Page 155

Appendix B Discrete Bit Results

Discrete Bit Outputs (cont’d)

Note: When using the backplane, don’t write directly to word 2. Write to word 1023. The CVIM will copy the data from word 1023 to word 2. Note: When communicating with a device through the Pyramid Integrator backplane, CVIM module results are posted in shared memory immediately after processing. When communicating with a device through the other ports, results are only available at the end of the inspection program. Table B.3 Discrete Bit Outputs

Word #

PI Backplane

Bit #

RS–232 and Remote I/O

D E C I M A L

O C T A L

PI

PLC

Definition

2

0

0–7

0–7

Not Used

2

0

8

10

Lock Request

Usage

Notes

0 = No Change 1 = Lock

Do not set bits 8 and 9 at the same time. If you set both bits, the CVIM will be unlocked. You must reset this bit to 0, then back to 1 to repeat a lock request.

2

0

9

11

Unlock Request

0 = No Change 1 = Unlock

You must reset this bit to 0, then back to 1 to repeat an unlock request.

2

0

10

12

Host Trigger Toolset 1

0 = No Trigger 1 = Trigger

You must reset this bit to 0, then back to 1 to repeat a trigger request.

2

0

11

13

Host Trigger Toolset 2

0 = No Trigger 1 = Trigger

You must reset this bit to 0, then back to 1 to repeat a trigger request.

2

0

12

14

Light Pen Request

0 = No Request 1 = Request

Bit 12 commands are specified in: Output words 1 and 6 (Remote I/O) Output words 3 and 8 (Backplane) You must reset bit to 0, then back to 1 to repeat a light pen request.

B–10

Page 156

Appendix B Discrete Bit Results

Table B.3 Discrete Bit Outputs Word #

PI Backplane

2

Bit #

RS–232 and Remote I/O

0

D E C I M A L

O C T A L

PI

PLC

13

15

Definition

Usage

I/O Request

0 = No Request 1 = Request

Notes

Bit 13 commands are specified in: Output words 2, 4, and 5 (Remote I/O) Output words 4, 6, and 7 (Backplane) You must reset bit to 0, then back to 1 to repeat an I/O request.

2

0

14

16

Configuration Move

0 = No Request 1 = Request

Bit 14 commands are specified in: Output word 2 (Remote I/O) Output word 4 (Backplane) You must reset bit to 0, then back to 1 to repeat a configuration move request.

2

0

15

17

Not Used

B–11

Page 157

Appendix B Discrete Bit Results

Discrete Bit Outputs (cont’d) Table B.3 Discrete Bit Outputs Word#

PI Backplane

3

Bit#

RS–232 and Remote I/O

1

D E C I M A L

O C T A L

PI

PLC

0–7

0–7

Definition

Usage

Runtime Display Control

00000000 = No Change 00000001 = Display Image Only 00000010 = Display Failed Tool 00000100 = Display All Tools 00001000 = Display I/O Page 00010000 = Display Results Page 00100000 = Display Statistics 1 Page 01000000 = Display Statistic 2 Page

B–12

Notes

Page 158

Appendix B Discrete Bit Results

Table B.3 Discrete Bit Outputs Word#

PI Backplane

3

Bit#

RS–232 and Remote I/O

1

D E C I M A L

O C T A L

PI

PLC

8 – 15

10 – 17

Definition

Usage

Freeze on Reject Control

00000000 = No Change

Notes

00000001 = Go On Reject 00000010 = Freeze First Reject 00000100 = Freeze All Rejects 00001000 = Freeze Next Image 00010000 = Halt On Reject 4

2

N/A

0–3

Toolset Flag Select

Not Applicable to Backplane

0000 = Not Valid

Bits 0 – 3 control which set of toolset results are assigned to discrete input words 1 through 7.

0001 = Toolset 1 0010 = Toolset 2

4

2

4–5

4–5

Discrete I/O Control

00 = No Change

Bits 4 through 7 refer to the local I/O module (Catalog Number 1771–JMB).

01 = Disable Outputs 10 = Enable Outputs 4

2

6–7

6–7

Forced I/O Control

00 = No Change 01 = Disable Forces 10 = Enable Forces

Bits 6 and 7 act upon the bitmap you set up in words: 4 and 5 (Remote I/O) 6 and 7 (Backplane)

B–13

Page 159

Appendix B Discrete Bit Results

Discrete Bit Outputs (cont’d) Table B.3 Discrete Bit Outputs Word#

PI Backplane

4

Bit#

RS–232 and Remote I/O

2

D E C I M A L

O C T A L

PI

PLC

8 – 11

10 – 13

Definition

Usage

Configuration Move Control

0000 = No Request

Notes

0001 = EEPROM to RAM 0010 = RAM to EEPROM 0100 = RAM Card to RAM 1000 = RAM to RAM Card 4

2

12 – 15

14 – 17

RAM Card Index

0000 = RAM Card Configuration 1 1111 = RAM Card Configuration 16

B–14

Bits 12 through 15 are numeric fields which specify RAM card locations 1 through 16.

