For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 25

Chapter

2

Plan the Kinetix 6000 Drive System Installation

This chapter describes system installation guidelines used in preparation for mounting your Kinetix® 6000 drive components. Topic

Page

System Design Guidelines

26

Electrical Noise Reduction

34

ATTENTION: Plan the installation of your system so that you can perform all cutting, drilling, tapping, and welding with the system removed from the enclosure. Because the system is of the open type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged in the circuitry, which can result in damage to components.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

25

Page 26

Chapter 2

Plan the Kinetix 6000 Drive System Installation

System Design Guidelines

Use the information in this section when designing your enclosure and planning to mount your system components on the panel. For on-line product selection and system configuration tools, including AutoCAD (DXF) drawings of the product, refer to http://www.rockwellautomation.com/en/e-tools.

System Mounting Requirements • To comply with UL and CE requirements, the Kinetix 6000 drive system must be enclosed in a grounded conductive enclosure offering protection as defined in standard EN 60529 (IEC 529) to IP54 such that they are not accessible to an operator or unskilled person. A NEMA 4X enclosure exceeds these requirements providing protection to IP66. • The panel you install inside the enclosure for mounting your system components must be on a flat, rigid, vertical surface that won’t be subjected to shock, vibration, moisture, oil mist, dust, or corrosive vapors. • Size the drive enclosure so as not to exceed the maximum ambient temperature rating. Consider heat dissipation specifications for all drive components. • Combined motor power cable lengths for all axes and hybrid cable lengths for all IDM units on the same DC bus must not exceed 240 m (787 ft) with 400V-class systems or 160 m (525 ft) with 200V-class systems. Drive-to-motor power cables must not exceed 90 m (295.5 ft). IMPORTANT

System performance was tested at these cable length specifications. These limitations also apply when meeting CE requirements.

• Segregate input power wiring and motor power cables from control wiring and motor feedback cables. Use shielded cable for power wiring and provide a grounded 360° clamp termination. • Use high-frequency (HF) bonding techniques to connect the modules, enclosure, machine frame, and motor housing, and to provide a lowimpedance return path for high-frequency (HF) energy and reduce electrical noise. Refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001, to better understand the concept of electrical noise reduction.

26

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 27

Plan the Kinetix 6000 Drive System Installation

Chapter 2

Transformer Selection The IAM module does not require an isolation transformer for three-phase input power. However, a transformer can be required to match the voltage requirements of the controller to the available service. To size a transformer for the main AC power inputs, refer to the Kinetix 6000 power specifications in the Kinetix Servo Drives Technical Data, publication KNX-TD003. IMPORTANT

If using an autotransformer, make sure that the phase to neutral/ground voltages do not exceed the input voltage ratings of the drive.

IMPORTANT

Use a form factor of 1.5 for three-phase power (where form factor is used to compensate for transformer, drive module, and motor losses, and to account for utilization in the intermittent operating area of the torque speed curve).

For example, to size a transformer to the voltage requirements of a 2094-BC01-M01-S integrated axis module: 2094-BC01-M01-S = 6 kW continuous x 1.5 = 9.0 KVA transformer

AC Line Filter Selection These AC line filters are available for your servo drive input power. Table 7 - Kinetix 6000 (three-phase) AC Line Filter Selection Current A @ 50 °C (122 °F)

Weight, approx kg (lb)

AC Line Filter Cat. No.

30

2.7 (5.9)

2090-XXLF-X330B

2094-AC16-M03-S

75

5.2 (11.4)

2090-XXLF-375

2094-AC32-M05-S

100

9.5 (20.9)

2090-XXLF-3100

30

2.7 (5.9)

2090-XXLF-X330B

2094-BC04-M03-S

75

5.2 (11.4)

2090-XXLF-375B

2094-BC07-M05-S

100

9.5 (20.9)

2090-XXLF-3100

Drive Cat. No.

