Page 153
Diagnostics
12
Diagnostic
Click on the Diagnostic icon in ToolsTalk to view the Diagnostics window. Press the PROG button on a Power Focus 3000 Graph keyboard to enter the Diagnostics menu section.
12.1
Tool Configuration
Tool general Information This window shows general information about the connected tool. It is also possible to have 36 characters in the tool memory and to change the Tool Max Torque. Changing Tool Max Torque requires great caution. Note! Using a tool for tightening with higher torque then the original Tool Max Torque decrease the lifetime of the tool. If the torque is too high the tool may be damage. Tool Calibration This window shows the Calibration and Normalisation value for the tool. It is also possible to change these values. Changing these values requires great caution since it has a direct effect on the torque measurement accuracy. Note! Do not change these values without contacting an Atlas Copco representative. The Motor tuning command calibrates the tool and motor control unit. This is normally not necessary to do. Open end parameters This window consists of the special settings for Open End tools. See chapter 16, Open End Tools, how to use these settings. Tool Service This window shows the service status of the tool. By turning the Service indicator alarm On the Power Focus 3000 will alert the user when the service interva l has expired.
12.2
Controller Diagnostic
This window shows the hardware configuration and the software versions installed on the Power Focus 3000 controller. 153
Page 154
Diagnostics
12.3
System Diagnostic
These functions enable you to test and diagnose your Power Focus 3000 system. Sensor Tracking Sensor tracking enables you to get torque and angle readings in real time. You will also get the zero offset of the torque transducer given as percentage of the calibration value. The Zero offset reading should ideally be close to zero when no torque is applied to the tool. However, the affect of for instance heat generated during a tightening, will cause the Zero offset to vary over time. This is why Power Focus 3000 is calibrated at the start of each tightening. The Power Focus 3000 is able to correct for deviations of up to ±10% in Zero offset drift. Connect a Reference transducer box to ensure that the Power Focus 3000 calibrates and measures torque correctly. At Sensor tracking start- up a calibration of the torque transducer is done together with a reset of the angle sensor. Pressing the Reset button will only reset the angle counter. Note! Torque and zero offset readings will not be generated for Tensor DS tools. Note! It is not possible to do tightenings while performing a Sensor tracking. I/O Diagnostics The status of all internal and external I/O devices can be viewed in System I/O diagnostics. You can also set the status of relays. All configured I/O devices will appear on the list of available devices. This function is useful whe n you want to test the interaction between the Power Focus 3000 and different external devices. For instance when trouble shooting complex systems with one or several PLC’s connected to the Power Focus 3000. The Relay status and Digin status windows show the status of the selected I/O device. Note that the Read status button has to be pressed in order to updated this view to reflect changes. The Relay test function enables you to set the relays of a selected I/O device. The new status of the relays is set when the Set relay button is pressed. Pushing the Restore button will restore the relays to reflect the current status of the Power Focus 3000. To updated this view to reflect changes triggered by other events push the Read status button.
154
Page 155
Identifier
13
Identifier
Click on the Identifier icon in ToolsTalk to view the Identifier window. Press the PROG button on a Power Focus 3000 Graph keyboard to enter the Identifier menu section. It is possible to send an identifier string to the Power Focus 3000. This string is normally generated from a barcode reader connected to one of the serial ports on the Power Focus 3000 (this barcode is in car plants usually called VIN or ESN). When entered, the Power Focus 3000 will use this number and send it together with the results to ToolsNet software etc. It is also possible to use the barcode to select Jobs or Psets. A filter can be set-up to decide what part of the barcode string that is of interest. The barcode string can be sent to the Power Focus 3000 via the serial connector, FieldBus or Ethernet.
13.1
Barcode String data
The maximum length of the string is 25 ASCII signs. If the string is longer Power Focus 3000 will use the 25 first signs. Serial protocol Baudrate 9600 bps Data bits 8 Stop bits 1 Parity no Handshake off Data string:
STX <data 1-25 characters> ETX (STX = 02H ETX = 03H)
Trouble shooting Symptom No barcode received in Power Focus 3000 No Job or Pset selected
Reason / Action Check the configuration of the barcode reader. Check the cables No match between barcode string and “select matrix”
155
Page 156
Identifier
13.2
Identifier set-up
•
Start by connecting ToolsTalk and the Identifier (Barcode reader) to the Power Focus 3000.
•
Start ToolsTalk and click on Identifier in the PF Map.
•
Set Identifier input source.
•
Click on Set Significant No.
•
Select the positions where the significant information is located in the barcode.
1 – 10 numbers can be selected (it is not necessary to set them in a row). •
156
Click on Set Identifier Setup.
