Page 183
Parameter List P2xx Programming + P20x
Current monitoring
Measures max compensated torque forming current during tightening as percentage of tool max torque.
P200
Current monitoring
Activates the function. The default value is NO.
P201
CM min
Defines min limit for OK tightening.
P201
CM max
Defines max limit for OK tightening.
P21x
PVT self-tap
This function makes it possible to tighten bolted joints where the torque during tightening is higher than the final target. For example, this may be the case when tightening self- tapping.
P210
Self- tap
Activates the function. The default value is NO.
P211
Self- tap interval
Defines the section where measuring is performed. Setting is performed in degrees in the interval 1 – 9999. Default value is 1.
P212
No. of self- tap windows
P213
Self- tap min
P214
Self- tap max
P22x
PVT monitoring
Defines the number of windows that the Self- tap interval [P211] is to be divided into. Each window is then evaluated separately. The number of windows can be chosen between 1 – 9999. Default value is 1. This parameter indicates the lowest torque level for the interval. If the torque level falls below this level, a low- level alarm will be generated. Range is from cycle complete value to self-tap max. Default value is cycle complete. This parameter indicates the highest torque level for the interval. If the torque level exceeds this level, a high level alarm will be generated. Range is from self- tap min to Tool max torque. Default value is tool max torque that means this parameter must be actively changed. Measures PVT during on going tightening.
P220
PVT monitoring
Activates the function. The default value is NO.
183
Page 184
Parameter List P221
P222
PVT delay interval
Defines delay before PVT monitoring starts.
PVT monitor interval
Setting is performed in degrees in the interval 0 – 9999. Default value is 0 degrees. Defines the interval during which the PVT monitoring is to be performed.
P223
No. of PVT windows
P224
PVT min limit
P225
PVT max limit
P23x
PVT compensate
Setting is performed in degrees in the interval 1 – 9999. Default value is 1. Defines the number of windows that the interval should be divided into. Each window is then evaluated separately. The number of windows can be chosen between 1 – 9999. Default value is 1. The PVT min value is evaluated against the monitor interval peak value at the end of the interval. If the torque value falls below this limit, an alarm is generated. Default value is cycle complete value. PVT max is monitored in real- time during the monitor interval and if exceeded, an alarm is generated. Default value is rundown complete value. The PVT compensate value is used as a base reference for the torque used during tightening. This means that each registered torque value is added to the PVT value before it is compared to the programmed torque values. The different values for torque, for example, Final target and First target for 1 st stage, are compensated with the PVT value. Also, the results are compensated.
P230
PVT compensate
Activates the function. The default value is NO. When PVT compensate is set to Yes, a prevailing torque PVT comp, measured at the interval of 20 samples preceding start of PVT comp point is used as the reference for the torque used during the actual tightening cycle. Any torque result is compensated (subtracted) with the prevailing value.
P231
184
PVT comp point
The value can be set between (0 – 9999) degrees. Default value is 10 degrees.
Page 185
Parameter List P24x
Options
P240
Tool tightening direction
P241
Soft stop
Select tool rotation direction. CW for right hand threaded screws and CCW for left hand threaded screws. To be able to start in the correct direction you must turn the tool direction ring to its correct position. This parameter has no effect when running an Open End tool (Tube Nut tool). Yes/No Reduces tool speed at the end of a tightening cycle. Yes is recommended.
P242
Alarm on Re-hit
Yes/No If selected, Power Focus 3000 will detect re-hits, error code E112. The red tool LED will be lit when a re-hit is detected. The criteria for a re- hit are a short or a non-existent second stage in combination with a slow speed in the first stage. Default is No.
P243
P244
Alarm on Tq < target
Yes/No
Alarm on Lost trigger
Yes/No
Decides if the tightening should be approved if the torque is lower than the final target. Default is No.
Decides if a lost tool trigger should abort the tightening. Default is No. P245
DS torque tuning factor
Only used if DS con is chosen as control strategy [P101]. It compensates for the error that DS measurement induces. The value can be set between 80% and 220%. Default value is 100%.
P4xx
Pset set-up
P40x
Pset admin
P402
Name Pset
Name the Pset. Up to 25 characters. Default value is empty.
