The text of a spec sheet · part 9 of 13
Relays and Timers Specifications, Bulletin Number 700, pages 81 to 90
Pages 81 to 90 of 128
The original document is the PDF (10 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HN122
Page 81
Relays and Timer Specifications
700-P Industrial Relays
Type
Standard Cartridge
Master Cartridge
Heavy duty
Bulletin No.
700-P
700-PMKIT
700-PHDKIT
10 A @ 600V AC 5 A @ 600V DC
20 A @ 600V AC 10 A @ 600V DC
35 A @ 600V AC 20 A @ 600V DC
AC
NEMA A600
2 x NEMA A600
2 x NEMA A600
DC
NEMA P600
N150 P600
N150 P600
Electrical Contact Rating Continuous Ratings Make/Break
Additional Contact Ratings for AC single-phase loads
3 Hp @ 240V AC - N.O. 5 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 3 Hp @ 240V AC - N.O./N.C. 1 Hp @ 120V AC - N.O./N.C. 2 Hp @ 120V AC - N.O./N.C. 20 A Resistive Heating to 600V AC 35 A General Use At 0.75 PF to 600V AC 20 A Tungsten Lighting Load to 480V AC 35 A Tungsten Lighting Load to 480V AC, DC Current Ratings Make/Break
Cartridge Cat. No. 700-CP1
Cartridge Cat. No. 700-CPM
Cartridge Cat. No. 700-CPH
Volts DC Contacts in Series DC Switching Inductive Load
Coil Voltage Range
24
64
125
500
600
24
1
5A
2.2 A 1.1 A .55 A .24 A
.2 A
2
10 A
10 A
5A
2A
.7 A
.5 A
3, - 7A
3A
4, - 10 A
5A
250
24
64
125
250
500
600
10 A
5A
2.2 A .55 A .24 A
.2 A
10 A
5A
2.2 A .55 A .24 A
.2 A
20 A
10 A
5A
2A
.7 A
.5 A
20 A
10 A
5A
2A
.7 A
.5 A
1.5 A 1.0 A, 15 A
7A
3A
1.5 A 1.0 A, 15 A
7A
3A
1.5 A 1.0 A
2.5 A 1.5 A, 20 A
10 A
5A
2.5 A 1.5 A, 20 A
10 A
5A
2.5 A 1.5 A
480W 480W 275W 138W 135W 120W
85…110%
85…110%
DC
80…110%
80…110%
80…110%
85…115%
85…115%
85…115%
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
132VA‡
138VA‡
132VA‡
138VA‡
132VA‡
138VA‡
19VA‡
19.3 VA‡
19VA‡
19.3VA‡
19.3VA‡
D Inrush C Sealed
600
125
85…110%
A Inrush C Sealed
500
64
AC Battery Charging
Coil Consumption
250
12.7VA‡
12.7VA‡
12.7VA‡
19VA‡ 12.7VA‡
12.7VA‡
12.7VA‡
PLL - PKLL AC Latch Unit
Inrush
15VA‡
15.6VA‡
5VA‡
15.6VA‡
15VA‡
Sealed
5.4VA‡
5.5VA‡
5.4VA‡
5.5VA‡
5.4VA‡
PLL - PKLL DC Latch Unit
Unlatch
35VA‡
35VA‡, Intermittent
35 W‡
35 W‡, Reset Time
PT – PKT
75 ms
75 ms, Minimum Pulse
PLL–PKLL
75 ms
75 ms, 15.6VA‡ 5.5VA‡
Mechanical Pickup
AC – 10…20 ms DC – 30…50 ms
AC – 10…20 ms DC – 30…50 ms
AC – 10…20 ms DC – 30…50 ms
Dropout
AC – 10…20 ms DC – 20…33 ms
AC – 10…20 ms DC – 20…33 ms
AC – 10…20 ms DC – 20…33 ms
Operating Time
Mechanical Life
10 million operations Construction
Contact Arrangement Contact Material Mounting
Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum)
Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum)
Up to 6 Poles, Convertible to N.O. or N.C. (4 N.C. Maximum)
Silver Nickel
Silver Cadmium Oxide
Silver Cadmium Oxide
Panel, Strip Mount, or DIN Rail Horizontal Mounting Recommended
