Page 91
Relays and Timer Specifications
700-PS Industrial Relays
Specifications Bulletin 700-PS Operation The timer must be energized continuously (L1-L2). ON-Delay: When the initiating contact closes, timing begins. At time-out, the output contact closes. OFF-Delay: When the initiating contact closes, the output contact closes instantly. When the initiating contact re-opens, timing begins. At time-out, the output contact re-opens.
Typical Wiring Diagram§
External Initiating Contact (See Attention)
Attention, To avoid damage to timer, do not switch any load in addition to timing relay at terminals S1–S2. Do not apply an external voltage to terminals S1–S2.
C1
Output Contact To Load § External Potentiometer units have R1, R2 terminals for connecting the potentiometer.
S1
S2
Type PS Timer C2
L1
L2
110/120V, 50/60 Hz
Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 700-PS
Cat. No. 700-N25
2 Mounting Screws with Springs
5.2 (13/64) 2 Mounting Slots
Bulletin 700-PS Timer Mounted on the Adapter Plate Cat. No. 700-N25 Approximate Shipping Wt. 0.45 kg (1 lb)
Rockwell Automation Publication 700-TD552A-EN-P
91
Page 92
700-PS Industrial Relays
Relays and Timer Specifications
160.6 max. (6-5/16)
164.7 max. (6-31/64)
700 Type P
700 Type R
700-PS Timer
700-PS Timer
Cat. No. 700-N26
Bulletin 700-PS Timer Mounted on a 4-Pole Bulletin 700-P or -PK, or 2-Pole Bulletin 700-PH Relay Approximate Shipping Wt. 1.02 kg (2.3 lb)
92
Bulletin 700-PS Timer Mounted on a 4-Pole Bulletin 700-R or -RM Relay Approximate Shipping Wt. 1.25 kg (2.8 lb)
Rockwell Automation Publication 700-TD552A-EN-P
Page 93
Relays and Timer Specifications
700-CF Control Relays
Assignment of Contacts Device Combinations in Accordance with IEC 60947-1 / -4-1 Auxiliary Contact Blocks
Control Relays 700-CF (AC and DC Control) 700-CF⊗220
700-CF⊗310
A1 13 21 31 43
A1 13 21
K1
Circuit Diagram
700-CF⊗400 A1 13 23 33 43
33 43
K1
K1
Control
A2 14 22 32 44
A2 14 22 34 44
A2 14 24 34 44
AC/DC
22E + 02E = 24Y
31E + 02E = 33Y
40E + 02E = 42Y
AC/DC
22E + 11E = 33Y
31E + 11E = 42Y
40E + 11E = 51Y
AC/DC
22E + 20E = 42Y
31E + 20E = 51Y
40E + 20E = 60Y
AC/DC
22E + 22E = 44Y
31E + 22E = 53Y
40E + 22E = 62Y
AC/DC
22E + 31E = 53Y
31E + 31E = 62Y
40E + 31E = 71Y
AC/DC
22E + 40E = 62Y
31E + 40E = 71Y
40E + 40E = 80Y
AC/DC
22E + L22E = L44Y
31E + L22E = L53Y
40E + L22E = L62Y
Front Mounting 51 61
100-FA02 52 62 53 61
100-FA11 54 62 53 63
100-FA20 54 64 53 61 71 83
100-FA22 54 62 72 84 53 61 73 83
100-FA31 54 62 74 84 53 63 73 83
100-FA40 54 64 74 84 53 61 75 87
100-FAL22 54 62 76 88
Control relay and auxiliary contact block AC/DC max. 4 N. C. 700-CF (DC conventional coils), vertical mounting, 60 °C ♦
700-CF (AC and DC electronic coils), vertical mounting, 60 °C♦
Cat. No. 700…
Max. N.O. Side Aux.
CF400 CF310
Max. N.C. Front Aux.
Max. N.O. Front + Side Aux.
Max. N.C. Front + Side Aux.
Max. N.O. + N.C. Front + Side Aux.
Cat. No. 700…
Max. N.O. Side Aux.
Max. N.C. Side Aux.
Max. N.O. Front Aux.
Max. N.C. Front Aux.
Max. N.O. Front + Side Aux.
