Generated when Enable input switches off when drive is enabled.

Decel/Disable

Yes Drive Enable Input

DriveHardFault (Safe-Off HW Flt)

E49

Safe torque-off function mismatch. Drive does not allow motion. Refer to the Kinetix Safe Torque-off Feature Safety Reference Manual, publication GMC-RM002, for more information. Applies to 2094-xCxx-Mxx-S IAM and 2094-xMxx-S AM modules with safe torque-off feature.

Coast/Disable (open contactor enable relay)

No

SercosFault (Sercos Same ADDR)

E50

Duplicate node address detected on Sercos ring.

Decel/Disable

No

DriveHardFault (Ifbk HW Fault)

E54

Current feedback hardware fault detected.

Coast/Disable (open contactor enable relay)

No

OverSpeedFault

E55

The velocity error limit has been exceeded.

Coast/Disable

No

DriveHardFault (Unknown Axis)

E60

Invalid module type identified by firmware when applying power.

Coast/Disable (open contactor enable relay)

No

AuxFeedbackFault (Aux Fdbk AQB)

E61

Auxiliary encoder has encountered an illegal state transition.

Coast/Disable

No

AuxFeedbackFault (Aux Fdbk Loss)

E62

The feedback wiring is open, shorted or missing.

Coast/Disable

No

AuxFeedbackNoise (Aux Fdbk Noise)

E63

Presence of noise on auxiliary feedback cable.

MotorFeedbackNoise (Mtr Fdbk Noise)

Coast/Disable

Yes Feedback Noise

E64

Presence of noise on motor feedback cable.

No Fault Message (condition indicated by on-screen message) (Hookup Fault)

E65

Hookup procedure failed.

Coast/Disable

No

No Fault Message (condition indicated by on-screen message) (Atune Flt)

E66

Autotune procedure failed.

Coast/Disable

No

DriveHardFault (Task init)

E67

Operating system failed.

Coast/Disable (open contactor enable relay)

No

DriveHardFault (SCANport Comm)

E68

DPI communication failed.

Decel/Disable

No

DriveHardFault (Objects Init)

E69

Nonvolatile memory attribute out of range.

Coast/Disable (open contactor enable relay)

No

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

No

179

Page 180

Chapter 7

Troubleshooting the Kinetix 6000 Drive System

Table 113 - Logix5000/Drive Fault Behavior (continued) Logix5000 Fault Message (HIM Message)

Error Code

Description

Drive Fault Action/ Attribute

Logix Designer Programmable Fault Action?

DriveHardFault (NV Mem Init)

E70

Nonvolatile memory corrupted.

Coast/Disable (open contactor enable relay)

No

DriveHardFault (Memory Init)

E71

RAM or nonvolatile memory validation failure.

Coast/Disable (open contactor enable relay)

No

DriveOvertempFault (Drive Overtemp)

E72

Inverter temperature limit exceeded. Firmware I2t protection does not generate a fault, rather it dynamically folds back current when 110% of drive rating is reached. Setting the Drive Thermal fault action to Status Only or Stop Motion bypasses the foldback behavior and allows the fault to occur.

N/A

Yes Drive Thermal

Communicate (Backplane Comm)

E73

Power rail backplane CAN communication failed.

Decel/Disable

No

DriveOvercurrentFault (Bus OverCurrent)

E74

The converter has exceeded its converter rating.

Coast/Disable (open contactor enable relay)

No

DriveOvervoltageFault (Shunt Time Out)

E75

The IAM/AM module or shunt module has exceeded its shunt resistor continuous rating. SHUTDOWN for IAM module, DISABLE for AM module. IAM module provides fault handling for shunt module.

Coast/Disable (open contactor enable relay)

No

DriveHardFault (Can Init)

E76

Either DPI or backplane CAN initialization failure.

Coast/Disable (open contactor enable relay)

No

DriveHardFault (Module Mismatch)

E77

Generated by IAM module if the power rating of an AM module on the same power rail does not match with IAM module input power rating.

Coast/Disable (open contactor enable relay)

No

DriveHardFault Sercos Init

E78

Control hardware fault detected.

Coast/Disable (open contactor enable relay)

No

DriveOvervoltageFault (Shunt Module Flt)

E79

Power rail mounted shunt module fault. Displayed on IAM module seven-segment fault status indicator.

Coast/Disable (open contactor enable relay)

No

HardwareFault (CPLD Flt)

E80

Control hardware fault detected.

Coast/Disable (open contactor enable relay)

No

HardwareFault (Common Bus Flt)

E81

Common-bus follower IAM module detected AC input power being applied.

Coast/Disable (open contactor enable relay)

No

HardwareFault (Precharge Timeout Flt)

E90

Precharge resistor power exceeds the resistor rating.

Coast/Disable (open contactor enable relay)

No

IPIMFault (IPIM Module Flt)

E95

A fault has occurred in one or more IPIM modules on the power rail.

Coast/Disable (open contactor enable relay)

No

(1) The Logix5000 Motor Thermal Fault Action is tied to the motor thermostat fault. If this is set to Shutdown or Disable (in controller), the drive folds back the current when the I2T calculation indicates that the motor temperature has exceeded 10% of its rated temperature. If it is set to Stop Motion or Status Only, the drive does not fold back the current. The I2T calculation never generates a fault. (2) The Logix5000 Drive Thermal Fault Action is tied to the drive thermostat fault. The drive always folds back the current when the I2T calculation indicates that the drive has exceeded 110% of its rating. The I2T calculation never generates a fault.

180