Page 66
Chapter 4
Connector Data and Feature Descriptions
IAM and AM Motor Power and Brake Connector Pinout Table 35 - Motor Power Connector MP Pin
Description
4
Chassis ground
3
Signal
W
2
Three-phase motor power
1
V U
IMPORTANT
Combined motor-power cable length for all axes on the same DC bus must not exceed 240 m (787 ft) with 460V systems or 160 m (525 ft) with 230V systems. Drive-to-motor power cables must not exceed 90 m (295.5 ft). System performance was tested at these cable length specifications. These limitations also apply when meeting CE requirements.
Table 36 - Motor Brake/Resistive Brake Connector BC Pin 6 5
Motor brake connections
Signal MBRKMBRK+
4
Motor brake common
COM
3
+24V brake input power (from LIM module or customer supplied)
PWR
2
RBM module connections (from RBM module and safety string)
DBRK-
1
66
Description
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
DBRK+
Page 67
Connector Data and Feature Descriptions
Control Signal Specifications
Chapter 4
This section provides a description of the Kinetix 6000 drive I/O (IOD), communication, contactor enable (CED), brake (BC), and control power (CPD) connectors.
Digital Inputs Two fast registration inputs and four other inputs are available for the machine interface on the IAM module and AM module. Each IAM and AM module supplies 24V DC @ 250 mA for the purpose of registration, home, enable, over-travel positive, and over-travel negative inputs. These are sinking inputs that require a sourcing device. A 24V DC power and common connection is provided for each input. IMPORTANT
To improve registration input EMC performance, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.
IMPORTANT
Over-travel limit input devices must be normally closed.
Table 37 - Understanding Digital Inputs IOD Pin
Signal
Description
Capture Time
Edge/Level Sensitive
IOD-2
ENABLE
Optically isolated, single-ended active high signal. Current loading is nominally 10 mA. A 24V DC input is applied to this terminal to enable each axis.
20 ms
Level
IOD-5
HOME
Optically isolated, single-ended active high signal. Current loading is nominally 10 mA. Home switch (normally open contact) inputs for each axis require 24V DC (nominal).
20 ms
Level
IOD-14 IOD-17
REG1 REG2
Fast registration inputs are required to inform the motor interface to capture the positional information with less than 3 µs uncertainty. Optically isolated, single-ended active high signal. 500 ns Current loading is nominally 10 mA. A 24V DC input is applied to this terminal to enable each axis.
Edge
IOD-8 IOD-11
OT+ OT-
Overtravel detection is available as an optically isolated, single-ended active high signal. Current loading is nominally 10 mA per input. The pos/neg limit switch (normally closed contact) inputs for each axis require 24V DC (nominal).
Level
30 ms
Table 38 - Digital Input Specifications Parameter
Description
Min
Max
On-state voltage
Voltage applied to the input, with respect to IOCOM, to guarantee an on-state.
ENABLE, HOME, and OT+/OT-
10.8V
26.4V
REG1 and REG2
21.6V
26.4V
On-state current
Current flow to guarantee an on-state.
3.0 mA
10.0 mA
Off-state voltage
Voltage applied to the input, with respect to IOCOM, to guarantee an off-state.
-1.0V
3.0V
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
67
Page 68
Chapter 4
Connector Data and Feature Descriptions
Figure 29 - Enable, Home, and Overtravel Digital Input Circuits 24V DC I/O SUPPLY (1)
IOD-1, -4, -7, -10
INPUT (2)
IOD-2, -5, -8, -11
VCC 3k Ω 0.1 μF
IO_COM
CTRL_INPUT
511 Ω
IOD-3, -6, -9, -12
1k Ω Kinetix 6000 IAM/AM Module
Customer-supplied Input Device
(1) 24V DC source (range) = 21.6V - 26.4V (supplied by drive, not to exceed 250 mA total). (2) Maximum current input = 10 mA.
