For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF
Page 43
Plan the Kinetix 6000 Drive System Installation
Chapter 2
Observe these guidelines when your system includes the 2094-SEPM-B24-S IPIM module. In this example, a 2094-BL02 LIM module is used in the Bulletin 2094 system and mounted left of the IAM module: • Establish clean (C) and dirty zones (D) similar to other Bulletin 2094 drive systems. • The Sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. • IPIM digital input wires are noise sensitive and belong with the fiberoptic cables in the clean zone. • Ethernet cables are noise sensitive and belong in the clean zone, however, they are connected only when programming the IPIM module. • IDM network cables, although noise sensitive by nature, are shielded and can be routed with the hybrid cables outside of the enclosure. • The Bulletin 2090 hybrid cable is dirty and belongs in the dirty zone. This layout is preferred due to the reduced size of the very dirty zone. Figure 16 - Noise Zones (Bulletin 2094 power rail with IPIM module) Dirty Wireway
D
Clean Wireway
Very Dirty Filter/IAM Connections (1)in wireway) Segregated (not
Motor and Hybrid Cables
C
D D
VD
Fiber-optic Cables and IPIM Digital Input Wires No sensitive (2) equipment within 150 mm (6.0 in.). Kinetix 6000 System
2094-BL02 or 2094-BLxxS Line Interface Module
C
D D
Route 24V DC I/O shielded cable.
C I/O (1), Feedback, and Network Cables Route encoder/analog/registration shielded cables.
(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
43
Page 44
Chapter 2
Plan the Kinetix 6000 Drive System Installation
Observe these guidelines when individual input power components are used in the Bulletin 2094 system and the Bulletin 2094 LIM module is not used: • The clean zone (C) is beneath the Bulletin 2094 system and includes the I/O wiring, feedback cable, and DC filter (gray wireway). • The dirty zone (D) is above the Bulletin 2094 system (black wireway) and includes the circuit breakers, transformer, 24V DC power supply, contactors, AC line filter, and motor power cables. • The very dirty zone (VD) is limited to where the AC line (EMC) filter VAC output jumpers over to the IAM module. Shielded cable is required only if the very dirty cables enter a wireway. • The Sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Figure 17 - Noise Zones (without LIM module) Dirty Wireway
Very Dirty Filter/IAM Connections Segregated (not in wireway)
D D (1)
Clean Wireway Motor Power Cables
D Fiber-optic Cable
(2)
C VD
Contactors Circuit Breaker
AC Line Filter (required for CE)
24V Motor Brake PS
(4) XFMR
Kinetix 6000 System
DC Filter
(3)
(2)
C
I/O (1) and Feedback Cables
C
D
Route 24V DC I/O shielded cable.
Route encoder/analog/registration shielded cables.
(1) If drive system I/O cable contains (dirty) relay wires, route cable in dirty wireway. (2) When space to the right of the IAM does not permit 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001. (3) This is a clean 24V DC available for any device that requires it. The 24V enters the clean wireway and exits to the right. (4) This is a dirty 24V DC available for motor brakes and contactors. The 24V enters the dirty wireway and exits to the left.
44
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 45
Plan the Kinetix 6000 Drive System Installation
Chapter 2
Observe these guidelines when installing your Logix5000™ Sercos interface module: • The clean zone (C) is beneath the less noisy modules (I/O, analog, encoder, registration, an so forth (gray wireway). • The dirty zone (D) is above and below the power supply and noisy modules (black wireway). • The Sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Figure 18 - Noise Zones (ControlLogix chassis) Clean Wireway
Dirty Wireway
D
(1) Route dirty wireways directly above the ControlLogix controller chassis (shielded by the chassis).