Panel, Strip Mount, or DIN Rail Horizontal Mounting Recommended
Panel, Strip Mount, or DIN Rail Horizontal Mounting Recommended
Environmental Temperature
–20…+65 °C (–4…149 °F)
–20…+65 °C (–4…149 °F)
–20…+65 °C (–4…149 °F)
Storage
–40…+65 °C (–40…149 °F)
–40…+65 °C (–40…149 °F)
–40…+65 °C (–40…149 °F)
Wire Terminations Wire size per UL/CSA
#18 AWG…(2) #12 AWG
Tightening Torque
8…12 lb•in (0.9…1.4 N•m)
Temperature inside the panel. ‡ Average value for all coils within range. For values on a specific coil voltage, contact your local Rockwell Automation sales office or Allen-Bradley distributor. International Symbol for Mechanically Linked Contacts
Rockwell Automation Publication 700-TD552A-EN-P
81
Page 82
700-P Industrial Relays
Relays and Timer Specifications
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 700-P Relays with standard, master contact, or heavy-duty contact cartridge 103.43 (4-5/64), 171.68 (6-49/64)
1/2
2.77 (7/64) 2.77 (7/64)
2- and 4-pole Bulletin 700-P Relay Approximate Shipping Weight: AC – 0.68 kg (1.5 lb), DC – 1.34 kg (2.95 lb)
2- and 4-pole Bulletin 700-P with Pneumatic Time Delay Attachment Approximate Shipping Weight: AC – 0.85 kg (1.88 lb), DC – 1.5 kg (3.33 lb)
AC 136.75 (5-25/64)
171.68 (6-49/64)
2.77 (7/64)
2.77 (7/64)
6- and 8-pole Bulletin 700-P Relay with one -PB adder deck Approximate Shipping Weight: AC – 0.79 kg (1.75 lb), DC – 1.45 kg (3.20 lb)
Bulletin 700-P Relay with Mechanical Latch Attachment Approximate Shipping Weight: AC – 0.97 kg (2.13 lb), DC – 1.62 kg (3.58 lb)
170.10 (6-45/64)
Cat. No. 700
2.77 (7/64)
#8 Screws (Captive)
Bulletin 700-P Relay, up to 12 poles with -PB and -PC adder decks Approximate Shipping Weight: AC – 1.02 kg (2.25 lb), DC – 1.68 kg (3.7 lb)
Relay Rail for Bulletin 700-P, -N, -NM, -R, -RM, -RT, -RTA Relays Secure the mounting strip with two screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots.
178.60 (7-1/32)
AC – 170.49 (6-23/32) DC – 187 (7-25/64)
700-PS Timer
Cat. No. 700-N31, Type 1 Enclosure for Bulletin 700-P, -RTC Relays Approximate Shipping Weight: 1.26 kg (2.8 lb)
5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
1000 (39-3/8)
Bulletin 700-PS Timer Mounted on a Bulletin 700-P Relay Approximate Shipping Weight: AC – 0.68 kg (1.5 lb) without 700-PS, eDC – 1.34 kg (2.9 lb) without 700-PS
3.98 (0.16) 27.0 (1.06)
7.5 (0.3)
0.5 (.02)
2.25 (0.09) 0.5 (.02)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
82
Rockwell Automation Publication 700-TD552A-EN-P
DIN Rail Adapter
Page 83
Relays and Timer Specifications
700S-P Industrial Relays
Type
Type
700S-P
700S-PK Electrical
Electrical Contact Rating Continuous Ratings Make/ Break
AC
NEMA A600
DC
NEMA P600
Minimum Contact Switching Ratings
DC Switching
Ratings Make/ Break
10V, 50 mA Volts DC
Contacts in Series
