Page 101

Relays and Timer Specifications

700S-CF Control Relays

Safety Relay Circuit With 5 Safety Outputs Use for E-stop control. E-stop will work properly if any one fault occurs (a fault could be one welded contact or one undesired open connection such as a loose wire). High output switching capability and long contact life. Circuit complies with EN 954 categories 1, 2, 3, 4. Helps prevent restart of the 5 safety outputs if there is a single fault anywhere in the system. Use (3) 700S-CF relays and this diagram to construct the circuit Basic Circuit (1) Output Circuit (3 Relays, 9 Terminal Blocks)

Basic Circuit (1) Output Circuit (3 Relays, 9 Terminal Blocks)

Start

Push To Stop Pull To Reset

Included in factory wired units

LOAD 1 (5) Output Circuit (3 Relays, 17 Terminal Blocks) LOAD 2 LOAD 3 LOAD 4 LOAD 5 Numbers shown are the line numbers where the contacts for this relay appear. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

Rockwell Automation Publication 700-TD552A-EN-P

101

Page 102

700S-CF Control Relays

Relays and Timer Specifications

Accessories Safety Control Relays with mm

[in.]

Auxiliary contact block for side mounting 1- or 2-pole a+9

(a + 23/64)

Electronic Timing Module on coil terminal side b + 24

(b + 15/16)

Interface Module on coil terminal side b+9

(b + 23/64)

Surge Suppressor on coil terminal side b+3

(b + 1/8)

Labeling with label sheet

+0

(+ 0)

Marking tag sheet with clear cover

+0

(+ 0)

Marking tag adapter for System Bul. 1492W

+ 5.5

(+ 7/32)

Mounting Position

AC and DC E Safety Control Relays

Front View

102

Side View

DC Safety Control Relays

Front View

Side View

Rockwell Automation Publication 700-TD552A-EN-P

Page 103

Relays and Timer Specifications

700-K Control Relays

Assignment of Contacts Device Combinations in Accordance with IEC 60947-1 / -4-1 Table valid for : AC / DC = 0.85…1.1 x Us, Tamb. = -25 °C…+60 °C, normal position (horizontal rail mounting). Also valid for Bulletin 700-KR relays and Bulletin 100-KR auxiliary contacts. Auxiliary Contact Blocks

Circuit Diagram

Control Relays 700-K (AC and DC Control) 700-K22Z-⊗

700-K31Z-⊗

700-K40E-⊗

700-KL22Z-⊗

A1 13 43 21 31

A1 13 33 43 21

A1 13 23 33 43

A1 13 47 21 35

Control

A2 14 44 22 32

A2 14 34 44 22

A2 14 24 34 44

A2 14 48 22 36

AC/DC, 31Z + 02E = 33Y ‡

40E + 02E = 42Y, AC/DC

22Z + 11E = 33Y

31Z + 11E = 42Y

40E + 11E = 51Y

L22Z + 11E = L33Y

AC/DC

22Z + 20E = 42Y

31Z + 20E = 51Y

40E + 20E = 60Y

L22Z + 20E = L42Y

AC/DC, - 40E + 04E = 44Y ‡, AC/DC, 31Z + 13E = 44Y ‡

40E + 13E = 53Y, AC/DC, 31Z + 22Z = 53Y ‡

40E + 22Z = 62Y, AC/DC, - 40E + 31Z = 71Y §, AC/DC

22Z + 40E = 62Y

31Z + 40E = 71Y

40E + 40E = 80Y

L22Z + 40E = L62Y

Front Mounting 51 61

100-KFA02E 52 62 53 61

100-KFA11E 54 62 53 63

100-KFA20E 54 64 51 61 71 81

100-KFA04E 52 62 72 82 53 61 71 81

100-KFA13E 54 62 72 82 53 83 61 71

100-KFA22Z 54 84 62 72 53 73 83 61

100-KFA31Z 54 74 84 62 53 63 73 83

100-KFA40E 54 64 74 84

For other operating limits, please contact our technical consultant. ‡ Tamb. max. +40 °C § Tamb. max. +40 °C and only allowed for coil voltage 24V DC or 230V AC

Rockwell Automation Publication 700-TD552A-EN-P

103

Page 104

700-K Control Relays

Relays and Timer Specifications

Auxiliary Contact Blocks

Connection Diagrams

Description

Screw Type Terminals

Spring Clamp Terminals

Cat. No.

