Page 203

Parameter List D2xx

Controller Diagnostics

D20x D200

Software information Main code version

D201

Application code version

This is the version number of the Power Focus software version. The version number of the application code.

D202

Parameter tree version

The version number of the parameter tree.

D203

MC code version

The version number of the Motor Card code.

D204

RBU code version

The version number of the RBU code.

D205

Boot code version

The version number of the Boot code.

D206

DSP code version

The version number of the DSP code.

D21x

Hardware information

D210

PF3000 type

Shows the type of the Power Focus. Available types are: Compact, Graph and Colour.

D215

RBU type

The type of RBU. Available types are: Bronze, Silver and Gold. There are also customer specific RBUs.

D216

RBU serial number

Shows the serial number of the RBU (the hard coded, unique, MAC address).

D3xx D30x D300 D31x D310

System Diagnostics Transducer information Sensor tracking Sensor tracking will monitor the torque and angle sensors in real-time and display the ongoing results. System I/O Diagnostic Relay status Shows the usage and status of the relay devices.

D311

DigIn status

Shows the usage and status of the digital input devices.

D312

Relay test

Performs a test of the relays used. Note that it is not possible to have PF3000 in normal operation during the test. 203

Page 204

Parameter List

18.5

FieldBus

F100

FieldBus type

There are four types of FieldBus available, DeviceNet, ProfiBus-DP, InterBus, ModBusPlus and Profibus. Default value is None.

F102 F103

From PF DataLength From the Power Focus DataLength is the total string length and from/to PLC to the Power Focus. The length must be the same To PF DataLength as defined in the PLC and all in bytes. The maximum length defined in the Power Focus is 122 in both directions. The total length in Profibus cannot exceed 416 bytes. Because swap bytes are needed for some FieldBus types, only even numbers can be inputted here.

F110

Connection mode

This is the mode of network communication. There are three modes; Polled, BitStrobe and Change of Status. The setting must be the same as the scanner set-up.

F120

FB node address

It is possible to set Node address from 1 to 125.

F131

Set node address from

There are two possible choices: software and hardware. When software is chosen, the node address is set from user interface. When hardware is chosen, the node address only can be set from the switches on Profibus card.

F200

FB update interval

The interval can be between 0.05 and 10 s.

F300

Bitmap select

Bitmap select is used to map data in the correct way with the PLC monitoring. For DeviceNet, Intel Endian must be used. For Profibus, Motorola Endian must be used.

204

Page 205

Parameter List

18.6

Identifier

I10x

General set-up

I100

Identifier input source

Defines what source is to be accepted when a VIN number is to be read. Available options : - Off - Scanner - FieldBus - Ethernet/Serial - Ethernet/Serial & Scanner

I101

Set significant numbers

This parameter is a string of integers that tells the PF which positions to look at in the Identifier string. The string can have maximum 25 characters.

I102

Set identifier set-up

This parameter is a table that match each string to a Pset (or multistage) no or a Job no. No limit on the number of strings. Several strings can match the same Pset (or multistage) no, or Job no.

I103

Send identifier

This parameter will tell PF3000 that an identifier string is being sent from the identifier- input source.

I20x

Card reader setup

I200

Defines the type of identifier reader connected to the PF3000

Available options are - None - Euchner ident system

205

Page 206

Parameter List

18.7

Sync

S10x Sync programming options S100 Sync group list

Sync programming options are only available if the PF3000 is a sync master Used to view all existing Power Focus, and to add them to the sync group Defines what strategy to use for sync tightening. Available options: - Stage sync Defines what strategy to use for loosening. Available options: - Normal - Sync loosening

S101

Sync tightening strategy

S102

Sync loosening strategy

S103

Continue if sync failed

Used if you want to continue with the sync tightening even if some cont roller function is lost. Available options Yes or No.

S104

Sync OK time

Time between first and last draw. Permitted values between 0 and 13 s.

206

Page 207

Event codes

19

Event codes

19.1

Event code types

Event codes are displayed to inform the operator of what happens to the Power Focus 3000 unit and why it behaves the way it does. Power Focus 3000 event codes can be classified in four categories: 1. 2. 3. 4.

Statistic event codes Warning event codes Event codes that must be acknowledged Fatal event codes

The event codes are recorded in either the Statistics event log or the General event log (depending on the event code type). Each log can store up to 100 event codes in total.