24V
64V
125V
250V
500V
600V
1
5A
2.2 A
1.1 A
0.55 A
0.24 A
0.2 A
2
10 A
10 A
5A
2A
0.7 A
0.5 A
3, - 7A
3A
1.5 A
1.0 A
4 Contact Electrical Life - Resistive Loads Coil Voltage
Contact Rating Continuous
10 A @ 600V AC 5 A @ 600V DC, - 10 A
5A
2.5 A
AC
NEMA A600
DC
NEMA P600
Additional Contact Ratings for AC Single-Phase Loss
3 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 1 HP @ 120V AC - N.O./N.C. 20 A resistive heating to 600V AC 20 A Tungsten lighting load to 480V AC
DC Current Ratings Make/Break
Cartridge Cat. No. 700-CMS
1.5 A
1.5 million operations at 10A break at 120V AC 14 million operations at 1A break at 120V AC 6 million operations at 1A break at 24V DC
20 A @ 600V AC 10 A @ 600V DC
DC Switching
Volts DC
Contacts in Series
24V
64V
125V
250V
500V
600V
1
10 A
5A
2.2 A
0.55 A
0.24 A
0.2 A
2
20 A
10 A
5A
2A
0.7 A
0.5 A
3, 15 A
7A
3A
1.5 A
1.0 A, 20 A
10 A
5A
2.5 A
1.5 A
AC
85…110%
4
DC
80…110%
AC
85…110%
Battery Charging
85…115%
DC
80…110%
Battery Charging
85…115%
Coil Voltage
Coil Consumption
50 Hz
60 Hz
Inrush
132 VA
138 VA
Coil Consumption
50 Hz
60 Hz
Sealed
19.3 VA
19 VA
Inrush
132 VA
138 VA
Sealed
19.3 VA
AC DC
Inrush
12.7 W
Sealed
12.7 W
AC DC
Mechanical Mechanically Linked Contacts Operating Time
All contacts are mechanically linked per IEC 9475-1 annex L for 2 to 12 poles
Pickup
AC – 10…20 ms DC – 30…50 ms
Dropout
AC – 10…20 ms DC – 20…33 ms
Mechanical Life
Contact Material/Design Mounting
Mechanically Linked Contacts Operating Time
Pickup
AC – 10…20 ms DC – 30…50 ms
Dropout
AC – 10…20 ms DC – 20…33 ms
Contact Arrangement Contact Material/Design
Silver Nickel/Bifurcated Panel mount or mount on 700-MP Relay or DIN Rail Horizontal Mounting Recommended Environmental -20…+65 °C (-4…+149 °F) -40…+65 °C (-40…+149 °F) #18 AWG…(2) #12 AWG
Tightening Torque
8…12 lb•in (0.9…1.4 N•m)
Mechanical (Mechanically-Linked Contacts) Mounting
2 to 12 Poles (8 N.C. Maximum) Silver Cadmium Oxide All contacts, are mechnically linked per IEC 947-5-1 Annex L for 2 to 12 poles Panel mount or strip mount recommended Environmental
Operating§ Temperature
Wire Terminations Wire size per UL/CSA
All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles
Construction
2 to 12 Poles, Double Break Contacts N.O. or N.C. (8 N.C. Maximum)
Storage Temperature
12.7 W Mechanical
10 million operations
Operating Temperature§
12.7 W
Sealed
Construction Contact Arrangement
19 VA
Inrush
-20…+65 °C (-4…+149 °F) -40…+65 °C (-40…+149 °F) Wire Terminations
Coil voltage required for proper operation (percent of rated coil voltage). § Temperature inside the panel.
Wire size per UL/CSA
#18 AWG…(2) #12 AWG
Tightening Torque
8…12 lb•in (0.9…1.4 N•m)
Coil voltage required for proper operation (percent of rated coil voltage). § Temperature inside the panel.