P406
Pset updated
Timestamp (date and time) for Pset latest modification. Not editable.
- View existing Pset - Create New Pset - Copy Pset - Delete Pset
185
Page 186
Parameter List P5xx
Statistic programming
P50x
Statistic common parameters
P500
Min valid stat tq limit
The result must be greater than or equal to this limit value in order for it to be included in the statistical calculations.
P501
Max valid stat tq limit
The result must be less than or equal to this limit value in order for it to be included in the statistical calculations.
P502
Subgroup size
Defines the subgroup size for statistical diagrams and control limits. If this parameter is changed, the results will be recalculated.
P503
No of subgroups
Group size can be set between 2 – 20. Power Focus can automatically calculate statistical control limits. In order for these limits to be reasonable, they must be performed on a greater number of tightenings. This parameter is used to set the number of subgroups used for these calculations.
The following Pset parameters are statistical control limits. They can be entered manually or be calculated automatically by Power Focus 3000. P504
Subgroup frequency Defines the number of tightening results that are used for one of the statistics calculations.
P505
Latest n values
The latest number of values, 0 – 100.
P506
SPC alarm tq
With this parameter it is possible to switch on or off the torque SPC alarm function.
P507
SPC alarm Angle
With this parameter it is possible to switch on or off the angle SPC alarm functio n.
P508
SPC alarm CM
With this parameter it is possible to switch on or off the current SPC monitoring alarm function.
P51x
SPC torque
Statistic Process Control for torque.
P510
Torque X-bar LCL
The lower control limit for mean value. Calculated automatically or entered manually.
186
Page 187
Parameter List P511
Torque X-bar UCL
The upper control limit for mean value.
P512
Torque range LCL
Calculated automatically or entered manually. The lower control limit for range. Calculated automatically or entered manually.
P513
Torque range UCL
The upper control limit for range. Calculated automatically or entered manually.
P514
Torque X-bar-bar
The mean value for calculated mean values for groups of tightenings.
P515
Torque range-bar
The mean value for calculated mean ranges for groups of tightenings.
P52x
SPC angle
Statistic Process Control for angle.
P520
Angle X-bar LCL
The lower control limit for mean value. Calculated automatically or entered manually.
P521
Angle X-bar UCL
The upper control limit for mean value. Calculated automatically or entered manually.
P522
Angle range LCL
The lower control limit for range. Calculated automatically or entered manually.
P522
Angle range UCL
The upper control limit for range. Calculated automatically or entered manually.
P524
Angle X-bar-bar
The mean value for calculated mean values for groups of tightenings.
P525
Angle range-bar
The mean value for calculated mean ranges for groups of tightenings.
P53x
SPC Rundown Angle
Statistic Process Control for rundown angle. (Only active if Rundown angle is chosen [P04]).
P530
Rundown X-bar LCL
The lower control limit for mean value. Calculated automatically or entered manually.
187
Page 188
Parameter List P531
Rundown X-bar UCL
P532
Rundown range LCL
P532
P534 P535 P54x P540
Rundown range UCL
The upper control limit for mean value. Calculated automatically or entered manually. The lower control limit for range. Calculated automatically or entered manually. The upper control limit for range. Calculated automatically or entered manually.
Rundown X-bar-bar The mean value for calculated mean values for groups of tightenings. Rundown range-bar The mean value for calculated mean ranges for groups of tightenings. SPC Self-tap
Statistic Process Control for self-tap. (Only active if PVT Self-tap is selected [210]). Self- tap X-bar LCL The lower control limit for mean value. Calculated automatically or entered manually.
P541
Self- tap X-bar UCL The upper control limit for mean value. Calculated automatically or entered manually.
P542
Self- tap range LCL
The lower control limit for range. Calculated automatically or entered manually.
P542
Self- tap range UCL The upper control limit for range. Calculated automatically or entered manually.
P544
Self- tap X-bar-bar
The mean value for calculated mean values for groups of tightenings.
P545
Self- tap range-bar
The mean value for calculated mean ranges for groups of tightenings.
P55x
SPC PVT
P550
PVT X-bar LCL
Statistic Process Control for prevailing torque. (Only active if PVT monitoring is chosen [220]). The lower control limit for mean value.
P551
PVT X-bar UCL
The upper control limit for mean value.
