For the Allen-Bradley 700-HN122
Page 101
Relays and Timer Specifications
700S-CF Control Relays
Safety Relay Circuit With 5 Safety Outputs Use for E-stop control. E-stop will work properly if any one fault occurs (a fault could be one welded contact or one undesired open connection such as a loose wire). High output switching capability and long contact life. Circuit complies with EN 954 categories 1, 2, 3, 4. Helps prevent restart of the 5 safety outputs if there is a single fault anywhere in the system. Use (3) 700S-CF relays and this diagram to construct the circuit Basic Circuit (1) Output Circuit (3 Relays, 9 Terminal Blocks)
Basic Circuit (1) Output Circuit (3 Relays, 9 Terminal Blocks)
Start
Push To Stop Pull To Reset
Included in factory wired units
LOAD 1 (5) Output Circuit (3 Relays, 17 Terminal Blocks) LOAD 2 LOAD 3 LOAD 4 LOAD 5 Numbers shown are the line numbers where the contacts for this relay appear. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.
Rockwell Automation Publication 700-TD552A-EN-P
101
Page 102
700S-CF Control Relays
Relays and Timer Specifications
Accessories Safety Control Relays with mm
[in.]
Auxiliary contact block for side mounting 1- or 2-pole a+9
(a + 23/64)
Electronic Timing Module on coil terminal side b + 24
(b + 15/16)
Interface Module on coil terminal side b+9
(b + 23/64)
Surge Suppressor on coil terminal side b+3
(b + 1/8)
Labeling with label sheet
+0
(+ 0)
Marking tag sheet with clear cover
+0
(+ 0)
Marking tag adapter for System Bul. 1492W
+ 5.5
(+ 7/32)
Mounting Position
AC and DC E Safety Control Relays
Front View
102
Side View
DC Safety Control Relays
Front View
Side View
Rockwell Automation Publication 700-TD552A-EN-P
Page 103
Relays and Timer Specifications
700-K Control Relays
Assignment of Contacts Device Combinations in Accordance with IEC 60947-1 / -4-1 Table valid for : AC / DC = 0.85…1.1 x Us, Tamb. = -25 °C…+60 °C, normal position (horizontal rail mounting). Also valid for Bulletin 700-KR relays and Bulletin 100-KR auxiliary contacts. Auxiliary Contact Blocks
Circuit Diagram
Control Relays 700-K (AC and DC Control) 700-K22Z-⊗
700-K31Z-⊗
700-K40E-⊗
700-KL22Z-⊗
A1 13 43 21 31
A1 13 33 43 21
A1 13 23 33 43
A1 13 47 21 35
Control
A2 14 44 22 32
A2 14 34 44 22
A2 14 24 34 44
A2 14 48 22 36
AC/DC, 31Z + 02E = 33Y ‡
40E + 02E = 42Y, AC/DC
22Z + 11E = 33Y
31Z + 11E = 42Y
40E + 11E = 51Y
L22Z + 11E = L33Y
AC/DC
22Z + 20E = 42Y
31Z + 20E = 51Y
40E + 20E = 60Y
L22Z + 20E = L42Y
AC/DC, - 40E + 04E = 44Y ‡, AC/DC, 31Z + 13E = 44Y ‡
40E + 13E = 53Y, AC/DC, 31Z + 22Z = 53Y ‡
40E + 22Z = 62Y, AC/DC, - 40E + 31Z = 71Y §, AC/DC
22Z + 40E = 62Y
31Z + 40E = 71Y
40E + 40E = 80Y
L22Z + 40E = L62Y
Front Mounting 51 61
100-KFA02E 52 62 53 61
100-KFA11E 54 62 53 63
100-KFA20E 54 64 51 61 71 81
100-KFA04E 52 62 72 82 53 61 71 81
100-KFA13E 54 62 72 82 53 83 61 71
100-KFA22Z 54 84 62 72 53 73 83 61
100-KFA31Z 54 74 84 62 53 63 73 83
100-KFA40E 54 64 74 84
For other operating limits, please contact our technical consultant. ‡ Tamb. max. +40 °C § Tamb. max. +40 °C and only allowed for coil voltage 24V DC or 230V AC
Rockwell Automation Publication 700-TD552A-EN-P
103
Page 104
700-K Control Relays
Relays and Timer Specifications
Auxiliary Contact Blocks
Connection Diagrams
Description
Screw Type Terminals
Spring Clamp Terminals
Cat. No.