Max. N.C. Front + Side Aux.
Max. N.O. + N.C. Front + Side Aux. 8
Max. N.C. Side Aux.
Max. N.O. Front Aux.
2
4
4
4
6
7
8
CF400
2
2
4
4Δ
6
5
2
4♣
4
4Δ
6
5
8
CF310
2
2
4
4Δ
6
5
8
CF220
4
4♣
4
2
8
5
8
CF220
2
2
4
2
6
4
8
CF040
2
2
4
0
6
2
6
♣ With no front auxiliary contacts installed. Otherwise 3 N.C. Maximum Δ With no side auxiliary contacts installed. Otherwise 3 N.C. Maximum ♦ For other operating conditions, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
Δ With no side auxiliary contacts installed. Otherwise 3 N.C. Maximum ♦ For other operating conditions, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
Rockwell Automation Publication 700-TD552A-EN-P
93
Page 94
700-CF Control Relays
Relays and Timer Specifications Cat. No. 100-JE
Cat. No. 100-JE12
Cat. No. 100-JE48
Electrical Input Voltage
24V DC
12V DC
48V DC
Input Voltage Range
18…30V DC
6…12V DC
35…48V DC 110…240V AC
Output Voltage
110…240V AC
110…240V AC
Power Consumption
0.1…0.4 W
0.02…0.12 W
0.2…0.5 W
Minimum Actuation
5V DC, 2 mA DC
5V DC, 2 mA DC
5V DC, 2 mA DC
Mechanical Finger Protection
IP20
IP20
IP20
Pickup Time
0…10 ms + pickup time of the contactor
0…10 ms + pickup time of the contactor
0…10 ms + pickup time of the contactor
Dropout Time
0…10 ms + dropout time 0…10 ms + dropout time 0…10 ms + dropout time of the contactor of the contactor of the contactor
Max. Cycles Per Second
Isolation/Breakdown Voltage
In: 50V, Out: 250V
In: 50V, Out: 250V
In: 50V, Out: 250V
4 kV
4 kV
4 kV
Rated Impulse Withstand Voltage Environmental Ambient Temperature Range
-25…60 °C
-25…60 °C
-25…60 °C
Storage Temperature Range
-50…+80 °C
-50…80 °C
-50…80 °C
100+ million ops
100+ million ops
100+ million ops
Operating Life
Construction 1 Wire
0.5…2.5 mm2
0.5…2.5 mm2
0.5…2.5 mm2
2 Wire
0.75…2.5 mm
2
2
0.75…2.5 mm
0.75…2.5 mm2
1 Wire
2
1.0…2.5 mm
2
1.0…2.5 mm
1.0…2.5 mm2
2 Wire
2
2
1.0…2.5 mm2
Flexible wire Wire Size Range Solid wire Solid and Stranded
1.0…2.5 mm
18…14 AWG
18…14 AWG
18…14 AWG
Tightening Torque
1…1.5 N•m/7…15 lb•in
1…1.5 N•m/7…15 lb•in
1…1.5 N•m/7…15 lb•in
Type of Light
LED
LED
LED
To consider the maximum operations/hour of the relays.