Voltage

2094-AC05-MP5-S 2094-AC05-M01-S 2094-AC09-M02-S

500V AC 50/60 Hz

2094-BC01-MP5-S 2094-BC01-M01-S 2094-BC02-M02-S

500V AC 50/60 Hz

Refer to the Kinetix Motion Accessories Specifications Technical Data, publication KNX-TD004, for additional AC line filter specifications.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

27

Page 28

Chapter 2

Plan the Kinetix 6000 Drive System Installation

Circuit Breaker/Fuse Options The 2094-xCxx-Mxx-S and 2094-xMxx-S drive modules, and the Kinetix 6000M integrated drive-motor system (2094-SEPM-B24-S IPIM module and MDF-SBxxxxx IDM units) use internal solid-state motor shortcircuit protection and, when protected by suitable branch circuit protection, are rated for use on a circuit capable of delivering up to 200,000 A (fuses) and 65,000 A (circuit breakers). Table 8 - Control and DC-bus Circuit Protection Specifications IAM Module Cat. No.

Control Input Power Bussmann Fuse (1)

Allen-Bradley® Circuit Breaker (2) (non-UL)

2094-AC05-MP5-S

DC-bus Power Mersen Fuse (3)

Bussmann Fuse N/A

A50P20-1

FWH-35B

A50P35-4

FWH-60B

A50P60-4

FWH-125B

A50P125-4

FWJ-20A14F

DCT20-2

HSJ20

FWJ-40A

A70QS40-4

HSJ40

2094-BC04-M03-S

FWJ-70A

A70QS70-4

HSJ70

2094-BC07-M05-S

FWJ-125A

A70QS125-4

HSJ125

2094-AC05-M01-S 2094-AC09-M02-S

1492-SPM2D060 FNQ-R-10 (10 A)

2094-AC16-M03-S

1492-SPM2D200

2094-AC32-M05-S 2094-BC01-MP5-S 2094-BC01-M01-S 2094-BC02-M02-S

FNQ-R-10 (10 A) or FNQ-R-7.5 (7.5 A)

1492-SPM2D060 or 1492-SPM1D150

(1) Use FNQ-R-7.5 circuit breaker for higher single -cycle inrush current capability. This is recommended when the continuous control-power current exceeds 3.0 A. (2) Use 1492-SPM1D150 circuit breaker for higher single -cycle inrush current capability. This is recommended when the continuous control-power current exceeds 3.0 A. (3) Mersen fuses were formerly known as Ferraz Shawmut.

Input Power Circuit Protection (LIM) The 2094-AL09 and 2094-BL02 line interface modules (LIM) contain supplementary protection devices and, when protected by suitable branch circuit protection, are rated for use on a circuit capable of delivering up to 5000 A. When these modules are used, protection on the line side of the LIM module is required. Fuses must be class J or CC only. The 2094-ALxxS, 2094-BLxxS, and 2094-XL75S-Cx LIM modules contain branch circuit rated devices suitable for use on a circuit capable of delivering up to 65,000 A (400V-class) or 100,000 A (200V-class). Refer to the Line Interface Module Installation Instructions, publication 2094-IN005, for power specifications and more information on using the LIM module. Refer to Input Power Circuit Protection (without LIM) on page 29 when your drive system does not include the LIM module.

28

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 29

Drive Voltage (three-phase) nom

230V

230V

230V

230V

230V

360…480V

360…480V

360…480V

360…480V

360…480V

IAM Module Cat. No.

2094-AC05-MP5-S

2094-AC05-M01-S

2094-AC09-M02-S

2094-AC16-M03-S

2094-AC32-M05-S

2094-BC01-MP5-S

2094-BC01-M01-S

2094-BC02-M02-S

2094-BC04-M03-S

2094-BC07-M05-S

Kinetix 6000 Drives

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

LPJ-80SP (80 A) Class J

LPJ-45SP (45 A) Class J

140G-G6C3-C90

140G-G6C3-C50

NA

140G-G6C3-C90

140G-G6C3-C50

NA

Molded Case CB Cat. No.

N/A

1492-SPM3D400

1492-SPM3D300

N/A

1492-SPM3D400

1492-SPM3D300

Miniature CB Cat. No.

N/A

1489-M3D400

1489-M3D300

N/A

1489-M3D400

1489-M3D300

NA

140M-F8E-C45

140M-F8E-C32

140M-F8E-C32

NA

140M-F8E-C20

140M-F8E-C16

140M-F8E-C16

Motor Protection CB Cat. No.