P552
PVT range LCL
The lower control limit for range.
188
Page 189
Parameter List P552
PVT range UCL
The upper control limit for range.
P554
PVT X-bar-bar
The mean value for calculated mean values for groups of tightenings.
P555
PVT range-bar
The mean value for calculated mean ranges for groups of tightenings.
P56x P560
SPC CM parameters CM (X-bar) LCL
P561
CM (X-bar) UCL
P562
CM R LCL
P563
CM R UCL
P564
CM (X bar)
P565
CM (R bar)
Defines the low limit for the permitted values to be in the x-bar calculations. Defines the high limit for the permitted values to be in the x-bar calculations. Defines the low limit for permitted variations in the range calculations. Defines the high limit for permitted variations in the range calculations. Defines the wanted CM average for all of the subgroups. (In each subgroup the average tightened CM value is calculated. Then an average is calculated based on all of the averages.) Defines the desired average of the CM variation for all of the subgroups. (In each subgroup the average tightened CM variation is calculated. Then an average is calculated based on all of the averages.)
189
Page 190
Parameter List Multistage M20x Multistage result properties M200 Name
Specifies the name of the opened Multistage.
M201 Stage list
Stage list specifies the list of available Psets, input by the operator, that can be linked together into a Multistage. Executes the specified link list of Psets into a Multistage
M202 Batch count
Activates a function that measures how many times a multistage tightening is repeated. It must be determined from where the Batch size value should be read, if the Batch count is activated Off: Batch count is not used. Pset: Use Psets Batch size. FieldBus: An external source decides Batch size via FieldBus. Ethernet/Serial: An external source sets Batch size via Ethernet or serial interface.
M203 Batch size
The Batch size specifies the number of Multistage tightenings in a batch. The range is 0-99.
M204 Lock at batch OK
When Lock at batch is set to yes, the tool is disabled until next Pset/Multistage is selected.
M205 Stop between stages When Stop between stages is set to yes, tightening has an idle time between two consecutive stages. The idle time is specified in Tool idle time. M206 Loosening on NOK If the status of the Multistage tightening is NOK and Loosening on NOK is asserted, the tool runs in reverse direction to loosen the joint. M210 Torque result
Specifies after which of the stages the final torque result shall be displayed. Default is last stage.
M211 Angle result
Specifies after which of the stages the final angle result shall be displayed. Default is last stage.
M212 Rundown result
Specifies after which of the stages the final rundown angle result shall be displayed. Default is last stage.
190
Page 191
Parameter List M213 Self- tap result M214 PVT result
Specifies after which of the stages the final prevailing torque self-tap result shall be displayed. Default is last stage. Specifies after which of the stages the final prevailing torque monitoring result shall be displayed. Default is last stage.
M215 CM result
Specifies after which of the stages the current monitoring result shall be displayed. Default is last stage.
M216 Trace
Specifies the point at which of the stages the graph results (trace diagram) are to be displayed. Default is last stage.
M22x Statistic common M220 Min valid stat tq limit
0 Nm – 9999 Nm
M221 Max valid stat tq limit
0 Nm – 9999 Nm
M222 Subgroup size
1 – 20
The result must be greater than or equal to this value to be included in the statistical calculations.
The result must be less than or equal to this value to be included in the statistical calculations.
Defines the size of the subgroup that forms the basis for the statistical charts and control limits.
M223 No of subgroups
If this parameter is changed, all the results have to be recalculated or deleted. 1 – 7500 Power Focus calculates control limits on request. For these limits to be relevant they must be based on a large number of data, at least 100. This parameter defines when enough results are collected. If this parameter is changed, all the results have to be recalculated or deleted.
M224 Subgroup frequency 1 – 7500 This parameter measures and stores a subgroup with a given range. It also indicates the number of subgroups that are disregarded between every stored subgroup.
191
Page 192
Parameter List M225 Latest n values
1 – 100
M226 SPC alarm tq
The number of tightening values which are included in statistical calculations. On/Off This parameter switch the torque SPC alarm function on or off.
M227 SPC alarm angle
On/Off This parameter switch the angle SPC alarm function on or off.
M228 SPC alarm CM
On/Off This parameter switch the current monitoring SPC alarm function on or off.
192