94
1.0…2.5 mm
Rockwell Automation Publication 700-TD552A-EN-P
Page 95
Relays and Timer Specifications
700-CF Control Relays
Coils AC Coil Code Q R J K KJ V W X Y KY KP D KD P S KG H L KL A F KF VA T KA I E N KN G B KB M C
50Hz, 12V, 24V, 32V 36V 42V 48V, 100V 110V, 120V 127V 200V, 200 - 220V, 220V 220 - 230V, 230 - 240V 240V, - - 380 - 400V, 400-415V 440V, 500V 550V
AC Voltages 60Hz 12V, 24V, - 36V, 48V, - 100 - 110V 120V, - - 200 - 220V 208V 208 - 240V, 240V 260V, - 277V, 347V 380V 440V, - 480V, - 600V
50/60Hz, - - - 24V, - - - 48V 100V, 110V, - 200V, - 200 - 230V, - 230V, - 240V, - - 400V, - 440V, - Cat. No. 700-CF TA006 TA404 TA013 TA407 TA855 TA481 TA410 TA482 TA414 TA860 TA861 TA473 TA856 TA425 TA428 TA862 TA049 TA296 TA864 TA474 TA441 TA851 TA440 TA480 TA858 TA065 TA067 TA071 TA863 TA457 TA475 TA859 TA479 TA476
DC Coil Code ZR ZQ DJ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT, - - - - - - - - - - - - - - - - - DC Voltages 9V 12V 24V Diode 24V 36V 48V 60V 64V 72V 80V 110V 115V 125V 220V 230V 250V, - - - - - - - - - - - - - - - - - Cat. No. 700-CF TA766 TA708 TA714M TA714 TA719 TA724 TA774 TA727 TA728 TA729 TA733 TA734 TA737 TA747 TA749 TA751, - - - - - - - - - - - - - - - - - Utilization Category Table from EN 60947-5-1 Verification of Making and Breaking Capacities of Switching Elements Under Normal Conditions Corresponding to the Utilization Categories‡ Normal Condition of Use Utilization Category
Make§
Number and Rate of Making and Breaking operations
Break§
I/Ie
U/Ue cos ψ
I/Ie
U/Ue cos ψ
No. operating cycles♣
Operating cycles per minute
AC-12♠
1
1
0.9
1
1
0.9
6050
6
0.05
AC-13♠
2
1
0.65
1
1
0.65
6050
6
0.05
ON time [s]♦
AC-14♠
6
1
0.3
1
1
0.3
6050
6
0.05
AC-15♠
10
1
0.3
1
1
0.3
6050
6
0.05
DC, - T0.95, - T0.95, - - DC-12
1
1
1 ms
1
1
1 ms
6050
6
0.05♦
DC-13
1
1
6 x PΔ
1
1
6 x PΔ
6050
6
0.05♦
DC-14♠
10
1
15 ms
1
1
15 ms
6050, 0.05♦
Ie Rated operational current, I Current to be made or broken Ue Rated operational voltage, U Voltage before make PUeIe Steady-state power consumption (W) T0.95 Time to reach 95% of the steady-state current (ms) ‡ See sub-clause 8.3.3.5.2. § For tolerances on test quantities, see sub-clause 8.3.2.2. ♣ The first 50 operating cycles shall be run at U/Ue=1.1 with the loads set at Ue. Δ The value “6 x P” results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, e.g., 6 x P= 300 W. ♦ The ON time shall be at least equal to T0.95. ♠ Where the break current differs from the make current value, the ON time refers to the make current value after which the current is reduced to the break current value for a suitable period e.g., 0.05 s.
Rockwell Automation Publication 700-TD552A-EN-P
95
Page 96
700-CF Control Relays
Relays and Timer Specifications
General Main Relay Cat. Nos. 700-CF, 700SCF
Front Mounted Main Relay Standard Cat. No. Auxiliary 700-CFB, 700SContacts CFB
Master Relay Cat. No. 700-CFM
Front Mounted Bifurcated Auxiliary Contacts
Side-mounted Auxiliary Contacts
Contact Ratings, NEMA
A600, P600
A600, Q600
A600, Q600
2 x A600, P600
A600, Q600
A600, Q600
Min. Contact Rating
17V, 10 mA
17V, 5 mA
8V, 5 mA, 5V, 3 mA
17V, 10 mA
24V
10 A
6A
3A
15 A
3A
6A
48V
10 A
6A
3A
15 A
3A
6A
120V
10 A
6A
3A
15 A
3A
6A
240V
10 A
5A
3A
15 A
3A
5A
400V
6A
3A
2A
7.5 A
2A
3A
480V/500V
2.5 A
1.6 A
1.2 A
5A
1.2 A
1.6 A
600V
1A
1A
0.7 A
2A
0.7 A
1A
690V
1A
1A
0.7 A
2A
0.7 A
1A
Ith
20 A 10 A
10 A
20 A
10 A
10 A
6A
6A
20 A
6A
6A
Contact Ratings, IEC AC-15 (solenoids, contactors) at rated voltage IEC 60947-5-1
40 °C AC-12 (Control of resistive loads) IEC 60947-5-1 60 °C
DC-12 Switching DC Loads L/R < 1ms, Resistive Loads IEC 60947-5-1
DC-13 IEC 60947-5-1, Solenoids and contactors
230V
8 kW
400V
14 kW
690V
24 kW
Ith
20 A
230V
8 kW
400V
14 kW
690V
24 kW
24V
15 A
10 A
6A
20 A
6A
6A
48V
10 A
9A
3.2 A
20 A
3.2 A
3.2 A
110V
6A
3.5 A
1A
8A
1A
1A
220V
1A
0.7 A
0.5 A
1.5 A
0.5 A
0.5 A
440V
0.4 A
0.2 A
0.2 A
0.4 A
0.2 A
0.2 A
24V
5A
5A
2.5 A
5A
2.5 A
5A
48V
3A
3A
1.5 A
3A
1.5 A
2.5 A
110V
1.2 A
1.2 A
0.6 A
1.2 A
0.6 A
0.68 A
220V
0.6 A
0.6 A
0.3 A
0.6 A
0.3 A
0.32 A
440V
0.3 A
0.15 A
0.15 A
0.3 A
0.15 A
0.15 A
State of N.C. Contacts if N.O. contact welds
Location of welded N.O. contacts
Main
Front aux.