140G-G6C3-C90

140G-G6C3-C50

NA

140G-G6C3-C90

140G-G6C3-C50

NA

Molded Case CB Cat. No.

Refer to the Kinetix Servo Drives Technical Data, publication KNX-TD003, for additional power specifications for your IAM module.

N/A

NA

140M-F8E-C45

1489-M3D400

KTK-R-30 (30 A) Class CC

140M-F8E-C32

NA

140M-F8E-C32

1489-M3D300

N/A

KTK-R-20 (20 A) Class CC

KTK-R-20 (20 A) Class CC

LPJ-80SP (80 A) Class J

LPJ-45SP (45 A) Class J

140M-F8E-C20

1489-M3D400

KTK-R-30 (30 A) Class CC

140M-F8E-C16

Motor Protection CB, Self-protected CMC Cat. No.

140M-F8E-C16

1489-M3D300

Miniature CB Cat. No.

KTK-R-20 (20 A) Class CC

KTK-R-20 (20 A) Class CC

Fuses (Bussmann) Cat. No.

UL Applications

IEC (non-UL) Applications

LIM Modules (catalog numbers 2094-ALxxS, 2094-BLxxS, and 2094-XL75S-Cx) provide branch circuit protection to the IAM module. Follow all applicable NEC and local codes.

Table 9 - Input Power Circuit Protection Specifications

IMPORTANT

The fuses and Allen-Bradley circuit breakers shown in Table 9 are recommended for use with 2094-xCxx-Mxx-S IAM modules when the line interface module (LIM) is not used.

Input Power Circuit Protection (without LIM)

Plan the Kinetix 6000 Drive System Installation Chapter 2

29

Page 30

Chapter 2

Plan the Kinetix 6000 Drive System Installation

Enclosure Selection This example is provided to assist you in sizing an enclosure for your Bulletin 2094 drive system. The example system consists of these components: • 6-axis Bulletin 2094 servo drive system • Line Interface Module (LIM) • ControlLogix® chassis and modules (controller) Size the Bulletin 2094 servo drive and LIM module and use the results to predict the amount of heat dissipated into the enclosure. You also need heat dissipation data from other equipment inside the enclosure (such as the ControlLogix controller). Once the total amount of heat dissipation (in watts) is known, you can calculate the minimum enclosure size. Table 10 - Bulletin 2094 System Heat Dissipation Example Loading (1)

Heat Dissipation (1) watts

15 kW (converter section)

20%

44

15 A (inverter section)

40%

72

Axis module (AM), 400/460V, 15 A

60%

93

2094-BM02-x

Axis module (AM), 400/460V, 15 A

60%

93

2094-BM01-x

Axis module (AM), 400/460V, 9 A

40%

73

2094-BM01-x

Axis module (AM), 400/460V, 9 A

40%

73

2094-BM01-x

Axis module (AM), 400/460V, 9 A

20%

57

2094-BL25S

Line interface module (LIM), 400/460V, 25 A; 24V DC 20 A

100%

43

2094-PRS6

Power rail, 460V, 6 axis

N/A

0

2090-XB33-32

Resistive brake module (RBM), 33 A, 32 Ω

N/A

30

Enclosure Component

Description

2094-BC02-M02-x

Integrated axis module (IAM), 400/460V

2094-BM02-x

Total Kinetix 6000 system wattage

578

(1) To determine heat dissipation specifications for your drive system components, refer to Table 12 on page 32.

30

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 31

Plan the Kinetix 6000 Drive System Installation

Chapter 2

Table 11 - ControlLogix System Heat Dissipation Example Enclosure Component

Description

Backplane Power Load (1) watts

Heat Dissipation (1) watts

1756-M08SE

8-axis Sercos interface module

3.2

0

1756-L5563

L63 ControlLogix processor

4.5

0

1756-IB16D

16 -point input module

0.84

5.8

1756-OB16D

16 -point output module

4.64

3.3

1756-ENxTx

EtherNet/IP communication module

4.0

0

17.18 (2)

N/A

Backplane total 1756-PB72

24V DC ControlLogix power supply

N/A

25 (2)

1756-A7

7-slot mounting chassis

N/A

N/A

Total ControlLogix system wattage

34.1

(1) For ControlLogix module specifications, refer to the ControlLogix Selection Guide, publication 1756-SG001. (2) Real power heat dissipation is determined by applying the backplane power load (17.18W) to the graph below.