Cat. No.

N.O.

N.C.

For Use With

0

2

100/104-K, 700-K

1

100-KFA02E

100-KRFA02E

1

1

100/104-K, 700-K

1

100-KFA11E

100-KRFA11E

2

0

100/104-K, 700-K

1

100-KFA20E

100-KRFA20E

0

4

100/104-K, 700-K

1

100-KFA04E

100-KRFA04E

1

3

100/104-K, 700-K

1

100-KFA13E

100-KRFA13E

2

2

100/104-K, 700-K

1

100-KFA22Z

100-KRFA22Z

3

1

100/104-K, 700-K

1

100-KFA31Z

100-KRFA31Z

4

0

100/104-K, 700-K

1

100-KFA40E

100-KRFA40E

51 61 52 62 53 61 54 62 53 63 54 64

Front-mounted auxiliary contacts Auxiliary Contact Blocks 2- and 4-pole versions Choice of contact configurations Snap on, no tools required Electronic-compatible bifurcated contacts for signals down to 15V/2 mA

Pkg. Qty.

51 61 71 81 52 62 72 82 53 61 71 81 54 62 72 82 53 83 61 71 54 84 62 72 53 73 83 61 54 74 84 62 53 63 73 83 54 64 74 84

May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.

Control Modules Connection Diagrams

Description Mechanical Interlock For interlocking of two adjacent contactors No added width to contactor assembly Front mount plug-in type Optional auxiliary contact blocks and suppressor modules mount onto the interlock 24…48V AC RC Suppressor

110…280V AC 380…480V AC

Surge Suppressor Plug-in type Limits surge voltage on coil drop-off

Cat. No.

100/104-K/KR, 700-K/KR

1

100-KMCH

100/104-K/KR, 700-K/KR

100-KFSC50

100-KFSC280

100-KFSC480

100-KFSV55

100-KFSV136

100-KFSV277

100-KFSD250

12…55V AC, 12…77V DC MOV Suppressor

56…136V AC, 78…180V DC

100/104-K/KR, 700-K/KR

137…277V AC, 181…250V DC Diode Suppressor

12…250V DC

May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.

104

Pkg. Qty.

For Use With

Rockwell Automation Publication 700-TD552A-EN-P

100/104-K/KR, 700-K/KR

Page 105

Relays and Timer Specifications

700-K Control Relays

IEC Specifications 700-K

700-KR

AC-12 Rated Thermal Current Ambient temperature 40°C Ith

24…240V

[A]

10

230…500V

[A]

10

230…690V

[A]

10

Ambient temperature 60°C Ith

24…240V

[A]

6

230…500V

[A]

6

230…690V

[A]

6

24V

[A]

3

48V

[A]

3

120V

[A]

3

AC-15/B600 Switching of Solenoids and contactors Ie

230V

[A]

2

240V

[A]

2 1.2

400V

[A]

480V

[A]

1

500V

[A]

1

600V

[A]

0.6

690V

[A]

0.6

[A]

10

Short-circuit Protection "gG" Fuse acc. to IEC 60947-5-1, no welding of contacts Fuse gG

Min. Switching Capacity 15V For bifurcated contacts (control relays and auxiliary contact blocks) [mA]

2

Main current circuit resistance, 1 pole

[mΩ]

6.5

Power dissipation, 4 poles

[W]

2.6

AC control, warm

[W]

4.4

DC control, warm

[W]

5.2

Resistance and Power Dissipation

Total power dissipation

Lifespan Mechanical

[Mio. op.]

15

Electrical AC-15 (240V / 2 A)

[Mio. op.]

0.7

AC control kg (lbs.)