19.1.1 Statistic event codes Statistic event codes show the operator that the running process does not meet requirements. When this type of event occurs, the STAT LED on the Power Focus 3000 unit is turned on. Statistic event codes are recorded and stored in the statistic event log, which can be accessed from the view menu of Power Focus 3000 Graph or by clicking the StatAlarm button in ToolsTalk.

19.1.2 Warning event codes Warning event codes show the operator that although the current settings are not optimal, it is still possible to run the tool, if the tool is not locked. This type of event code disappears from the Power Focus unit’s display after 3 seconds or when it is acknowledged. Warning event codes are recorded and stored in the General event log, which can be accessed from the view menu of Power Focus 3000 Graph or from the Options menu in ToolsTalk.

19.1.3 Event codes that must be acknowledged These event codes show the operator that it is not possible to run the tool with the present settings. The event codes remains displayed until they are acknowledged. Acknowledge the event by using the buttons on the Power Focus unit, ToolsTalk, or the digital inputs. Event codes that must be acknowledged are recorded and stored in the General event log. The General event log can be accessed from the view menu of Power Focus Graph or from the Options menu in ToolsTalk.

207

Page 208

Event codes

19.1.4 Fatal Event Codes If a fatal event code occurs, an event that prevents operation of the unit has been detected. The unit is required to be power cycled (and get the problem related to the displayed event code solved) before it is possible to proceed. Fatal event codes are recorded and stored in the General event log, which can be accessed from the view menu of Power Focus 3000 Graph or from the Options menu in ToolsTalk.

Event Groups

Event code

Group

Description

E000-E099 E100-E199 E200-E299 E300-E399 E400-E499 E500-E599 E600-E699 E700-E799 E800-E899 E900-E999

0 1 2 3 4 5 6 7 8 9

Rundown failures Event-related errors User input error Statistical errors Communication errors Hardware errors TOOL Hardware errors DC3000/MC3000 Hardware errors Software errors Errors MMI3000

EXXX "Text"

1/2/3/4

Information

Tool not ready

PF not ready

Category

Acknowledg ement

Event code list

Short description (graphic display)

Event code

19.3

Tool locked

19.2

ACK / PFNR / - TNR / - LCK "Text" /-

E000-E099: Rundown errors E001 E002 E003 E004 E005 E006 E007

Torque LO Torque HI Torque measurement possibly invalid Angle1 LO Angle1 HI Angle2 LO Angle2 HI

2 2 2 2 2 2 2

-

-

-

-

E100-E199: Event-related errors E101 E102

Pset invalid (check sum error) Rundown prohibited due to Lock on Reject

3 2

ACK -

-

TNR

E103

Forward direction prohibited via digital input

2

-

-

TNR

208

LCK This error code is displayed after a NOK tightening when the function Lock on Reject is activated. In this case the tool is disabled, the tool can be unlocked with a digital input or with the tool ring. LCK The forward direction is prohibited via the digital input.

Page 209

EXXX "Text"

1/2/3/4

ACK / PFNR / - TNR / - LCK "Text" /-

E104

Reverse direction prohibited

2

-

-

-

E105

Reverse direction prohibited via ToolsTalk Rundown prohibited due to active CycleHold Rundown prohibited due to Line Control, batch not enabled

2

-

-

-

2

-

-

TNR

2

-

-

TNR

Rundown prohibited due to keypad usage Pset revision not supported by this SW Configuration revision not supported by this SW MC Rundown timeout

2

-

-

TNR

2

-

-

TNR

-

2

-

-

TNR

-

2

-

-

-

-

2 2

ACK

PFNR

TNR

-

3

ACK

PFNR

TNR

-

2 2

-

-

-

-

E120

Rehit Current limit reached – Rundown aborted OpenEnd Reference position not found Direction uncertain SelfTap maxtorque reached – Rundown aborted MC Motortuning failure

3

ACK

PFNR

TNR

-

E121

OpenEnd tuning failure

3

ACK

PFNR

TNR

-

E122123 E126

Multistage abort ed

2

-

-

-

-

E127

PVT shut off

2

-

-

-

-

E128

Trigger lost

2

-

-

-

-

E106 E107

E108 E109 E110 E111 E112 E113 E114 E115 E116

Information

Tool locked

Tool not ready

PF not ready

Acknowledg ement

Category

Short description (graphic display)

Event code

Event codes

-

The reverse direction is prohibited via digital input or in Job mode. The reverse direction is prohibited in job mode when Lock at Job Done is selected or batch mode is configured to NOK+OK. - The reverse direction is prohibited via Tools Talk. LCK The tool is locked due to Cycle hold. LCK A job using Line Control is selected. The job does not start until Line Control Start signal is received. -

The rundown was not terminated before the drive time out (2 minutes). The current limit has been reached; the drive is disabled.