Figure 30 - Registration Digital Input Circuits IOD-13, -16
+24V DC
I/O SUPPLY VCC INPUT
IOD-14, -17 1k Ω
3k Ω 0.001 μF IO_COM Customer-supplied Registration Input Device
511 Ω
REG_INPUT HCPL-0631
IOD-15, -18 Kinetix 6000 IAM/AM Module
Sercos Communication Specifications The Rx and Tx Sercos connectors are provided on the Kinetix 6000 IAM and AM module for communication with the Logix5000 controller. Attribute
Value
Data rates
4 and 8 Mbps, selectable via DIP switch (1)
Light intensity
Low power or high power, selectable via DIP switch
Cyclic update period
500 μs, min
Node addresses
01…99 (2)
(1) The Kinetix 6000M IDM system supports only 8 Mbps and is hardwired for this setting. (2) Node address assignments begin with the IAM module. Node addresses for additional axes on the same power rail are assigned by incrementing from left to right (starting with the IAM module address). Each IDM unit has it’s own node address switches and can be set to any valid address. However, node addresses for the IAM and AM modules on the power rail and for IDM units must be unique.
68
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 69
Connector Data and Feature Descriptions
Chapter 4
Analog Outputs The IAM and AM modules include two analog outputs (IOD-23 and IOD-25) that you can configure through software to represent drive variables. Figure 31 - Analog Output Circuit Kinetix 6000 IAM/AM Module
Oscilloscope
CH1
DAC
(second channel not shown)
CH2
IMPORTANT
Output values can vary during powerup until the specified power supply voltage is reached.
Table 39 - Analog Output Specifications Parameter
Description
Min
Max
Resolution
Number of states that the output signal is divided into, which is 2 (to the number of bits).
–
±11 bits
Output current
Current capability of the output.
0
+2 mA
2094-xCxx-Mxx and 2094-xMxx drives
0
+5V
2094-xCxx-Mxx-S and 2094-xMxx-S drives
0
+10V
Output signal range
Range of the output voltage.
Offset error
Deviation when the output is expected to be at 0V.
–
1 mV
Bandwidth
Frequency response of the analog output
DC
7.2k Hz (3 db)
Table 40 - Linear Scaling Specifications Drive Cat. No.
2094-xCxx-Mxx or 2094-xMxx
2094-xCxx-Mxx-S or 2094-xMxx-S
Speed rpm
Value V DC
Torque %
10,000
5.0
1000
0
2.5
0
-10,000
0
-1000
10,000
10.0
1000
0
5.0
0
-10,000
0
-1000
For configuration/set up of the analog outputs, refer to Configure Drive Parameters and System Variables beginning on page 162.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
69
Page 70
Chapter 4
Connector Data and Feature Descriptions
Contactor Enable Relay Contactor enable is a relay-driven contact used in the three-phase powerenable control string to protect the drive electronics during certain fault conditions. It is capable of handling 120V AC or 24V DC at 1 A or less. Contactor enable is a function of the converter and is not available in the axis modules. An active state indicates the drive is operational and does not have a fault. ATTENTION: Wiring the contactor enable relay is required. To avoid personal injury or damage to the drive, wire the contactor enable relay into your three-phase power-enable control string so that: • three-phase power is removed from the drive in the event of shutdown fault conditions. • drive operation is prevented when the power rail is not fully populated. • control power is applied to the drive prior to three-phase power. Refer to IAM Module (without LIM module) on page 192 for a wiring example. IMPORTANT
All power rail slots must have a module installed or the contactor enable relay does not close.
Figure 32 - Contactor Enable Relay Circuit CONT EN+
Normally Open Relay CONT EN-
Kinetix 6000 IAM Module
Table 41 - Contactor Enable Relay Output Specifications
70
Attribute
Value
Min
Max
On-state current
Current flow when the relay is closed
–
1A
On-state resistance
Contact resistance when the relay is closed
–
1Ω
Off-state voltage
Voltage across the contacts when the relay is open
–
120V AC or 24V DC
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 71
Connector Data and Feature Descriptions
Chapter 4
This section provides a description of the Kinetix 6000 brake relay (BC), input power (IPD), motor power (MP), and control power (CPD) connectors.
