Page 34

Chapter 2

Plan the Kinetix 6000 Drive System Installation

Electrical Noise Reduction

This section outlines best practices that minimize the possibility of noiserelated failures as they apply specifically to Kinetix 6000 system installations. For more information on the concept of high-frequency (HF) bonding, the ground plane principle, and electrical noise reduction, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.

Bonding Modules Bonding is the practice of connecting metal chassis, assemblies, frames, shields, and enclosures to reduce the effects of electromagnetic interference (EMI). Unless specified, most paints are not conductive and act as insulators. To achieve a good bond between power rail and the subpanel, surfaces need to be paint-free or plated. Bonding metal surfaces creates a low-impedance return path for high-frequency energy. IMPORTANT

To improve the bond between the power rail and subpanel, construct your subpanel out of zinc plated (paint-free) steel.

Improper bonding of metal surfaces blocks the direct return path and allows high-frequency energy to travel elsewhere in the cabinet. Excessive highfrequency energy can effect the operation of other microprocessor controlled equipment.

34

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 35

Plan the Kinetix 6000 Drive System Installation

Chapter 2

These illustrations show details of recommended bonding practices for painted panels, enclosures, and mounting brackets. Figure 8 - Recommended Bonding Practices for Painted Panels Stud-mounting the Subpanel to the Enclosure Back Wall

Stud-mounting a Ground Bus or Chassis to the Subpanel Subpanel

Back Wall of Enclosure

Mounting Bracket or Ground Bus

Subpanel

Welded Stud

Star Washer Nut

Scrape Paint

Flat Washer Welded Stud

Nut

Flat Washer

Use a wire brush to remove paint from threads to maximize ground connection. Use plated panels or scrape paint on front of panel.

Star Washer

If the mounting bracket is coated with a non-conductive material (anodized or painted), scrape the material around the mounting hole.

Bolt-mounting a Ground Bus or Chassis to the Back-panel Subpanel

Bolt

Tapped Hole Ground Bus or Mounting Bracket

Nut Star Washer Scrape paint on both sides of panel and use star washers. Star Washer

Flat Washer Nut

Flat Washer

Star Washer

If the mounting bracket is coated with a non-conductive material (anodized or painted), scrape the material around the mounting hole.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

35

Page 36

Chapter 2

Plan the Kinetix 6000 Drive System Installation

Bonding Multiple Subpanels Bonding multiple subpanels creates a common low impedance exit path for the high frequency energy inside the cabinet. If subpanels are not bonded together, and do not share a common low impedance path, the difference in impedance can affect networks and other devices that span multiple panels: • Bond the top and bottom of each subpanel to the cabinet by using 25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) wire braid. As a rule, the wider and shorter the braid is, the better the bond. • Scrape the paint from around each fastener to maximize metal-to-metal contact. Figure 9 - Multiple Subpanels and Cabinet Recommendations

Wire Braid 25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) Cabinet ground bus bonded to the subpanel.

Paint removed from cabinet.

36

Wire Braid 25.4 mm (1.0 in.) by 6.35 mm (0.25 in.)

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 37

Plan the Kinetix 6000 Drive System Installation

Chapter 2

Establishing Noise Zones Observe these guidelines when the 2094-ALxxS, 2094-BLxxS, or 2094-XL75S-Cx LIM module is used in the Bulletin 2094 system and mounted left of the IAM module with the AC (EMC) line filter mounted above the LIM module: • The clean zone (C) is to the right and beneath the Bulletin 2094 system (gray wireway). • The dirty zone (D) is to the left and above the Bulletin 2094 system, and above and below the LIM module (black wireway). • The very dirty zone (VD) is from the filter output to IAM module. Shielded cable is required on the EMC filter (load side) and the braided shield attached to the clamp provided. • The Sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Figure 10 - Noise Zones (LIM mounted left of IAM module) Dirty Wireway

D

Clean Wireway

AC Line Filter (required for CE)

VD Motor Power Cables

D VAC Load

D

D

D

Very Dirty Filter/IAM Connections Segregated (not in wireway)

D

VAC Line

C VD Fiber-optic Cable

No sensitive (2) equipment within 150 mm (6.0 in.). Kinetix 6000 System Line Interface Module I/O (1) and Feedback Cables

D

D

C

Route 24V DC I/O shielded cable.

Route encoder/analog/registration shielded cables.

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

37

Page 38

Chapter 2

Plan the Kinetix 6000 Drive System Installation

Observe these guidelines when the 2094-ALxxS, 2094-BLxxS, or 2094-XL75S-Cx LIM module is used in the Bulletin 2094 system and mounted right of the IAM module with the AC (EMC) line filter mounted behind the IAM module: • The clean zone (C) is to the left and beneath the Bulletin 2094 system (gray wireway). • The dirty zone (D) is to the right and above the Bulletin 2094 system, and above and below the LIM module (black wireway). • The very dirty zone (VD) is from the filter output to IAM module. Shielded cable is required on the EMC filter (load side) and the braided shield attached to the clamp provided. • The Sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Figure 11 - Noise Zones (LIM with EMC filter behind IAM module) Dirty Wireway

Clean Wireway Motor Power Cables

Very Dirty Filter/IAM Connections Segregated (not in wireway)

D

D

D D

VAC Line

VD C

Control VAC, AUX VAC Output, and 24V DC Brake

Fiber-optic Cable

D I/O

VD

D

VAC Load

No sensitive (2)

D AC (EMC) Line Filter equipment within 150 mm (6.0 in.). Kinetix 6000 System

C

I/O (1) and Feedback Cables

Line Interface Module

C D

Route encoder/analog/registration shielded cables.