Motor tuning failed. The trigger could have been released before the end of the motor tuning or the tool has a defect. This error indicates that the open end tuning command has not been successfully performed. Either the command was aborted by the operator or the command could not be performed for any other reason.

This error indicates that the current running multistage has not been performed entirely (the drive has been shut off or the tool trigger was released before the end…). This error indicates that the drive was shut off in the Self-tap or prevail phase of the rundown. When the function Trigger lost is activated in the Pset, this error indicates that the trigger of the tool was released before final target.

209

Page 210

EXXX "Text"

1/2/3/4

Torque lower than target

2

-

-

-

E130 E131

Post view torque shut off Tool Disconnected

4

ACK

PFNR PFNR

TNR TNR

E132

Wrong tool start input setting

2

ACK

PFNR

TNR

E133

Forward direction prohibited via ToolsTalk MC Target input active at start attempt

2

-

-

TNR

2

-

-

TNR

E135

MC No start Ack from CC

2

-

-

TNR

E136

Rundown prohibited due to batch locked

2

-

-

TNR

E137 E138

Rundown prohibited via field bus Wrong tool start input source

2 2

-

-

TNR TNR

E139

Rundown prohibited via Open protocol Insert user ID card to release tool

2

-

-

TNR

2

-

-

TNR

3

ACK

PFNR

TNR

E142 E150

MC Current Monitoring torque deviation MC SyncroTorque diffstop Job client does not respond

2 2

-

-

-

E151

Job in OFF mode

2

-

-

-

E152

PF locked in job mode

2

-

-

TNR

E153

Not Ok to select new job

2

-

-

-

E140 E141

210

Information

ACK / PFNR / - TNR / - LCK "Text" /-

E129

E134

Tool locked

Tool not ready

PF not ready

Acknowledg ement

Category

Short description (graphic display)

Event code

Event codes

-

When the function torque lower than target is activat ed in the Pset, this error indicates that the torque result is below final target. The torque status is NOK even if the torque result was larger than final torque min. - Post view torque conditions were not fulfilled. - This error indicates that the tool is not connected to the controller or that the tool cable has been damaged. - 1) Check if the remote start wiring in the PF is correctly set in accordance to the settings in the Configuration parameters (C220). 2) Check if the tool trigger is constantly pressed or if there is some malfunction in the tool. LCK The forward direction is prohibited via Tools Talk. - The target signal is active in the drive though the tightening has been acknowledged by the CCcard - No start acknowledgement has been received by the MC drive from the CC-card (timeout 32s) LCK This error is displayed if the function lock at batch OK is enabled and when the batch is completed. The tool can only be unlocked via a digital input. LCK The rundown is prohibited via field bus. - It is only possible to start the tool from the selected tool start select source. LCK The rundown is prohibited via Open protocol LCK The tool is locked, the user must insert his ID card in the card reader to release the tool -

When running a Cell Job, this error is displayed by the job master when one of the job members does not respond. - It is not possible to select a new job, the PF3000 is in Job Off mode. LCK This error appears when in a forced cell job an attempt is made to tighten with a controller which is not currently active or when a controller has performed all tightenings. - A job is currently running, it is not possible to select a new job until the first is finished in some way (completed or aborted). This message is also displayed if a job is selected on a job member.

Page 211

EXXX "Text"

1/2/3/4

Information

Tool locked

Tool not ready

PF not ready

Acknowledg ement

Category

Short description (graphic display)

Event code

Event codes

ACK / PFNR / - TNR / - LCK "Text" /-

E154

Remote jo b running

2

-

-

-

-

E155

Remote job aborted

2

-

-

-

-

E156

Job members lost

2

-

-

-

-

E157

Job reference lost

2

-

-

-

-

E158 E159 E160

Invalid Job Id No Pset In Selected Job Job select source not valid

2 2 2

-

-

-

-

E161

Line Control Alert 1

2

-

-

-

-

E162

Line Control Alert 2

2

-

-

-

-

E180

Euchner Ident System only supports Siemens 3964R protocol

2

-

-

-

-

E181

Not possible to read ID card

2

-

-

-

-

2 2 2

-

-

TNR TNR TNR

-

2

-

-

TNR

-

E205 E206

First target > Final target Final target > Tool max torque First target < XX % of tool max torque Final target < YY % of tool max torque Pset not open Pset number invalid