Power and Relay Specifications
Motor/Resistive Brake Relay The brake option is a spring-set holding brake that releases when voltage is applied to the brake coil in the motor. The customer-supplied 24V power supply drives the brake output through a solid-state relay (series C) and mechanical relays (series A and B). The solid-state brake driver circuit provides the following: • Brake current-overload protection • Brake over-voltage protection Two connections are required for the (customer-supplied) motor/resistive brake input power (BC-3 and BC-4) and two connections each for the motor and resistive brake output, as shown in Figure 33. Wiring is consistent with all series releases. Connections are rated for +24V and current as shown in Table 42. Table 42 - Brake Relay Output Specifications Attribute
Description
Brake Current Value, max
IAM/AM Module
Series A
2094-AC05-Mxx,-x 2094-AC09-M02-x, 2094-AMP5-x, 2094-AM01-x, 2094-AM02-x
On-state current (1)
Current flow when the relay is closed
2094-BC01-Mxx-x, 2094-BC02-M02-x, 2094-BMP5-x, 2094-BM01-x, 2094-BM02-x
Series B
Series C
N/A 1.0 A 3.0 A 3.0 A
2094-AC16-M03-x, 2094-AC32-M05-x, 2094-AM03-x, 2094-AM05-x
1.3 A
N/A
2094-BC04-M03-x, 2094-BC07-M05-x, 2094-BM03-x, 2094-BM05-x
3.0 A
3.0 A
On-state resistance
Contact resistance when the relay is closed
1Ω
Off-state voltage
Voltage across the contacts when the relay is open
30V
(1) For motors requiring more than the maximum current specified, a relay must be added.
Figure 33 - Brake Relay Circuit (series C) 24V PWR (BC-3)
24V PWR (BC-3)
MBRK+ (BC-5)
Control Board
FQB22P10
(1)
DBRK+ (BC-1) FQB22P10
Control Board
(1) DBRK– (BC-2)
MBRK– (BC-6)
Motor Brake Circuitry Kinetix 6000 IAM/AM Module
Resistive Brake Module Circuitry Kinetix 6000 IAM/AM Module 24V COM (BC-4)
24V COM (BC-4)
(1) Noise suppression device.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
71
Page 72
Chapter 4
Connector Data and Feature Descriptions
IMPORTANT
Motor parking-brake switching frequency must not exceed 10 cycles/min.
Control of the relay to release the motor brake (BC-5 and BC-6) is configurable in the Logix Designer application (refer to Configure Axis Properties on page 151). An active signal releases the motor brake. Turn-on and turn-off delays are specified by the BrakeEngageDelayTime and BrakeReleaseDelayTime settings. Refer to Controlling a Brake Example on page 213 for brake coil currents. IMPORTANT
Holding brakes that are available on Allen-Bradley rotary motors are designed to hold a motor shaft at 0 rpm for up to the rated brakeholding torque, not to stop the rotation of the motor shaft, or be used as a safety device. You must command the servo drive to 0 rpm and engage the brake only after verifying that the motor shaft is at 0 rpm.
The resistive brake relay (BC-1 and BC-2) controls the resistive brake module (RBM) contactor. The RBM module is wired between the drive and motor by using an internal contactor to switch the motor between the drive and a resistive load. The RBM module contact delay is the time it takes to fully close the contactor across the motor power input lines, and must be configured in the software. Refer to RBM Module Interconnect Diagrams beginning on page 269 for wiring examples. These steps provide one method you can use to control a brake. 1. Wire the mechanical brake according to the appropriate interconnect diagram in Appendix A beginning on page 187. 2. Enter the BrakeEngageDelay and BrakeReleaseDelay times in the Logix Designer application. Refer to Axis Properties>Parameter List. The delay times must be from the appropriate motor family brake specifications table in the Kinetix Rotary Motion Specifications Technical Data, publication KNXTD001. 3. Use the motion instruction Motion Axis Stop (MAS) to decelerate the servo motor to 0 rpm. 4. Use the motion instruction Motion Servo Off (MSF) to engage the brake and disable drive.