Page 157
Identifier In this window you enter the different combinations of the significant numbers that you need. •
Enter a string (same length as in parameter significant number above) in the Add Identifier string field and click Add. A matrix where the columns represent existing function ID numbers and the rows represent the added Identifier strings is then formed.
•
Once all strings are entered, associate them with a Pset, Multistage or Job by double clicking in the corresponding cell in the matrix and selecting a function ID number from the pop up list.
•
Click OK to exit the window.
•
Click Store to save the settings.
157
Page 158
Page 159
FieldBus
14
FieldBus
Click on the FieldBus icon in ToolsTalk to view the FieldBus window.
A FieldBus communication can be used for data communication between the Power Focus 3000 and PLC’s. It is an effective and fast way for data transferring of short data packages. It is normally used to send discrete I/O data instead of using a large number of discrete cables that have to be hard wired to relays and digital inputs. There are many different FieldBus standards on the market and they all have different hardware and software protocols. To be able to communicate on FieldBus, the Power Focus 3000 must be equipped with a specific card for the preferred type of FieldBus. Profibus-DP, DeviceNet, Interbus and ModBusPlus are the possible selections. Power Focus 3000 acts as a slave in a FieldBus system. A PLC or similar will act as the master. With help of ToolsTalk the FieldBus functionality in the Power Focus 3000 can be configured to fit the customer specific bitmap. It is a very easy way to configure or modify a customer specific bitmap. When the configuration is done you can download to the Power Focus 3000 or save it as a file for later use. The ToolsTalk interface for FieldBus consists of three parts, General set-up, From PF set- up and To PF set- up.
159
Page 160
FieldBus
14.1.1 General set-up The figure below shows the Tools Talk parameters in General Setup for DeviceNet.
160
Page 161
FieldBus Parameters in General SETUP The table below shows the parameters ava ilable for the selected FieldBus type. Parameter
DeviceNet ProfiBus -DP
FieldBus Type To PF DataLength From PF DataLength FB Update Interval Set node address and baud rate from FB Node Addre ss Baud Rate Set source address from Source address Connection Mode PCP length Process DataLength From PF Global DataLength To PF Global DataLength Bitmap select
X X X X X X X
X X X X X X
InterBus
ModBusPlus
X X X X
X X X X X X X X
X X X
X
X
X
X X X
X = Available in FieldBus type FieldBus Type Select the FieldBus Type to use. This parameter shall be selected first. It includes the types; “DeviceNet”, “Profibus-DP”, “InterBus” and “ModBusPlus”. If there is no FieldBus configuration inside the Power Focus 3000 when open FieldBus icon or read from PF, “None” will be shown in the set-up window. If Offline programming is used, “None” is selected when you start. If there is no FieldBus card installed in Power Focus, FieldBus programming only works in Offline mode. DeviceNet ProfiBus DP InterBus ModBusPlus None
If DeviceNet module is installed in the Power Focus 3000. If Profibus module is installed in Power Focus 3000. If Interbus module is installed in Power Focus 3000. If ModbusPlus module is installed in Power Focus 3000. If no FieldBus card is installed or the FieldBus functionality shall be switched off (default).
To PF DataLength To PF DataLength is the total length of the data string send from the PLC to the Power Focus 3000. The length must be the same as defined in the PLC. Because swap bytes are needed for some FieldBus types, only even numbers should be programmed (2, 4, 8, 10, etc). Data length should be a number higher than zero. 161
Page 162
FieldBus The Maximum length that can be programmed is different for each FieldBus type. See the FieldBus specific pages for data. Note! If InterBus is used you have to restart the Power Focus 3000 when the data length is changed. From PF DataLength From PF DataLength is the total length of the data string send from the Power Focus to the PLC. The lengths must be the same as defined in the PLC. Because swap bytes are needed for some FieldBus type, only even numbers should be programmed (2, 4, 8, 10, etc). Data length should be a number higher than zero. The Maximum length that can be programmed varies for different buses. See the FieldBus specific pages for data. Note! If the InterBus is used, you have to restart the PF when the data length is changed.
FB Update Interval If the FieldBus system is heavily loaded it might be necessary to slow down the update interval in PF FieldBus card. If this parameter is set to 0.5 seconds the PF updates the bus every 0.5 sec. The average data traffic must be possible to fit within the programmed interval. If the traffic has a higher peak load the messages are buffered. Valid settings range from 0.05 to 10.00 seconds. Default setting is 0.10 seconds. Set node address and baud rate from Some buses can use a SW-configured node address and baud rate. There are two choices, software or hardware. When “software” is chosen, it is possible to program node address and baud rate from user interface. When “hardware” is chosen, node address and baud rate is configured with the switches on the FieldBus card. Note! Normally the switches on the FieldBus card must be set in a specific way to enable these parameters from ToolsTalk. See the specific bus type pages for possible settings.
162