Side aux.
Main
Open
Open
Front aux.
Open
Open, Mechanically Linked Contacts‡
Side mounted auxiliary contacts provide “mirror contact” performance with main poles only. ‡ Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).
Cat. No. 700-CF
Aux./Pneu matic Timer Contact (Frontmounted)
[Mil]
15
AC-15 (240V, 3 A)
[Mil]
AC Coil
[g]
Mechanical Life Electrical Life Weight
DC Switching Ratings for 700-CF Main Poles in Series (Resistive Load at 60 °C) 1 pole
2 poles
3 poles
24/48V
15/10 A
25 A
25 A
125V
6A
25 A
25 A
5
220V
1.5 A
8A
25 A
1.5
1.5
440V
0.4 A
1A
3A
390, 2 x A4
2 x A4
1.5…6
0.5…2.5 0.75…2.5
Terminal Cross-Sections Terminal Type Terminal Size per IEC60 947-1 Solid/ Stranded
1 Conductor
[mm ]
♣
2 Conductor
[mm2]
1.5…6
Max. Wire Size per UL/CSA
[AWG]
16…10
18…14
Tightening Torque
[lb·in]
13.3…17.7
8.9…13.3
Tightening Torque
[N·m]
1.5…2.0
1…1.5
2
♣ For 16 or more strands, end ferrule is required.
96
Rockwell Automation Publication 700-TD552A-EN-P
Page 97
Relays and Timer Specifications
700-CF Control Relays
Control Circuit
General Cat. No. 700-CF
Cat. No. 700-CF
Operating Voltage AC 50/60 Hz DC
DC (electronic EQ, EW) DC (electronic EY) DC (electronic ED) DC (electronic EA)
Rated Insulation Voltage Ui
Pickup
[x Us]
0.85…1.1
IEC
690V
Dropout
[x Us]
0.3…0.6
UL; CSA
600V
Pickup
[x Us]
0.8…1.1
Rated Impulse StrengthUimp
6 kV
Dropout
[x Us]
0.1…0.6
2500V
Pickup
[x Us]
0.7...1.25
High Test Voltage 1 minute (per IEC 60947-4)
Dropout
[x Us]
0.3...0.4
DC (conventional) DC (electronic EQ, EJ) DC (electronic EY) DC (electronic ED) DC (electronic EA)
115, 230, 400, 500, 690V
DC
24, 48, 110, 220, 440V
Pickup
[x Us]
0.8...1.25
Dropout
[x Us]
0.3...0.4
Pickup
[x Us]
0.7...1.12 ‡
Dropout
[x Us]
0.3...0.4
Pickup
[x Us]
0.8...1.1
Storage
–55…+80 °C (–67…176 °F)
Dropout
[x Us]
0.3...0.4
Operation at nominal current
–25…+60 °C (–13…140 °F)
15% current reduction for AC-12 at > 60 °C
–25…+70 °C (–13…158 °F)
Corrosion Resistance humid-alternating climate, cyclic, per IEC 60068-2-30 and DIN 50 016, 56 cycles
Altitude
2000 m above mean sea level, per IEC60 947-4
Coil Consumption AC 50/60 Hz
Rated Voltage Ue AC
Inrush
[VA]
75
Sealed
[VA/W]
9.5/2.7
Inrush
[W]
7.7
Sealed
[W]
6.3
Inrush (avg./ peak)
[W]
10/17
Sealed
[W]
1.7
Inrush (avg./ peak)
[W]
10/17
Sealed
[W]
1.9
Inrush (avg./ peak)
[W]
12/19
Short-Circuit Protection gG Fuse 20 A Rated Frequency
50/60 Hz, DC
Ambient Temperature
Type of Protection
Sealed
[W]
2.1
Inrush (avg./ peak)
[W]
14/22
Sealed
[W]
3.0