Cat. No.
N.O.
N.C.
For Use With
0
2
100/104-K, 700-K
1
100-KFA02E
100-KRFA02E
1
1
100/104-K, 700-K
1
100-KFA11E
100-KRFA11E
2
0
100/104-K, 700-K
1
100-KFA20E
100-KRFA20E
0
4
100/104-K, 700-K
1
100-KFA04E
100-KRFA04E
1
3
100/104-K, 700-K
1
100-KFA13E
100-KRFA13E
2
2
100/104-K, 700-K
1
100-KFA22Z
100-KRFA22Z
3
1
100/104-K, 700-K
1
100-KFA31Z
100-KRFA31Z
4
0
100/104-K, 700-K
1
100-KFA40E
100-KRFA40E
51 61 52 62 53 61 54 62 53 63 54 64
Front-mounted auxiliary contacts Auxiliary Contact Blocks 2- and 4-pole versions Choice of contact configurations Snap on, no tools required Electronic-compatible bifurcated contacts for signals down to 15V/2 mA
Pkg. Qty.
51 61 71 81 52 62 72 82 53 61 71 81 54 62 72 82 53 83 61 71 54 84 62 72 53 73 83 61 54 74 84 62 53 63 73 83 54 64 74 84
May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.
Control Modules Connection Diagrams
Description Mechanical Interlock For interlocking of two adjacent contactors No added width to contactor assembly Front mount plug-in type Optional auxiliary contact blocks and suppressor modules mount onto the interlock 24…48V AC RC Suppressor
110…280V AC 380…480V AC
Surge Suppressor Plug-in type Limits surge voltage on coil drop-off
Cat. No.
100/104-K/KR, 700-K/KR
1
100-KMCH
100/104-K/KR, 700-K/KR
100-KFSC50
100-KFSC280
100-KFSC480
100-KFSV55
100-KFSV136
100-KFSV277
100-KFSD250
12…55V AC, 12…77V DC MOV Suppressor
56…136V AC, 78…180V DC
100/104-K/KR, 700-K/KR
137…277V AC, 181…250V DC Diode Suppressor
12…250V DC
May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.
104
Pkg. Qty.
For Use With
Rockwell Automation Publication 700-TD552A-EN-P
100/104-K/KR, 700-K/KR
Page 105
Relays and Timer Specifications
700-K Control Relays
IEC Specifications 700-K
700-KR
AC-12 Rated Thermal Current Ambient temperature 40°C Ith
24…240V
[A]
10
230…500V
[A]
10
230…690V
[A]
10
Ambient temperature 60°C Ith
24…240V
[A]
6
230…500V
[A]
6
230…690V
[A]
6
24V
[A]
3
48V
[A]
3
120V
[A]
3
AC-15/B600 Switching of Solenoids and contactors Ie
230V
[A]
2
240V
[A]
2 1.2
400V
[A]
480V
[A]
1
500V
[A]
1
600V
[A]
0.6
690V
[A]
0.6
[A]
10
Short-circuit Protection "gG" Fuse acc. to IEC 60947-5-1, no welding of contacts Fuse gG
Min. Switching Capacity 15V For bifurcated contacts (control relays and auxiliary contact blocks) [mA]
2
Main current circuit resistance, 1 pole
[mΩ]
6.5
Power dissipation, 4 poles
[W]
2.6
AC control, warm
[W]
4.4
DC control, warm
[W]
5.2
Resistance and Power Dissipation
Total power dissipation
Lifespan Mechanical
[Mio. op.]
15
Electrical AC-15 (240V / 2 A)
[Mio. op.]