2 2

-

-

TNR TNR

-

E207

Wrong Pset Select Source

2

-

-

-

-

E208

Not Ok to select new Pset

2

-

-

-

-

E233

Final target range error

2

-

-

TNR

-

E234

Start final angle range error

2

-

-

TNR

-

When running a Cell Job, this is displayed by the job members when a cell job is selected on the job master. When running a Cell Job, This is displayed by the job members when a cell job is aborted. When running a Cell Job, this is displayed by the master when it has lost contact with one of its job member. When running a Cell Job, this is displayed by the job members when they have lost contact with their Job Master. When the selected job does not exist. When the selected job does not contain any Pset. Attempt to select a Job with the wrong input source. The line control has been activated, and the first control alert limit has been reached. The line control has been activated, and the second control alert limit has been reached. The protocol settings for the serial COM port 1 is not set to 3964R, it is not possible to use the Euchner Ident System with this configuration It was not possible to read the ID card inserted in the Euchner system

E200-E299: User input error E201 E202 E203 E204

An attempt was made to do a tightening with the wrong Pset within a job. Attempt to select Pset from a source not specified in the Cset. It is not allowed to select new Pset when the already selected Pset is auto selected by Job. This error code is displayed when an attempt is made to tighten with a final target out of range (larger than tool max torque or 9999). This error code is displayed when an attempt is made to tighten with a start final angle out of range.

211

Page 212

EXXX "Text"

Information

Tool locked

Tool not ready

PF not ready

Acknowledg ement

Category

Short description (graphic display)

Event code

Event codes

1 / 2 / 3 / 4 ACK / - PFNR / - TNR / - LCK "Text" /-

E235 E236

Target angle range error Configuration set inconsistent

2 3

ACK

PFNR

TNR TNR

-

E237

Strategy Configuration error

2

-

-

TNR

-

E238

Not possible to run a multistage with a click wrench Pset

2

-

-

TNR

-

E240

Password Incorrect Input Source

2

-

-

-

-

E241 E242 E250

Password Access Denied Password Locked Out Maxtime for first tightening run out (job)

2 2 2

-

-

-

-

E251

Maxtime to complete job run out

2

-

-

-

-

This error code is displayed if one device on the IO bus has the right Id but the wrong type (for example a selector is connected and a re-alarm is configured). No valid control strategy was chosen for the stored Pset. An attempt was made to perform a multistage tightening containing at least one Pset with a click wrench strategy. The password is entered from an invalid source according to the configuration.

This message is displayed and the job is terminated if the first tightening is not performed within the specified time. This message is displayed and the job is terminated if the job is not completed within the specified time.

E300-E399: Statistical errors E333

Not allowed subscription

1

-

-

-

-

E334

No statistic available for this Pset

1

-

-

-

-

E335

Not enough data

1

-

-

-

-

E336

Mem alloc fail

1

-

-

-

-

E340

Xucl tq

1

-

-

-

-

E341

Xlcl tq

1

-

-

-

-

E342

Rucl tq

1

-

-

-

-

E343

Rlcl tq

1

-

-

-

-

E344 E345 E346

Cp tq Cpk tq 7inc x tq

1 1 1

-

-

-

-

E347

7dec x tq

1

-

-

-

-

E348

7inc r tq

1

-

-

-

-

212

The requested statistic subscription is not allowed. For example it is not allowed to set an angle stat istic subscription for a Pset using only the torque control strategy. The Pset strategy is not suitable to calculate statistics (no strategy is chosen, DS control…) No enough data were available to calculate the statistic control limits. It was not possible to allocate enough memory for the statistic subscription. The last subgroup mean torque value is larger than the upper control limit. The last subgroup mean torque value is lower than the lower control limit. The last subgroup range torque value is larger than the upper control limit. The last subgroup range torque value is lower than the lower control limit. The torque Cp is lower than 2. The torque Cpk is lower than 1,33. Trend deviation alarm, the subgroup torque mean value has increased 7 times consecutively. Trend deviation alarm, the subgroup torque mean value has decreased 7 times consecutively. Trend deviation alarm, the subgroup torque range value has increased 7 times consecutively.