0.16 (0.35)

DC control kg (lbs.)

0.2 (0.44)

Weight

Load Carrying Capacity per UL/CSA AC

[V]

Continuous rating

Rated voltage

40 °C

[A] max. 600

Switching capacity

AC

[A]

B 600

Rated voltage

DC

[V] max. 600

Switching capacity

DC

[A]

Q 600

10

Rockwell Automation Publication 700-TD552A-EN-P

6

105

Page 106

700-K Control Relays

Relays and Timer Specifications 700-K

DC-13/Q600 1 pole

24V

[A]

48V

[A]

2.3 1

110V

[A]

0.55

125V

[A]

0.55

220V

[A]

0.27

250V

[A]

0.27

400V

[A]

0.15

440V

[A]

0.15

600V

[A]

0.1

Cross Sections Conductor Cross Sections - Main Contacts, Auxiliary Contacts, and Coil Terminals

700-K

700-KR

Terminal type

Fine stranded with ferrule

(1) Conductor (2) Conductors

[mm2] [mm2]

0.75…2.5 0.75…2.5

0.50…2.5 0.50…2.5

Solid or coarse stranded

(1) Conductor (2) Conductors

[mm2] [mm2]

1…4 1…2.5 + 1…4

0.75…2.5 ♣ 0.75…2.5 ♣

[Nm]

1.2, Cross section per UL/CSA

Recommended torque

[AWG]

18…12 ‡

18…14 ♣

Recommended torque

[lb-in]

10.6, Pozidriv No. 2 / Blade No. 3 screw ‡ Use same cross sections ♣ Stranded wire only

106

Rockwell Automation Publication 700-TD552A-EN-P

Page 107

Relays and Timer Specifications

700-K Control Relays

Coil Data 700-K Operating Limits AC control 50 Hz, 60 Hz, 50/60 Hz DC control pick-up

[x Us]

0.85…1.1 dropout

[x Us]

0.2…0.75 pick-up

[x Us]

0.8…1.1 9, 12, 24, 110V DC: 0.7…1.25 dropout

[x Us]

0.1…0.75 pick-up

[VA/W]

35/32 hold-in

[VA/W] pick-up

[W] cold 3.0, warm 2.6 hold-in

[W] cold 3.0, warm 2.6 closing delay

[ms]

15…40 opening delay

[ms]

15…33 opening delay

[ms]

15…28 closing delay

[ms]

18…40 6…12

Coil Consumption AC control 50 Hz, 60 Hz, 50/60 Hz DC control

5/1.8

Operating Times AC With RC module DC opening delay

[ms]

With integrated diode opening delay

[ms]

8…12

With external diode opening delay

[ms]

35…50

Rockwell Automation Publication 700-TD552A-EN-P

107

Page 108

700-K Control Relays

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters. Approximate Dimensions are not intended for manufacturing purposes.

(mm)

12 35 45

4

35.2

*)

*) -Minimum distance to grounded parts or walls

49 79

108

180°

54

56

50

25° 25°

Rockwell Automation Publication 700-TD552A-EN-P

Page 109

Relays and Timer Specifications

700-SA Solid State Relays

Control/Input Ratings Rated Control Voltage

Cat. No. 700-SAZY5Z25 700-SANY3Z25

Control Voltage Levels

Max. Operating Control Voltage Range

Max. Reverse Control Voltage

Impedance

4…32V DC

-32V DC

15 mA

4…30V DC

-30V DC

1.5 kΩ (+20% -10%)

5…24V DC

Pick-up Voltage

Drop-out Voltage

4V DC max.

1V DC min.

Load/Output Ratings Continuous Load Current (Resistive) [A]

Cat. No.

Rated Load Voltage

Maximum Load Voltage Range

Min.

Max. Inrush Current‡

700-SAZY5Z25

100…240V AC

75…264V AC

0.1

5.0

80 A, @ 50/60 Hz for 1 cycle

700-SANY3Z25

5…110V DC

3…125V DC

0.1

3.0

12 A (10 ms)

Characteristics Description

Cat. No. 700-SAZY5Z25

Cat. No. 700-SANY3Z25

Triac

Transistor

Pick-up Time

1/2 cycle of load power source cycle time§ + 1 ms max.

