Mount the Kinetix 6000 Drive System This chapter provides the system installation procedures for mounting your Kinetix® 6000 drive components on the Bulletin 2094 power rail. Topic

Page

Before You Begin

51

Determine Mounting Order

52

Mount Modules on the Power Rail

54

This procedure assumes you have prepared your panel, mounted your Bulletin 2094 power rail, and understand how to bond your system. For installation instructions regarding equipment and accessories not included here, refer to the instructions that came with those products. SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting and wiring of the Bulletin 2094 power rail and drive modules prior to applying power. Once power is applied, connector terminals can have voltage present even when not in use. ATTENTION: Plan the installation of your system so that you can perform all cutting, drilling, tapping, and welding with the system removed from the enclosure. Because the system is of the open type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged in the circuitry, which can result in damage to components.

Before You Begin

Before you begin, consider your Bulletin 2094 power rail installation and using 2094 mounting brackets.

Using the 2094 Mounting Brackets You can use Bulletin 2094 mounting brackets to mount the power rail or LIM module over the AC line filter. Refer to the 2094 Mounting Brackets Installation Instructions, publication 2094-IN008, when using mounting brackets with your Kinetix 6000 drive system.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

51

Page 52

Chapter 3

Mount the Kinetix 6000 Drive System

Installing the 2094 Power Rail The Bulletin 2094 power rail comes in lengths to support one IAM module and up to seven additional AM/IPIM modules, or up to six additional AM/ IPIM modules and one shunt module. The connector pins for each slot are covered by a protective cover. The cover is designed to protect the pins from damage and make sure that no foreign objects lodge between the pins during installation. Refer to the Kinetix 6000 Power Rail Installation Instructions, publication 2094-IN003, when installing your power rail. ATTENTION: To avoid damage to the power rail during installation, do not remove the protective covers until the module for each slot is ready for mounting. The Kinetix 6000M integrated drive-motor (IDM) system is supported by Bulletin 2094 (400V-class) power rail configurations. You can mount up to four IDM power interface (IPIM) modules on the Bulletin 2094 power rail. Refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003, for more information.

Determine Mounting Order

Mount IAM, AM/IPIM, shunt, and slot-filler modules in the order (left to right) as shown in Figure 22. Mount axis modules and the IPIM module according to power utilization (highest to lowest) from left to right starting with the highest power utilization. Power utilization is the average power (kW) consumed by a servo axis. If Motion Analyzer software was used to size the axis, the calculated axis power required can be used for the power utilization value. If Motion Analyzer software was not used, you can use the continuous power value (kW) for each module to determine mounting order. Table 20 - Kinetix 6000 (200V-class) Axis Modules Attribute

2094-AMP5-S

2094-AM01-S

2094-AM02-S

2094-AM03-S

2094-AM05-S

Continuous Power Output, nom

1.2 kW

1.9 kW

3.4 kW

5.5 kW

11.0 kW

Table 21 - Kinetix 6000 (400V-class) Axis Modules Attribute

2094-BMP5-S

2094-BM01-S

2094-BM02-S

2094-BM03-S

2094-BM05-S

Continuous Power Output, nom

1.8 kW

3.9 kW

6.6 kW

13.5 kW

22.0 kW

Table 22 - Kinetix 6000M (400V-class) IPIM Module

52

Attribute

2094-SEPM-B24-S

Continuous Power Output, nom

15.0 kW

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 53

Mount the Kinetix 6000 Drive System

Chapter 3

Figure 22 - Module Mounting Order Example Highest Power Utilization Integrated Axis Module 2094-BC02-M02-x

IPIM Module 2094-SEPM-B24-S

Lowest Power Utilization

Axis Module 2094-BM02-x

IMPORTANT

Axis Module 2094-BM02-x

Axis Module 2094-BM01-x

Axis Module 2094-BM01-x

Shunt Module 2094-BSP2

Slot-filler Module 2094-PRF

The IAM module must be positioned in the leftmost slot of the power rail. Position your AM/IPIM modules, shunt module, and slot-filler modules to the right of the IAM module. The shunt module must be installed to the right of the last AM/IPIM module. Only slotfiller modules can be installed to the right of the shunt module. Do not mount the shunt module on power rails with a follower IAM module. Common-bus follower IAM modules disable the internal, rail mounted, and external shunt modules. SHOCK HAZARD: To avoid personal injury due to electrical shock, place a 2094-PRF slot-filler module in all empty slots on the power rail. Any power rail connector without a module installed disables the Bulletin 2094 system; however, control power is still present.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

53

Page 54

Chapter 3

Mount the Kinetix 6000 Drive System

Mount Modules on the Power Rail

Follow these steps to mount the IAM, AM, IPIM, shunt, and slot-filler modules. TIP

All modules mount to the power rail by using the same technique; however, only the IAM module is used in the examples.

1. Remove the protective covers from the power rail connectors. IMPORTANT

The IAM module must be positioned in the leftmost slot of the power rail. Position your axis modules, shunt module, and slot-filler modules to the right of the IAM module.

2. Determine the next available slot and module for mounting. ATTENTION: To avoid damage to the pins on the back of each IAM, AM, IPIM, shunt, and slot-filler module and to make sure that module pins mate properly with the power rail, hang modules as shown in step 3 through step 6. The power rail must be mounted vertically on the panel before hanging modules on the power rail. Do not mount modules if the power rail is horizontal. 3. Hang the mounting bracket from the slot on the power rail. Mounting Bracket

Power Rail Slot Slots for additional axis modules, shunt module, or slot-filler modules.

Power Rail

54

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Kinetix 6000 IAM, AM, IPIM, Shunt, or Slot-filler Module (IAM module is shown)

Page 55

Mount the Kinetix 6000 Drive System

Chapter 3

4. Pivot module downward and align the guide pins on the power rail with the guide pin holes in the back of the module. Pivot module downward and align with guide pins.

Guide Pin Holes

Guide Pins

Power rail (side view) in upright vertical position.

Kinetix 6000 IAM, AM, IPIM, Shunt, or Slot-filler Module, Side View (IAM module is shown)

Kinetix 6000 IAM, AM, IPIM, Shunt, or Slot-filler Module, Rear View (IAM module is shown)

TIP

The IAM module can have two or three power rail connectors and guide pins, the AM module can have one or two, all other modules have one.

5. Gently push the module against the power rail connectors and into the final mounting position.

Bracket secured in slot.

Kinetix 6000 IAM, AM, IPIM, Shunt, or Slot-filler Module (IAM module is shown)

Power Rail

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

55

Page 56

Chapter 3

Mount the Kinetix 6000 Drive System

6. Use 2.26 N•m (20 lb•in) torque to tighten the mounting screws.

Bottom front view of single-wide AM, IPIM, shunt, or slot-filler module (AM module is shown).

Bottom front view of double-wide IAM or AM module (AM module is shown). Mounting Screws

IMPORTANT

There are two mounting screws when mounting 2094-AC32-M05-x, 2094-BC04-M03-x, and 2094-BC07-M05-x (double-wide) IAM modules, and 2094-BM03-x and 2094-BM05-x (double-wide) AM modules.

Repeat step 1 through step 6 for each AM, IPIM, shunt, or slot-filler module in your Bulletin 2094 drive system