0.7
AC control kg (lbs.)
0.16 (0.35)
DC control kg (lbs.)
0.2 (0.44)
Weight
Load Carrying Capacity per UL/CSA AC
[V]
Continuous rating
Rated voltage
40 °C
[A] max. 600
Switching capacity
AC
[A]
B 600
Rated voltage
DC
[V] max. 600
Switching capacity
DC
[A]
Q 600
10
Rockwell Automation Publication 700-TD552A-EN-P
6
105
Page 106
700-K Control Relays
Relays and Timer Specifications 700-K
DC-13/Q600 1 pole
24V
[A]
48V
[A]
2.3 1
110V
[A]
0.55
125V
[A]
0.55
220V
[A]
0.27
250V
[A]
0.27
400V
[A]
0.15
440V
[A]
0.15
600V
[A]
0.1
Cross Sections Conductor Cross Sections - Main Contacts, Auxiliary Contacts, and Coil Terminals
700-K
700-KR
Terminal type
Fine stranded with ferrule
(1) Conductor (2) Conductors
[mm2] [mm2]
0.75…2.5 0.75…2.5
0.50…2.5 0.50…2.5
Solid or coarse stranded
(1) Conductor (2) Conductors
[mm2] [mm2]
1…4 1…2.5 + 1…4
0.75…2.5 ♣ 0.75…2.5 ♣
[Nm]
1.2, Cross section per UL/CSA
Recommended torque
[AWG]
18…12 ‡
18…14 ♣
Recommended torque
[lb-in]
10.6, Pozidriv No. 2 / Blade No. 3 screw ‡ Use same cross sections ♣ Stranded wire only
106
Rockwell Automation Publication 700-TD552A-EN-P
Page 107
Relays and Timer Specifications
700-K Control Relays
Coil Data 700-K Operating Limits AC control 50 Hz, 60 Hz, 50/60 Hz DC control pick-up
[x Us]
0.85…1.1 dropout
[x Us]
0.2…0.75 pick-up
[x Us]
0.8…1.1 9, 12, 24, 110V DC: 0.7…1.25 dropout
[x Us]
0.1…0.75 pick-up
[VA/W]
35/32 hold-in
[VA/W] pick-up
[W] cold 3.0, warm 2.6 hold-in
[W] cold 3.0, warm 2.6 closing delay
[ms]
15…40 opening delay
[ms]
15…33 opening delay
[ms]
15…28 closing delay
[ms]
18…40 6…12
Coil Consumption AC control 50 Hz, 60 Hz, 50/60 Hz DC control
5/1.8
Operating Times AC With RC module DC opening delay
[ms]
With integrated diode opening delay
[ms]
8…12
With external diode opening delay
[ms]
35…50
Rockwell Automation Publication 700-TD552A-EN-P
107
Page 108
700-K Control Relays
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters. Approximate Dimensions are not intended for manufacturing purposes.
(mm)
12 35 45
4
35.2
*)
*) -Minimum distance to grounded parts or walls
49 79
108
180°
54
56
50
25° 25°
Rockwell Automation Publication 700-TD552A-EN-P
Page 109
Relays and Timer Specifications
700-SA Solid State Relays
Control/Input Ratings Rated Control Voltage
Cat. No. 700-SAZY5Z25 700-SANY3Z25
Control Voltage Levels
Max. Operating Control Voltage Range
Max. Reverse Control Voltage
Impedance
4…32V DC
-32V DC
15 mA
4…30V DC
-30V DC
1.5 kΩ (+20% -10%)
5…24V DC
Pick-up Voltage
Drop-out Voltage
4V DC max.
1V DC min.
Load/Output Ratings Continuous Load Current (Resistive) [A]
Cat. No.
Rated Load Voltage
Maximum Load Voltage Range
Min.