Route 24V DC I/O shielded cable.

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.

38

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 39

Plan the Kinetix 6000 Drive System Installation

Chapter 2

Observe these guidelines when the 2094-ALxxS, 2094-BLxxS, or 2094-XL75S-Cx LIM module is used in the Bulletin 2094 system and mounted right of the drive with the AC (EMC) line filter mounted behind the LIM module: • The clean zone (C) is to the left and beneath the Bulletin 2094 system (gray wireway). • The dirty zone (D) is to the right and above the Bulletin 2094 system, and above and below the LIM module (black wireway). • The very dirty zone (VD) is from the filter output to drive. Shielded cable is required on the EMC filter (load side) and the braided shield attached to the clamp (when provided). • The Sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Figure 12 - Noise Zones (EMC filter behind LIM module) Dirty Wireway

Clean Wireway Motor Power Cables

Very Dirty Filter/IAM Connections Segregated (not in wireway)

VD

D

D

D Control VAC, Auxiliary VAC, and 24V DC Brake

D VAC Line

VAC Load

Fiber-optic Cable

D LIM I/O

No sensitive (2) equipment within 150 mm (6.0 in.).

VD AC (EMC) Line Filter

C

PR PRS

Kinetix 6000 System

LIM

I/O (1) and Feedback Cables

C

Route encoder/analog/registration shielded cables.

Line Interface Module (2094-ALxxS shown) D

2094 Mounting (3) Brackets x2

Route 24V DC I/O shielded cable.

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001. (3) Only the 2094-ALxxS and 2094-XL75S-Cx LIM modules are compatible with the 2094 mounting brackets. The 2094-BLxxS, 2094AL09, and 2094-BL02 LIM modules are not compatible.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

39

Page 40

Chapter 2

Plan the Kinetix 6000 Drive System Installation

Keep the DC common-bus cable (very dirty) segregated from all other cables (not in a wireway) when the 2094-ALxxS, 2094-BLxxS, or 2094-XL75S-Cx LIM module is used in a DC common-bus configuration and the follower IAM module is mounted below the leader IAM module. Figure 13 - Noise Zones (DC common bus) Dirty Wireway

D

Clean Wireway

VD

AC Line Filter (required for CE)

Motor Power Cables

D

Very Dirty Filter/IAM Connections Segregated (not in wireway)

D

D C

VD

VAC Line, AUX VAC Output, 24V

Fiber-optic Cable

VAC Load

D

D

VAC Line No sensitive (2) equipment within 150 mm (6.0 in.). Kinetix 6000 System (leader IAM) I/O (1) and Feedback Cables

D

Line Interface Module

C

D

D

D

D

VD

C

Very Dirty DC Bus Connections Segregated (not in wireway)

Fiber-optic Cable

No sensitive (2) equipment within 150 mm (6.0 in.). Kinetix 6000 System (follower IAM) I/O (1) and Feedback Cables

C

Route 24V DC I/O shielded cable.

Route encoder/analog/registration shielded cables.

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.

40

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 41

Plan the Kinetix 6000 Drive System Installation

Chapter 2

Observe these guidelines when the 2094-AL09 or 2094-BL02 LIM module is used in the Bulletin 2094 system and mounted left of the IAM module: • The clean zone (C) is to the right and beneath the Bulletin 2094 system (gray wireway). • The dirty zone (D) is to the left and above the Bulletin 2094 system, and above and below the LIM module (black wireway). • The very dirty zone (VD) is limited to where the LIM module VAC output jumpers over to the IAM module. Shielded cable is required only if the very dirty cables enter a wireway. • The Sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. This layout is preferred due to the reduced size of the very dirty zone. Figure 14 - Noise Zones (LIM mounted left of IAM module) Dirty Wireway

D

Clean Wireway

Very Dirty Filter/IAM Connections (1)in wireway) Segregated (not

Motor Power Cables

C

D D

VD

Fiber-optic Cable

No sensitive (2) equipment within 150 mm (6.0 in.). Kinetix 6000 System

D

Line Interface Module

C D

Route 24V DC I/O shielded cable.

C I/O (1) and Feedback Cables Route encoder/analog/registration shielded cables.

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

41

Page 42

Chapter 2

Plan the Kinetix 6000 Drive System Installation

Observe these guidelines when the 2094-AL09 or 2094-BL02 LIM module is used in the Bulletin 2094 system and mounted above the IAM module: • The clean zone (C) is to the right and beneath the Bulletin 2094 system (gray wireway). • The dirty zone (D) is to the left and above the Bulletin 2094 system, and above and below the LIM module (black wireway). • The LIM VAC output is very dirty (VD). Use shielded cable with a braid clamp attached at both ends of the cable to reduce the rating to dirty (D). • The Sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Figure 15 - Noise Zones (LIM mounted above IAM module) Dirty Wireway

Clean Wireway

VD

D

Very dirty LIM/IAM (1) connections must be shielded with braid clamp at both ends. Line Interface Module

D

Motor Power Cables

C

D Fiber-optic Cable

No sensitive (3) equipment within 150 mm (6.0 in.). Kinetix 6000 System

C

C D

I/O (2) and Feedback Cables Route encoder/analog/registration shielded cables. Route 24V DC I/O shielded cable.

(1) For examples of shield clamp attachment, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001. (2) If drive system I/O cable contains (dirty) relay wires, route cable in dirty wireway. (3) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.

42

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017