AC Line Filter
D
Line Filter/Power Supply Connections Segregated (not in wireway)
Spare Slots
Dirty I/O (24V DC I/O, AC I/O)
C
Clean I/O (Analog, Encoder Registration)
Cable Categories for Kinetix 6000 Systems These tables indicate the zoning requirements of cables connecting to the Kinetix 6000 drive components. Table 14 - IAM Module (converter side) Zone Wire/Cable
Connector
CTRL 1 and 2
CPD
DC-/DC+ (unshielded cable) L1, L2, L3 (shielded cable)
Very Dirty
Method Dirty
Clean
Ferrite Sleeve
Shielded Cable
X X
IPD
L1, L2, L3 (unshielded cable)
X
X
X
CONT EN- and CONT EN+ (M1 contactor)
CED
DPI
DPI
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
X X
X
45
Page 46
Chapter 2
Plan the Kinetix 6000 Drive System Installation
Table 15 - AM Module or Axis Module (inverter side) Zone Wire/Cable
Connector
U, V, W (motor power)
MP
Very Dirty
Dirty
DBRK-, DBRK+ (resistive brake)
Clean
Ferrite Sleeve
X
Shielded Cable X
COM, PWR (24V DC), filtered (1) COM, PWR (24V DC), unfiltered (2)
Method
X X
BC
X
MBRK-, MBRK+ (motor brake)
X
MBRK-, MBRK+ (motor brake) 1326AB motors with resolver feedback
BC
X
COM, PWR (24V DC), safety enable, and feedback signals for safe torque-off feature
STO
X
Motor feedback
MF
X
X
Auxiliary feedback
AF
X
X
X
X
Registration and analog outputs Others Fiber-optic
IOD Rx and Tx
X
X No restrictions
(1) This is a clean 24V DC available for any device that requires it. (2) This is a dirty 24V DC available for motor brakes and contactors.
Table 16 - Line Interface Module (LIM) Zone Wire/Cable
Connector
VAC line (main input)
IPL
X
Aux power input
APL
X
VAC load (shielded option) VAC load (unshielded option)
OPL
Very Dirty
Dirty
Method Clean
Ferrite Sleeve
X
Shielded Cable
X
X
Control power output
CPL
X
MBRK PWR, MBRK COM
P1L/PSL
X
Status I/O
IOL
X
Aux power output
P2L
X
Table 17 - Shunt Module Zone Wire/Cable
Connector
COL, DC+ (shielded option) COL, DC+ (unshielded option)
46
RC
Very Dirty
Dirty
Method Clean
Ferrite Sleeve
Shielded Cable
X
X
X
X
Thermal switch
TS
X
Fan (if present)
N/A
X
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 47
Plan the Kinetix 6000 Drive System Installation
Chapter 2
Table 18 - IDM Power Interface Module (IPIM) Zone
Wire/Cable
Very Dirty
Hybrid DC bus power, control power, inter-module communication, and Safe Torque Off (1)
Dirty
Method Clean
Ferrite Sleeve
X
Enable input
Shielded Cable X
X
X
Ethernet network
X
X
IDM network (1)
X
X
Fiber-optic
No restrictions
(1) There is no option for making your own hybrid power or IDM network cables.
Table 19 - Resistive Brake Module (RBM) Zone
Wire/Cable
Connections
Resistive brake module coil power
TB3-6 and TB3-7
X
Resistive brake module I/O
TB1-1…TB1-5 and TB3-8
X
Resistive brake module drive and motor power
TB1 and TB2
X
230V power
TB4
X
Very Dirty
Dirty
Method Clean
Ferrite Sleeve
Shielded Cable
X
Noise Reduction Guidelines for Drive Accessories Refer to this section when mounting an AC (EMC) line filter or external shunt module for guidelines designed to reduce system failures caused by excessive electrical noise.
AC Line Filters Observe these guidelines when mounting your AC (EMC) line filter (refer to the figure on page 44 for an example): • Mount the AC line filter on the same panel as the Kinetix 6000 drive and as close to the power rail as possible. • Good HF bonding to the panel is critical. For painted panels, refer to the examples on page 35. • Segregate input and output wiring as far as possible. IMPORTANT
CE test certification applies only to AC line filter and single power rail. Sharing a line filter with multiple power rails can perform satisfactorily, but the user takes legal responsibility.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
47
Page 48
Chapter 2
Plan the Kinetix 6000 Drive System Installation
External Shunt Modules Observe these guidelines when mounting your external shunt module outside the enclosure: • Mount circuit components and wiring in the very dirty zone or in an external shielded enclosure. Run shunt power and fan wiring inside metal conduit to minimize the effects of EMI and RFI. • Mount resistors (other than metal-clad) in a shielded and ventilated enclosure outside the cabinet. • Keep unshielded wiring as short as possible. Keep shunt wiring as flat to the cabinet as possible. • Route thermal switch and fan wires separate from shunt power. Figure 19 - External Shunt Module Outside the Enclosure Customer-supplied Metal Enclosure 150 mm (6.0 in.) clearance (min) on all four sides of the shunt module.