IP2X (IEC 60529 and DIN 40050)
in connected state
Shock Resistance
IEC 60068-2: Half sinusoidal shock 11 ms, 30 G (in 3 directions)
Vibration Resistance
IEC 60068-2: Static >2 G, in normal position no malfunction <5 G
Operating Times Pickup Time
[ms]
15…30
Dropout Time
[ms]
10…60
Pickup Time
[ms]
40…70
Dropout Time
[ms]
7…15
With integrated diode
Opening Delay
[ms]
14...20
With external diode
Opening Delay
[ms]
70...125
Closing Delay
[ms]
25…50
Opening Delay
[ms]
27...45
AC 50/60 Hz DC (conventional)
DC (electronicEQ, EJ) Min OFF time
[ms]
50
Max. ripple DC (electronicEY, ED, EA)
± 15% Closing Delay
[ms]
25...50
Opening Delay
[ms]
23...33
Min OFF time
[ms]
50
Max. ripple
± 15% Latch Attachment Release, 100-FL
Coil Consumption
AC
[VA/W]
DC
[W]
25
[min./max]
0.03…15 s
Contact Signal Duration
45/40
Timing Attachment Reset Time, 100ETA, 100-ETB Repeat Accuracy at min. time setting
[ms] at max. time setting
[ms]
10 70 ± 10%
For 9V DC, code ZR, use operating voltage 0.65…1.3 x Us. For 24V DC, code ZJ, DJ, or EJ use operating voltage 0.7…1.25 x Us. ‡ At 110V DC, coil code ED has an operating voltage range of 0.7...1.25 x Us.
Rockwell Automation Publication 700-TD552A-EN-P
97
Page 98
700-CF Control Relays
Relays and Timer Specifications
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended for manufacturing purposes.
Mounting Position AC and DC Control Relay with DC Electronic Coil
Front View be mounted to 35 mm EN 50 022 DIN Rail.
Side View
DC Control Relay
Side View
Front View AC and DC Control Relays with 12V or 24V DC Electronic Coil Type a b c c1 c2
700-CF, -CFB, -CFM
45 (1-25/32)
81 (3-3/16)
80.5 (3-11/64)
75.5 (3-3/32)
6 (1/4)
Ød 2 screws 4.5 (3/16)
d1 d2
60 (2-23/64)
35 (1-25/64)
d1 d2
60 (2-23/64)
35 (1-25/64)
d1 d2
60 (2-23/64)
35 (1-25/64)
DC Control Relays with 48...72V, 110...125V or 220...250V DC Electronic Coil Type a b c c1 c2
700-CF, -CFB, -CFM
45 (1-25/32)
105 (4-1/8)
80.5 (3-11/64)
75.5 (3-3/32)
6 (1/4)
Ød 2 screws 4.5 (3/16)
DC Control Relays with Conventional Coil Type a b c c1 c2
700-CF, -CFB, -CFM
45 (1-25/32)
81 (3-3/16)
106.5 (4-3/16)
101.5 (4)
6 (1/4)
Ød 2 screws 4.5 (3/16)
Accessories AC Control Relay Relay with
(inches)
mm
(inches)
c/c1 + 39
(c/c1 + 1 – 37/64)
c/c1 + 39 c/c1 + 1 – 37/64)
Auxiliary Contact for Front Mounting
2- or 4-pole
Auxiliary Contact for Side Mounting
1- or 2-pole a+9
(a + 23/64)
a+9
(a + 23/64)
Pneumatic Timing Module
⎯ on coil terminal side c/c1 + 58
(c/c1 + 2 – 23/64)
b + 24
(b + 15/16)