Rockwell Automation Publication 700-TD552A-EN-P
83
Page 84
700S-P Industrial Relays
Relays and Timer Specifications
Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 103.43 (4-5/64)
AC 136.75 (5-25/64)
1/2
2.77 (7/64)
2.77 (7/64)
2- and 4-pole Bulletin 700S-P Relay Approximate Shipping Weight: AC – 0.68 kg (1.5 lb), DC – 1.34 kg (2.95 lb)
6- and 8-pole Bulletin 700S-P Relay Approximate Shipping Weight: AC – 0.79 kg (1.75 lb), DC – 1.45 kg (3.20 lb)
170.10 (6-45/64)
Cat. No. 700
2.77 (7/64)
10- and 12-pole Bulletin 700S-P Approximate Shipping Weight: AC – 1.02 kg (2.25 lb), DC – 1.68 kg (3.7 lb)
5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
1000 (39-3/8)
27.0 (1.06)
7.5 (0.3)
DIN Rail
84
Rockwell Automation Publication 700-TD552A-EN-P
#8 Screws (Captive)
Relay Rail
Page 85
Relays and Timer Specifications
700-N Industrial Relays Bul. 700-N
Bul. 700-NT
Electrical Ratings Rated Thermal Current Ith
10 A
Rated Insulation Voltage
300V
Contact Rating Coil Voltage Range
10 A @ 300V AC, NEMA A300 AC
85…110%, DC
80…110%, Coil Consumption
AC
50 Hz
60 Hz, Inrush
120 VA
133 VA, Sealed
24 VA
20 VA, Mechanical AC, Pickup
14 ms, Drop Out
13 ms, - 0.2…60 s
Repeat Accuracy, ±15% of setting
Reset Time, 75 ms
Timing Mode, On-Delay, convertible to OFF Delay, up to 2 poles convertible to N.O. or N.C.
Max. Operating Time Timing Range
Construction Contact Arrangement Contact Material Mounting
Up to 8 Poles, Convertible to N.O. or N.C., Silver
Silver
Panel or strip mount Horizontal mounting recommended
On relay only
Environmental Ambient Temperature (Outside Enclosure) Operating Temperature Rise (Inside Enclosure)
Operating
–20…+40 °C (–4…+104 °F)
Storage
–40…+60 °C (–40…+140 °F) +25 °C Max, Wire Terminations Wire size per UL/CSA
#18 AWG…(2) #12 AWG
Tightening Torque
8…12 lb•in. (0.9…1.4 N•m)
Rockwell Automation Publication 700-TD552A-EN-P
85
Page 86
700-N Industrial Relays
Relays and Timer Specifications
Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Open Type Without Enclosure Type of Relay
No. of Poles
Type 1 General Purpose Enclosure
Drawing Number
A Wide
B High
C Deep
D
Approx. Ship. Wt. kg (lbs.)
D
E
Approx. Ship. Wt. kg (lbs.)
88.90 (3-1/2)
82.55 (3-1/4)
79.38 (3-1/8)
0.68 (1-1/2)
107.95 (4-1/4)
185.74 (7-5/16)
103.19 (4-1/16)
146.05 (5-3/4)
85.73 (3-3/8)
1.59 (3-1/2)
A Wide
B High
C Deep
Bulletin 700
2…4
1
57.15 (2-1/4)
Bulletin 700
6…8
2
57.15 (2-1/4)
88.90 (3-1/2)
106.36 (4-3/16)
79.38 (3-1/8)
0.79 (1-3/4)
112.71 (4-7/16)
228.60 (9)
120.65 (4-3/4)
206.38 (8-1/8)
92.08 (3-5/8)
2.27 (5)
N with Pneumatic Timer
Bulletin 700
2…4
3
57.15 (2-1/4)
88.90 (3-1/2)
138.11 (5-7/16)
79.38 (3-1/8)
0.91 (2), - - - - - N with Solid-State Timer
Bulletin 700
2…4
3
57.15 (2-1/4)
88.90 (3-1/2)
160.34 (6-5/16)
79.38 (3-1/8)
1.02 (2-1/4), - - - - - N
C
A
A
C
D B
A
C
D B
D B
Drawing Number 2
Drawing Number 1
Drawing Number 3
178.60 (7-1/32)
Cat. No. 700
#8 Screws (Captive)
5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38) 7.5 (0.3)
1000 (39-3/8)
3.98 (0.16)
0.5 (.02)
2.25 (0.09) 0.5 (.02)
DIN Rail Adapter
86
Rockwell Automation Publication 700-TD552A-EN-P
27.0 (1.06)
Page 87
Relays and Timer Specifications
700-R, -RM Sealed Switch Relays
Application Data – Because of the inherent characteristics of this device, the normally open contacts may close before the normally closed contacts open on energization and the normally closed contacts may close before the normally open contacts open on de-energization. Note: For Bul. 700-RM, energizing both the latch and unlatch coil together will cause the relay to be energized and both latch and unlatch coils can be operated together continuously.