Max. Inrush Current‡
700-SAZY5Z25
100…240V AC
75…264V AC
0.1
5.0
80 A, @ 50/60 Hz for 1 cycle
700-SANY3Z25
5…110V DC
3…125V DC
0.1
3.0
12 A (10 ms)
Characteristics Description
Cat. No. 700-SAZY5Z25
Cat. No. 700-SANY3Z25
Triac
Transistor
Pick-up Time
1/2 cycle of load power source cycle time§ + 1 ms max.
0.5 ms max.
Drop-out Time
1/2 cycle of load power source cycle time§ + 1 ms max.
2.5 ms max.
Load Switching Method/Device
Output ON Voltage Drop
1.6V (RMS) max.
1.5V max.
Output Leakage Current
5 mA max. (at 100V AC); 10 mA max. (at 200V AC)
5 mA max. (at 125V DC)
Output VDRM VCEO (V)
600
150
Output di/dt (A/uS)
50, Output dv/dt (V/uS)
500, Output I2t (A2S)
41.6, Output Tj (ºC) Max.
125
Insulation Resistance
150 100 MΩ min. (at 500V DC)
Dielectric Strength
1500V AC, 50/60 Hz for 1 min
Vibration Resistance (Max.)
10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (max.)
1000 m/s2 (100 G)
Ambient Temperature
Operating
–30…80 °C (–22…176 °F) with no icing or condensation
Storage
–30…100 °C (–22…212 °F) with no icing or condensation
Ambient Humidity
45…85% (no condensation)
Standards Compliance
UL 508, CSA C22.2 No. 14, EN 60947-1, -4-3
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified
Weight
Approx. 70 g
1 With constant current input system. SSR input impedance varies with a change in input (control) voltage. Refer to the following graph “Load Current Vs. Ambient Temperature Characteristics” for additional load current details. ‡ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to “Inrush Current Resistivity” graph below. § 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time = 20 ms.
Load Current vs. Ambient Temperature Characteristics
Inrush Current ResistivityΔ
700-SA
700-SA 80
2 1
40
700-SAZY5Z25
30 20 10
Ambient Temperature [° C]
500
100
700-SANY3Z25 200
0
30 50
100
80
60
40
20
0
0 -30 -20
50
5000
700-SANY3Z25 3
10
Load Current [A]
4
70 60
1000
Inrush Current [A. Peak]
700-SAZY5Z25 5
Energizing Time [ms]
Δ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
Rockwell Automation Publication 700-TD552A-EN-P
109
Page 110
700-SA Solid State Relays
Relays and Timer Specifications
Terminal Arrangement (Bottom View)
Load Load power supply
Load Input
Input voltage Note: The plus and minus symbols shown in parentheses are for DC loads.
Basic Application Considerations High Density Mounting of Multiple SSRs If multiple SSRs are installed side-by-side be aware that the outer case wall of the SSR serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current to half.
Protective Component When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has builtin surge suppression (Bulletins 700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device. Select a varistor that meets the conditions of the load voltage outlined in the table below. Load Voltage
Varistor Voltage [V]
100…120V AC
240…270
200…240V AC
440…470
380…480V AC
820…1000
Varistor Surge Resistance 1000 A min.
Note: For additional details applying solid-state relays, refer to pub. 700-AT001*, Solid-State Relay Application Guide.
For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.
EMC Directive Compliance 1. AC-switching models comply with EMC Directives under the following conditions:
Load Load power supply
SSR
Input
3 m max. Load Input
700-SA
Varistor: 470 V, 0.6 W Film Capacitor: 1µ F, 250 VAC
Output Varistor
Film Capacitor
• Connect a varistor between the output terminals. • Connect a film capacitor to the load power supply. • The input cable must be less than 3 m. 2. DC-switching models comply with EMC Directives under the following conditions: Less than 10 m Load Input
700-SA Output
• The input cable must be less than 10 m.
Approximate Dimensions All units in millimeters unless otherwise indicated. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.
Bul.
+ 35 max.
+ 35 max.
52.5 max.
Bulletin 700-SA is compatible with Cat. Nos. 700-HN100, -108, -125, and -204 (sockets).
110
Rockwell Automation Publication 700-TD552A-EN-P