⎯ b + 24
⎯ (b + 15/16)
⎯ on coil terminal side c/c1 + 61
(c/c1 + 2 – 31/64)
⎯
⎯
DC Interface b+9
(b + 23/64)
Surge Suppressor on coil terminal side b+3
(b + 1/8)
⎯ b+3
⎯ (b + 1/8)
Labelling with:
label sheet
+0
(+0)
+0
(+0)
⎯ marking tag with cover
+0
(+0)
+0
(+0)
⎯ marking tag carrier for System V4/V5
+5.5
(+7/32)
+5.5
(+7/32)
⎯ marking tag carrier for System Bull. 1492W
+5.5
(+7/32)
+5.5
(+7/32)
Solid-state Timing Module Mechanical Latching
98
DC Control Relay mm
Rockwell Automation Publication 700-TD552A-EN-P
Page 99
Relays and Timer Specifications
700S-CF Control Relays
Cat. No. Aux. Contact 700S-CF (Front-mounted) Mechanical Life Electrical Life
AC-15 (240V, 3 A)
Weight
AC Coil
[Mil]
15
15
[Mil]
1.5
1.5
[g]
390
⎯
2 x A4
2 x A4
[mm2]
1.5…6
0.5…2.5 0.75…2.5
Terminal Cross-Sections Terminal Type Terminal Size per IEC 947-1 1 Conductor
Solid/ Stranded§ 2 Conductor
[mm2]
1.5…6
Max. Wire Size per UL/CSA
[AWG]
16…10
18…14
Tightening Torque
[lb•in]
13.3…22
8.9…13.3
Tightening Torque
[N•m]
1.5…2.5
1…1.5
§ For 16 or more strands, end ferrule is required DC Switching Ratings for 700S-CF Main Poles in Series (Resistive Load at 60 °C) 1 pole
2 poles
24/48V
15/10 A
25 A
3 poles 25 A
125V
6A
25 A
25 A
220V
1.5 A
8A
25 A
440V
0.4 A
1A
3A
Assignment of Contacts Safety Control Relays with Front-mount Auxiliary Contacts, 8-Pole AC or DC Coil Voltage
A1
53 61 71 81
53 61 71 83
53 61 73 83
54 62 72 82
54 62 72 84
54 62 74 84
A1
13 21 33 43
K1
13 21 33 43
K1 A2
14 22 34 44
700S-CF440⊗… 700S-CFB440⊗…
A1
13 21 33 43
A2
14 22 34 44
K1 A2
14 22 34 44
700S-CF530⊗… 700S-CFB530⊗…
Rockwell Automation Publication 700-TD552A-EN-P
700S-CF620⊗… 700S-CFB620⊗…
99
Page 100
700S-CF Control Relays
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended for manufacturing purposes. c2 c1 c
AC and DC Safety Control Relays with 12V or 24V DC Electronic Coil Cat. No. 700S-CF a b c c1 c2
Ød d1
45
81
119.5
114.5
6
2 - 4.5
60 d2 35
(1-25/32)
(3-3/16)
(4-3/4)
(4-43/64)
(1/4)
(2 - 3/16)
(2-23/64)
(1-25/64)
d2
DC Safety Control Relays with 48...72V, 110...125V or 220...250V DC Electronic Coil Cat. No. 700S-CF a b c c1 c2
Ød d1
45
105
119.5
114.5
6
2 - 4.5
60
35
(1-25/32)
(4-1/8)
(4-3/4)
(4-43/64)
(1/4)
(2 - 3/16)
(2-23/64)
(1-25/64)
d2
DC Safety Control Relays with Conventional Coil Cat. No. 700S-CF
100 a b c c1 c2
Ød d1
45
81
145.5
140.5
6
2 - 4.5
60
35
(1-25/32)
(3-3/16)
(5-49/64)
(5-37/64)
(1/4)
(2 - 3/16)
(2-23/64)
(1-25/64)
Rockwell Automation Publication 700-TD552A-EN-P