Figure 6 - ControlLogix Real Power 1756-P B72 1756-P B75 DC

Backplane Power Load (watts)

75 60 45 30 15 0 0

20

40

60

80

100

Real Power (watts)

For backplane power loading requirements of other ControlLogix power supplies, refer to the ControlLogix Selection Guide, publication 1756-SG001. In this example, the amount of power dissipated inside the cabinet is the sum of the Bulletin 2094 system value (578 W) and the ControlLogix system value (34 W) for a total of 612 W. With no active method of heat dissipation (such as fans or air conditioning) either of these approximate equations can be used. Metric

Standard English

A=

0.38Q 1.8T - 1.1

A=

4.08Q T - 1.1

Where T is temperature difference between inside air and outside ambient (°C), Q is heat generated in enclosure (Watts), and A is enclosure surface area (m2). The exterior surface of all six sides of an enclosure is calculated as:

Where T is temperature difference between inside air and outside ambient (°F), Q is heat generated in enclosure (Watts), and A is enclosure surface area (ft²). The exterior surface of all six sides of an enclosure is calculated as:

A = 2dw + 2dh + 2wh

A = (2dw + 2dh + 2wh) / 144

Where d (depth), w (width), and h (height) are in meters.

Where d (depth), w (width), and h (height) are in inches.

Total system watts dissipated (Q) was calculated at 612 W. The maximum ambient rating of the Bulletin 2094 system is 50 °C (122 °F) and if the maximum environmental temperature is 30 °C (86 °F), then T=20 in the equation below. A=

0.38 (612) = 6.66 m 2 1.8 (20) - 1.1

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

31

Page 32

Chapter 2

Plan the Kinetix 6000 Drive System Installation

In this example, the enclosure must have an exterior surface of 6.66 m2. If any portion of the enclosure is not able to transfer heat, do not include that portion in the calculation. Because the minimum cabinet depth to house the 460V drive (selected for this example) is 302 mm (11.9 in.), then the cabinet needs to be approximately 2500 mm (high) x 950 mm (wide) x 302 mm (deep). 2 x (0.3 x 0.95) + 2 x (0.3 x 2.5) + 2 x (0.95 x 2.5) = 6.82 m2 Because this cabinet size is considerably larger than what is necessary to house the system components, consider some means of cooling in a smaller cabinet to be more efficient. Contact your cabinet manufacturer for options available to cool your cabinet. Table 12 - Power Dissipation Specifications Usage as % of Rated Power Output (watts)

Bulletin 2094 Drive Modules (1) 20%

40%

60%

80%

100%

2094-AC05-MP5-S

8

11

15

19

24

2094-AC05-M01-S

9

12

16

20

25

2094-AC09-M02-S

14

20

28

36

46

2094-AC16-M03-S

19

30

43

58

74

2094-AC32-M05-S

41

68

100

136

176

18

21

25

29

2094-BC02-M02-S

36

44

54

64

75

2094-BC04-M03-S

50

67

87

110

135

2094-BC07-M05-SS

71

101

137

179

226

2094-AC05-MP5-S or 2094-AMP5-S

28

32

37

41

46

2094-AC05-M01-S or 2094-AM01-S

31

38

46

54

62

2094-AC09-M02-S or 2094-AM02-S

34

45

57

70

84

2094-AC16-M03-S or 2094-AM03-S

48

68

91

116

144

2094-AC32-M05-S or 2094-AM05-S

104

156

212

274

342

2094-BC01-MP5-S or 2094-BMP5-S

46

54

61

69

77

2094-BC01-M01-S or 2094-BM01-S

57

73

90

108

126

2094-BC02-M02-S or 2094-BM02-S

53

72

93

116

142

2094-BC04-M03-S or 2094-BM03-S

94

130

169

211

255

2094-BC07-M05-S or 2094-BM05-S

121

183

252

326

407

Shunt module - 2094-BSP2

68

121

174

227

280

IPIM module - 2094-SEPM-B24-S

To calculate power dissipation for IPIM modules on your 2094 power rail, refer to the Kinetix 6000M Integrated Drive-Motor User Manual, publication 2094-UM003.