0.5 ms max.

Drop-out Time

1/2 cycle of load power source cycle time§ + 1 ms max.

2.5 ms max.

Load Switching Method/Device

Output ON Voltage Drop

1.6V (RMS) max.

1.5V max.

Output Leakage Current

5 mA max. (at 100V AC); 10 mA max. (at 200V AC)

5 mA max. (at 125V DC)

Output VDRM VCEO (V)

600

150

Output di/dt (A/uS)

50, Output dv/dt (V/uS)

500, Output I2t (A2S)

41.6, Output Tj (ºC) Max.

125

Insulation Resistance

150 100 MΩ min. (at 500V DC)

Dielectric Strength

1500V AC, 50/60 Hz for 1 min

Vibration Resistance (Max.)

10…55 Hz, 1.5 mm double amplitude (10 G)

Shock Resistance (max.)

1000 m/s2 (100 G)

Ambient Temperature

Operating

–30…80 °C (–22…176 °F) with no icing or condensation

Storage

–30…100 °C (–22…212 °F) with no icing or condensation

Ambient Humidity

45…85% (no condensation)

Standards Compliance

UL 508, CSA C22.2 No. 14, EN 60947-1, -4-3

Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified

Weight

Approx. 70 g

1 With constant current input system. SSR input impedance varies with a change in input (control) voltage. Refer to the following graph “Load Current Vs. Ambient Temperature Characteristics” for additional load current details. ‡ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to “Inrush Current Resistivity” graph below. § 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time = 20 ms.

Load Current vs. Ambient Temperature Characteristics

Inrush Current ResistivityΔ

700-SA

700-SA 80

2 1

40

700-SAZY5Z25

30 20 10

Ambient Temperature [° C]

500

100

700-SANY3Z25 200

0

30 50

100

80

60

40

20

0

0 -30 -20

50

5000

700-SANY3Z25 3

10

Load Current [A]

4

70 60

1000

Inrush Current [A. Peak]

700-SAZY5Z25 5

Energizing Time [ms]

Δ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.

Rockwell Automation Publication 700-TD552A-EN-P

109

Page 110

700-SA Solid State Relays

Relays and Timer Specifications

Terminal Arrangement (Bottom View)

Load Load power supply

Load Input

Input voltage Note: The plus and minus symbols shown in parentheses are for DC loads.

Basic Application Considerations High Density Mounting of Multiple SSRs If multiple SSRs are installed side-by-side be aware that the outer case wall of the SSR serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current to half.

Protective Component When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has builtin surge suppression (Bulletins 700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device. Select a varistor that meets the conditions of the load voltage outlined in the table below. Load Voltage

Varistor Voltage [V]

100…120V AC

240…270

200…240V AC

440…470

380…480V AC

820…1000

Varistor Surge Resistance 1000 A min.

Note: For additional details applying solid-state relays, refer to pub. 700-AT001*, Solid-State Relay Application Guide.

For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.

EMC Directive Compliance 1. AC-switching models comply with EMC Directives under the following conditions:

Load Load power supply

SSR

Input

3 m max. Load Input

700-SA

Varistor: 470 V, 0.6 W Film Capacitor: 1µ F, 250 VAC

Output Varistor

Film Capacitor

• Connect a varistor between the output terminals. • Connect a film capacitor to the load power supply. • The input cable must be less than 3 m. 2. DC-switching models comply with EMC Directives under the following conditions: Less than 10 m Load Input

700-SA Output

• The input cable must be less than 10 m.

Approximate Dimensions All units in millimeters unless otherwise indicated. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.

Bul.

+ 35 max.

+ 35 max.

52.5 max.

Bulletin 700-SA is compatible with Cat. Nos. 700-HN100, -108, -125, and -204 (sockets).

110

Rockwell Automation Publication 700-TD552A-EN-P