Ratings AC Voltage NEMA Rating Designation
Voltage Up to 300V AC
B300 C600
Above 300V AC
DC Voltage
Make
Break
120V
30
3
240V
15
1.5
480V
7.5
0.75
600V
6.0
0.60
Continuous Carrying Current [A]
NEMA Rating Designation
5
Volts DC
Make/Break
Continuous Carrying Current [A]
46…300
138 VA
5
5…46
3A
5
NEMA P300 2.5
Maximum Allowable Off-State Leakage Current Maximum Off-State Leakage Current [mA]
Maximum Off-State Leakage Current [mA]
Type R
Type RM
24V DC
Voltage
23
8
24V AC
23
8
120V AC
5
2
Relay Data Type
700-R
Contact Arrangement
700-RM
Up to 8 poles, available in any combination of N.O. or N.C. contacts
Contact Material
W (tungsten in a controlled gas atmosphere)
Coil Voltage Range
24…250V AC 24…250V DC
Coil Power
Sealed Voltage Range: –15… +10%
5.5 VA, 50/60 Hz 5.5 W DC
1.7 VA, 50/60 Hz (latch or unlatch) 1.7 W DC
Inrush
5.5 VA, 50/60 Hz 5.5 W DC
1.7 VA, 50/60 Hz (latch or unlatch) 1.7 W DC
Pickup Time
30 ms
75 ms min. latch pulse
Dropout Time
30 ms
75 ms min. unlatch pulse
Operating Temperature
–40…+60 °C (–40…+140 °F)
Mounting
–40…+60 °C (–40…+140 °F) Panel mount
Haz. Loc. Ratings
Class I, Division 2, Groups A, B, C, and D
Bulletin 700-R Operating Coils Bulletin 700-R 2-…8-Pole AC Coil Volts
Bulletin 700-R Operating Coil
60 Hz
50 Hz
Bulletin 700-R 2-…8-Pole DC
24
77AB27
77AB27
77D152
48
77AB134
77AB134
77D166
110
77AB86
77AB86, 115…125, - 77D155
120
77AB86
77AB86, 208, - - 220
77AB83
77AB83, 240
77AB83
77AB83, 230…250, - 77D156
Rockwell Automation Publication 700-TD552A-EN-P
87
Page 88
700-R, -RM Sealed Switch Relays
Relays and Timer Specifications
Dimensions are shown in millimeters (inches) shown. Dimensions are not intended to be used for manufacturing purposes.
C
A
C
B
C
A
B
D
Bulletin 700-R400…, -RM400…
A
B
D
Bulletin 700-R800, -RM800…
A
D
Bulletin 700-R with 852s timer
C
160.6 max (6-21/64)
B
D
3.98 (0.16)
700-PS Timer
700 Type R
E Type 1 Enclosure
700-N26
2.25 (0.09)
0.5 (.02)
Cat. No. 700
0.5 (.02) Secure the mounting strip with 2 screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots.