Page 160

Appendix B Discrete Bit Results

Table B.3 Discrete Bit Outputs Word #

PI Backplane

5

Bit #

RS–232 and Remote I/O

3

D E C I M A L

O C T A L

PI

PLC

N/A

0–2

Definition

Usage

Block Transfer Type

000 = Invalid Request

Reference only. Not used for Backplane.

001 = Results Block 010 = Configuration Block 100 = Template Block 101 = Statistics Block – See Notes

Notes

This word only applies to Remote I/O interface. To send programmable block transfer to the CVIM, set bits 0, 1, and 2 to equal 111 and then send a block transfer write. No other bits (last block, toolset, or block number) need to be sent. After sending a configuration block or template block to the CVIM, you should check the condition of the configuration fault bit (Word 0, Discrete Bit Inputs) To send programmable statistics , set bits 0, 1, and 2 to equal 101 and then send a block transfer write to the CVIM. No other bits (last block , toolset, or block number) need to be sent.

111 = Programmable Block Transfer – See Notes 5

3

N/A

3

Last Block Flag

Reference only. Not used for Backplane. 5

Reference only. Not used for Backplane.

Bit 3 only applies to block transfer writes.

1 = Last Block 3

N/A

4–7

Toolset Request

0000 = No Toolset 0001 = Toolset 1 0010 = Toolset 2

Bits 4 through 7 only apply to results block.

3

N/A

10 – 17

Block Transfer Block Number

0 = Invalid Number See Notes

Results block numbers may be from 1 to 4. Configuration block numbers may be from 1 to 136. Template block numbers may be from 1 to 255 (variable).

Reference only. Not used for Backplane. 5

0 = Not Last Block

B–15

Page 161

Appendix B Discrete Bit Results

Discrete Bit Outputs (cont’d) Table B.3 Discrete Bit Outputs Word#

PI Backplane

B–16

Bit#

RS–232 and Remote I/O

D E C I M A L

O C T A L

PI

PLC

Definition

Usage

Notes

6

4

0

0

Local I/O Output 1 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

1

1

Local I/O Output 2 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

2

2

Local I/O Output 3 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

3

3

Local I/O Output 4 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

4

4

Local I/O Output 5 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

5

5

Local I/O Output 6 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

6

6

Local I/O Output 7 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

7

7

Local I/O Output 8 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

8

10

Local I/O Output 9 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

9

11

Local I/O Output 10 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

10

12

Local I/O Output 11 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

11

13

Local I/O Output 12 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

12

14

Local I/O Output 13 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

13

15

Local I/O Output 14 Force ON

0 = No Force 1 = Force On

Refers to Catalog Number 1771–JMB Local I/O Board.

6

4

14 – 15

16 – 17

Not Used

Page 162

Appendix B Discrete Bit Results

Table B.3 Discrete Bit Outputs Word#

PI Backplane

Bit#

RS–232 and Remote I/O

D E C I M A L

O C T A L

PI

PLC

Definition

Usage

Notes

7

5

0

0

Local I/O Output 1 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

1

1

Local I/O Output 2 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

2

2

Local I/O Output 3 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

3

3

Local I/O Output 4 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

4

4

Local I/O Output 5 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

5

5

Local I/O Output 6 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

6

6

Local I/O Output 7 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

7

7

Local I/O Output 8 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

8

10

Local I/O Output 9 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

9

11

Local I/O Output 10 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

10

12

Local I/O Output 11 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

11

13

Local I/O Output 12 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

12

14

Local I/O Output 13 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

13

15

Local I/O Output 14 Force OFF

0 = No Force 1 = Force Off

Refers to Catalog Number 1771–JMB Local I/O Board.

7

5

14 – 15

16 – 17

Not Used

B–17

Page 163

Appendix B Discrete Bit Results

Discrete Bit Outputs (cont’d) Table B.3 Discrete Bit Outputs Word#

PI Backplane

B–18

Bit#

RS–232 and Remote I/O

D E C I M A L

O C T A L

PI

PLC

Definition

Usage

Notes

8

6

0–1

0–1

Toolset Display Control

8

6

2

2

Not Used

8

6

3

3

Resume Control

0 = No Change 1 = Resume

Use in conjunction with light pen request: Word 0 bit 12 (Remote) Word 2 bit 12 (Backplane)

8

6

4–5

4–5

Page Control

00 = No Change 01 = Page Up 10 = Page Down

Use in conjunction with light pen request: Word 0 bit 12 (Remote) Word 2 bit 12 (Backplane)

8

6

6

6

Reset Statistics

0 = No Change 1 = Reset

Use in conjunction with light pen request: Word 0 bit 12 (Remote) Word 2 bit 12 (Backplane)

8

6

7

7

Reset Counters

0 = No Change 1 = Reset

Use in conjunction with light pen request: Word 0 bit 12 (Remote) Word 2 bit 12 (Backplane)

8

6

8 – 15

10 – 17

Not Used

00 = No Change 01 = Display Toolset 1 10 = Display Toolset 2