Metal Conduit (where required by local code)
1394 Digital Servo Controller 300W Shunt Module ALLEN-BRADLEY
R
BULLETIN 1394 300W SHUNT MODULE CAT. PART INPUT DC INPUT AC FOR FUSE REPLACEMENT USE: BUSSMAN CAT. NO.
SER.
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
Shunt thermal Switch and Fan Wires (when present) Dirty Wireway
(1)
D
Very Dirty Connections Segregated (not in wireway)
D
Clean Wireway
Shunt Power Wiring Methods: Twisted pair in conduit (1st choice). Shielded twisted pair (2nd choice). Twisted pair, two twists per foot (min) (3rd choice).
Motor Power Cables 2094-BSP2 Shunt Module
D
D
VD
VD
No sensitive equipment within 150 mm (6.0 in.). Kinetix 6000 System
D
C
C
Line Interface Module
D I/O and Feedback Cables Route 24V DC I/O shielded cable.
48
Enclosure
Route encoder/analog/registration shielded cables.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 49
Plan the Kinetix 6000 Drive System Installation
Chapter 2
When mounting your shunt module inside the enclosure, follow these additional guidelines: • Mount metal-clad modules anywhere in the dirty zone, but as close to the Bulletin 2094 drive system as possible. • Route shunt power wires with motor power cables. • Keep unshielded wiring as short as possible. Keep shunt wiring as flat to the cabinet as possible. • Separate shunt power cables from other sensitive, low voltage signal cables. Figure 20 - External Shunt Module Inside the Enclosure Clean Wireway
Dirty Wireway Enclosure 150 mm (6.0 in.) clearance (min) on all four sides of the shunt module.
1394 Digital Servo Controller 300W Shunt Module ALLEN-BRADLEY
R
BULLETIN 1394 300W SHUNT MODULE CAT. PART INPUT DC INPUT AC FOR FUSE REPLACEMENT USE: BUSSMAN CAT. NO.
SER.
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
Shunt thermal Switch and Fan Wires (when present) Very Dirty Connections Segregated (not in wireway)
D
VD
Motor Power Cables
D
D
VD
D
Shunt Power Wiring Methods:
Twisted pair in conduit (1st choice). Shielded twisted pair (2nd choice). Twisted pair, two twists per foot (min) (3rd choice).
2094-BSP2 Shunt Module No sensitive equipment within 150 mm (6.0 in.).
Kinetix 6000 System
D
Line Interface Module
D
C
C I/O and Feedback Cables
Route 24V DC I/O shielded cable.
Route encoder/analog/registration shielded cables.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
49
Page 50
Chapter 2
Plan the Kinetix 6000 Drive System Installation
Resistive Brake Modules Observe these guidelines when mounting your RBM module: • Mount circuit components and wiring in the dirty zone or in an external shielded enclosure. If mounting the RBM module in a separate ventilated shielded enclosure, run wiring inside metal conduit to minimize the effects of EMI and RFI. • Keep unshielded wiring as short as possible. Keep wiring as flat to the cabinet as possible. • Route RBM module power and I/O cables separate from other sensitive low voltage signal cables. Figure 21 - Noise Zones (RBM mounted above AM module) Clean Wireway
Dirty Wireway
D
D
RBM I/O
Very Dirty LIM/IAM Connections Segregated (not in wireway)
LIM VAC Input Power
Motor Power Cables
D
C D
VD
Fiber-optic Cable No sensitive equipment within 150 mm (6.0 in.). Kinetix 6000 System
D
Line Interface Module
C D
LIM and IAM/AM (dirty) I/O
IAM/AM Feedback and (clean) I/O
Motor Brake and Thermal Switch The thermal switch and brake are mounted inside the motor, but how you connect to the axis module depends on the motor series. Refer to Wire the Motor/Resistive Brake (BC) Connector on page 113 for wiring guidelines. Refer to Axis Module/Rotary Motor Wiring Examples beginning on page 198 for the interconnect diagram of your drive/motor combination.
50
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017