#8 Screws (Captive)
Relay Rail
6.2 (15/64)
50 (1-63/64)
5.2 (13/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8) Cat. No. 199-DR1 DIN Mounting Rail Series B Bulletin 700-R, -RM Relays Open Type Without Enclosures Type of Relay
R
Bulletin 700 and Bulletin 700DC
R with Bulletin 700 Bulletin 852S and Timer Bulletin 700DC
RM
Bulletin 700 and Bulletin 700DC
RM with Bulletin 700 Bulletin 852S and Timer Bulletin 700DC
88
Type 1 General Purpose Enclosure
Drawing Number
A Wide
B High
C Deep
D
Approx. Ship Wt. [kg (lb)]
D
E
Approx. Ship Wt. [kg (lb)]
2…4
1
55.56 (2-3/16)
88.90 (3-1/2)
92.25 (3-3/8)
79.38 (3-1/8)
0.91 (2)
104.78 (4-1/8)
185.74 (7-5/16)
103.19 (4-1/16)
146.05 (5-3/4)
85.73 (3-3/8)
1.81 (4)
5…8
2
55.56 (2-3/16)
88.90 (3-1/2)
111.13 (4-3/8)
79.38 (3-1/8)
1.02 (2-1/4)
112.71 (4-7/16)
228.60 (9)
120.65 (4-3/4)
206.38 (8-1/8)
92.08 (3-5/8)
2.49 (5)
2…4
3
55.56 (2-3/16)
88.90 (3-1/2)
165.1 (6-1/2)
79.38 (3-1/8)
1.25 (2-3/4), - - - - - 2…4
1
55.56 (2-3/16)
88.90 (3-1/2)
95.25 (3-3/8)
79.38 (3-1/8)
0.91 (2)
104.78 (4-1/8)
185.74 (7-5/16)
103.19 (4-1/16)
146.05 (5-3/4)
85.73 (3-3/8)
1.81 (4)
5…8
2
55.56 (2-3/16)
89.90 (3-1/2)
111.13 (4-3/8)
79.38 (3-1/8)
1.02 (2-1/4)
112.71 (4-7/16)
228.60 (9)
120.65 (4-3/4)
206.38 (8-1/8)
92.08 (3-5/8)
2.49 (5)
2…4
3
55.56 (2-3/16)
88.90 (3-1/2)
165.1 (6-1/2)
79.38 (3-1/8)
1.25 (2-3/4), - - - - - No. of Poles
A Wide
B High
C Deep
Rockwell Automation Publication 700-TD552A-EN-P
Page 89
Relays and Timer Specifications
700-RTC Industrial Relays
Voltage and Power Requirements AC Voltage +10% –15% 50/60 Hz
Total Power Required
Initiate Terminal Power
Maximum Allowable Leakage Current
Coil Code
24V AC
8 VA
4 VA
10 mA
U24
110/120V AC
9 VA
4 VA
2.4 mA
U1
DC Voltage +10% –20%
Total Power Required
Initiate Terminal Power
Maximum Allowable Leakage Current
Coil Code
24V DC
10 W
5W
10 mA
U24
120V DC
11 W
5W
2.4 mA
U1
Type Contact Rating (See pub. 700-SG003*)
700-RTC NEMA B600 600V AC, 5 A NEMA P300 300V DC, 5 A
Contact Arrangement
1…4 poles. Max. of 2 timed and 2 instantaneous. Available in any combination of N.O. and N.C. contacts
Contact Material
W (tungsten in a controlled gas atmosphere)
Operating Mode
Convertible to ON-Delay or OFF-Delay
Timing Range
0.015…64 minutes; 0.05...120 seconds
Reset Time
25 ms
Repeat Accuracy
±1% (or ±50 ms) at constant voltage and temperature
Mounting
Panel or strip mount
Surge Suppression
Not required. Timers have internal suppression
Haz. Loc. Ratings
Class I, Division 2, Groups A, B, C, and D
Maximum Allowable Leakage Current
24V AC/DC
10 mA
110/120V AC, 120V DC
2.4 mA
Ambient Operating:
–20…+60 °C (–4…+140 °F)
Storage:
–20…+60 °C (–4…+140 °F)
Continuous duty units placed close to each other (3 in a row) have a temperature range of –20…+45 °C (–4…+113 °F) or should have air circulated around the units. Approximate space of 3/4 in (mm) on all sides is needed.
Rockwell Automation Publication 700-TD552A-EN-P
89
Page 90
700-RTC Industrial Relays
Relays and Timer Specifications
Typical Wiring Diagram L1 External Initiating Contact (N.O. or N.C.) Timed Contacts Any Combination of N.O. and N.C.
Instantaneous Contacts Any Combination of N.O. and N.C.
L2
P TIMED
L1 +
INST
L2
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
5.2 (2-13/64) Dia. Mounting Holes
Approximate Shipping Weight 0.92 kg (2.1 lb.)
NEMA Type 1 Enclosure for RTC Relays Approximate Shipping Weight 1.26 kg (2.8 lb.)
90
Rockwell Automation Publication 700-TD552A-EN-P