IAM (converter) module (2)

2094-BC01-MP5-S 2094-BC01-M01-S

34 33

IAM (inverter) module or AM module (2)

(1) Power dissipation for the Bulletin 2094 control modules, catalog numbers 2094-SE02F-M00-Sx and 2094-EN02D-M01-Sx, is included in the IAM and AM power module specifications. (2) Internal shunt power is not included in the calculations and must be added based on utilization.

32

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 33

Plan the Kinetix 6000 Drive System Installation

Chapter 2

Minimum Clearance Requirements This section provides information to assist you in sizing your cabinet and positioning your Bulletin 2094 system components. IMPORTANT

Mount the module in an upright position. Do not mount the module on its side.

Figure 7 illustrates minimum clearance requirements for proper airflow and installation: • Additional clearance is required for the cables and wires connected to the top and front of the drive. • Additional clearance left and right of the power rail is required when the drive is mounted adjacent to noise sensitive equipment or clean wireways. Figure 7 - Minimum Clearance Requirements Drive Cat. No.

Clearance above for airflow and installation.

Kinetix 6000 Drive System Mounted on 2094 Power Rail

F

A and C

237 mm (9.3) in.

A and C

420 mm (16.5) in.

2094-AC05-Mxx-x 2094-AC09-M02-x 2094-AMP5-x, 2094-AM01-x, 2094-AM02-x

F

2094-AC16-M03-x 2094-AC32-M05-x Clearance right of the module is not required. (1)

Clearance left of the module is not required. (1)

Series

2094-AM03-x, 2094-AM05-x 2094-BC01-Mxx-x 2094-BC02-M02-x

50.8 (2.0 in.) clearance below drive for airflow and installation.

Power Rail (2094-PRSx is shown)

Refer to Power Dissipation Specifications on page 32, and Kinetix Servo Drives Technical Data, publication KNX-TD003, for Kinetix 6000 drive dimensions. (1) The power rail (slim), catalog number 2094-PRSx, extends left and right of the first and last module 5.0 mm (0.20 in.). The Bulletin 2094-PRx power rail extends approximately 25.4 mm (1.0 in.) left of the IAM module and right of the last module mounted on the rail.

2094-BMP5-x, 2094-BM01-x, 2094-BM02-x

A, B, and C

2094-SEPM-B24-S 2094-BSP2

A

2094-BC04-M03-x 2094-BM03-x

A, B, and C

2094-BC07-M05-x 2094-BM05-x

B and C

2094-BC07-M05-x 2094-BM05-x

A and C

287 mm (11.3) in.

374 mm (14.7) in. 436 mm (17.2) in.

Table 13 - Minimum Cabinet Depth Drive Cat. No.

Cabinet Depth, min (1)

Drive Cat. No.

Cabinet Depth, min (1)

2094-AC05-Mxx-x, 2094-AC09-M02-x, 2094-AMP5x, 2094-AM01-x, 2094-AM02-x

198 mm (7.8 in.)

2094-AC16-M03-x, 2094-AC32-M05-x, 2094-AM03x, 2094-AM05-x

198 mm (7.8 in.)

2094-BC01-Mxx-x, 2094-BC02-M02-x, 2094-BMP5-x, 2094-BM01-x, 2094-BM02-x

272 mm (10.7 in.)

2094-BC04-M03-x, 2094-BC07-M05-x, 2094-BM03-x, 2094-BM05-x

272 mm (10.7 in.)

2094-BSP2

272 mm (10.7 in.)

2094-SEPM-B24-S

263 mm (10.3 in.)

(1) Minimum cabinet depth is based on the use of 2090-K6CK-xxxx low-profile connector kits. Other means of making feedback connections can require additional clearance.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

33