72
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 73
Connector Data and Feature Descriptions
Chapter 4
Input Power Cycle Capability The power cycle capability is inversely proportional to the system capacitance (including DC bus follower), but cannot exceed 2 contactor cycles per minute with up to 4 axes or 1 contactor cycle per minute with 5…8 axes. The cycle capability also depends on the converter power rating and the total system capacitance. Refer to Appendix C on page 227 to calculate total system capacitance. Table 43 - Maximum Input Power Cycling Specifications (230V) Attribute
2094-AC05-MP5-S
Main AC input power cycling (cycles per minute for 10,000 μf)
0.69
2094-AC05-M01-S
2094-AC09-M02-S
2094-AC16-M03-S
2094-AC32-M05-S
4.30
Table 44 - Maximum Input Power Cycling Specifications (460V) Attribute
2094-BC01-MP5-S
Main AC input power cycling (cycles per minute for 10,000 μf)
0.12
2094-BC01-M01-S
2094-BC02-M02-S
2094-BC04-M03-S
2094-BC07-M05-S
0.52
2.15
4.30
For example, in a 4 axis system with a 2094-BC02-M02-S IAM module and 2,000 µF total capacitance, the calculated capability is 0.52 x 10,000/2000 = 2.6 cycles per minute. However, this value is reduced to 2.0 by the 4 axes per system limitation.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
73
Page 74
Chapter 4
Connector Data and Feature Descriptions
Peak Enhancement Specifications Drives that support the Peak-enhanced mode have the capability of increasing the maximum inverter peak current to achieve greater overload performance. IMPORTANT
The peak enhancement feature requires the use of RSLogix 5000® software or the Logix Designer application, and drive firmware as specified in Table 45.
Table 45 - Peak Enhancement Software and Firmware Requirements IAM Module Cat. No.
AM Module Cat. No.
RSLogix 5000 Software Version
Kinetix 6000 Drive Firmware Revision
2094-BC01-MP5-S
2094-BMP5-S
16 or later
1.111 or later
2094-BC01-M01-S
2094-BM01-S
16 or later
1.111 or later
2094-BC02-M02-S
2094-BM02-S
16 or later
1.111 or later
2094-BC04-M03-S
2094-BM03-S
17 or later
1.117 or later
2094-BC07-M05-S
2094-BM05-S
17 or later
1.117 or later
Table 46 - Kinetix 6000 Inverter Peak Overload Support Kinetix 6000 Drives Cat. No.
Module
Safe Torque- Series A off Drive
Series B and C
2094-BCxx-Mxx
IAM
2094-BMxx
AM
Non Safe Torque-off
Standard
N/A
2094-BCxx-Mxx-S
IAM
2094-BMxx-S
AM
Safe Torque-off
Standard
Standard or Peak Enhanced (1)
(1) Standard mode is enabled by default to preserve backward compatibility, but you can enable the Peak-enhanced mode to achieve increased peak current performance.
Table 47 - Kinetix 6000 Peak Current Ratings
74
Peak Inverter Current Rating
Peak Converter Current Rating
IAM/AM Module Cat. No.
Standard
Peak Enhanced
Series A
Series B and C
2094-BC01-MP5-S
150%
250%
200%
250%
2094-BC01-M01-S
150%
250%
200%
250%
2094-BC02-M02-S
150%
250%
200%
250%
2094-BC04-M03-S
150%
250%
200%
250%
2094-BC07-M05-S
150%
200%
200%
300%
2094-BMP5-S
150%
250%
N/A
N/A
2094-BM01-S
150%
250%
N/A
N/A
2094-BM02-S
150%
250%
N/A
N/A
2094-BM03-S
150%
250%
N/A
N/A
2094-BM05-S
150%
200%
N/A
N/A
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017