Page 273

Appendix D Batch Status OK (nxOK) Batch is OK (nxOK) Data type Bit

String length 1 bit

Value 0 = Not used 1 = OK

Set signal Batch done

Reset signal Start new tightening or new Pset selected

Set signal Tightening done

Reset signal Start new tightening or new Pset selected.

Cycle Complete Indicates that a tightening is finished. Do not care about the result. Data type String length Value Bit 1 bit 0 = Not used 1 = Cycle complete

Dig In # [# = 1 – 4] Mimic the status on a dig input in PF or I/O-expander. The input must be configured to FieldBus Dig In # X. There are four different Items. Data type String length Value Set signal Reset signal Bit 1 bit 0 = Input Off Dig in # X On Dig in # X Off 1 = Input On

Dset Calibration Value Shows the tool calibration value in selected engineering units. Data type String length Value Fixed Point Number 4 bytes See final torque

Set signal DsetData

Reset signal No signal

Error Code Shows error code. Data type U16

String length 2 bytes

Value Binary representation (decimal 0-65535)

Set signal Error occur

Reset signal Error Acc or Time out

String length 2 byte

Value Binary representation (Decimal 0-65 535)

Set signal Tightening done

Reset signal Start new tightening or new Pset selected

String length 4 byte

Value *

Set signal Tightening done

Reset signal Start new tightening or new Pset selected

Final Angle The final angle result Data type U16

Final Torque The final torque result Data type Fixed Point Number

* A FixedPointNumber data type is used. The value is 2 digits if torque value is less than 100, one digit if 100 <= torque value < 1000 and 0 if torque value >= 1000. For example, if torque value is 25.64, the two byte integer part shows 25 and the two byte decimal part shows 64; if torque value is 345.5, the integer part shows 345 and decimal part shows 5; if torque value is 2431, the integer part shows 2431 and decimal part shows 0. The value is represented in the selected engineering units in the Power Focus.

273

Page 274

Appendix D Job Done Status Job OK (done) or NOK (done) or aborted (reset) Data type String length Character 1 byte ASCII Bit Field

2 bits

Value O =OK N = NOK A = Aborted 00 = Not used 01 = OK 10 = NOK 11 = Aborted

Set signal Job done or reset

Reset signal Start new tightening

Value 0 = Not used 1 = Job Aborted

Set signal Job aborted

Reset signal Start new tightening

Value 0 = Not used 1 = NOK

Set signal Job done

Reset signal Start new tightening

Value 0 = Not used 1 = OK

Set signal Job done

Reset signal Start new tightening

Value 0000 0001 = Job 1 0001 0000 = Job 16 00….0001 = Job 1 00….1000 = Job 8

Set signal Job selected

Reset signal Job done

Value 0 = Job done and no job selected 1 = Job is running

Set signal Job selected

Reset signal Job done

Job Done Status Job Aborted Shows Job aborted Data type Bit

String length 1 Bit

Job Done Status NOK Job is NOK (Not all tightening OK) Data type String length Bit 1 bit

Job Done Status OK (nxOK) Job is OK (nxOK) Data type Bit

String length 1 bit

Job ID Gives the number on the selected JOB Data type String length Bit Field 2 – 8 bits in the same byte. U16 16 bits in one word

Job Running A job is selected and “running” Data type String length Bit 1 bit

Line Control Alerted 1 Indicates Line Control Alert1 received by PF Data type String length Bit 1 Bit

274

Value Set signal 0 = Not used Line control alerted 1 1 = LineControlAlerted1

Reset signal Start new tightening

Page 275

Appendix D Line Control Alerted 2 Indicates Line Control Alert2 received by PF. Data type String length Bit 1 Bit

Value Set signal 0 = Not used Line control alerted 2 1 = LineControlAlerted2

Reset signal Start new tightening

Line Control Done Indicates job with line control finished before line control alert2 inputted. Data type String length Value Bit 1 Bit 0 = Not used 1 = LineControlDone

Set signal Line control done

Reset signal Start new tightening

Value 0 = Not used 1 = LineControlStart

Set signal Line control started

Reset signal Start new tightening

Value 0000 0001 = Pset 1 0001 0000 = Pset 16 00….0001 = Pset 1 00….1000 = Pset 8

Set signal Pset selected

Reset signal No signal. On until new Pset is selected.

Set signal Pset selected

Reset signal No signal. On until new Pset is selected.

Value 0000 0001 = CH 1 0001 0000 = CH 16 00….0001 = CH 1 00….1000 = CH 8

Set signal PF ready and channel ID programmed in Config.

Reset signal No signal

Value 0 = Errors in PF 1 = No errors in PF

Set signal PF ready (no errors)

Reset signal PF not ready (errors)

Line Control Started Indicates Line Control Start set in PF. Data type String length Bit 1 Bit

New Pset selected Running Pset number. Data type Bit Field U16

String length 2 – 8 bits in the same byte. 16 bits in one word

New Pset Selected 0 Is 1 Running Pset number. Number 0 = Pset 1 number 1 = Pset 2 etc. Data type String length Value Bit Field 2 – 8 bits in the same 0000 0001 = Pset 2 byte. 0001 0000 = Pset 17

PF Channel ID Gives the channel ID number on the FieldBus PF. Data type String length Bit Field 2 – 8 bits in the same byte. U16 16 bits in one word

PF Ready No severe errors in PF. Data type String length Bit 1 bit

Pset Final Angle Min / Final Angle Max / Step 1 Speed / Step 2 Speed Shows Pset parameters from the running Pset Data type String length U16 2 bytes

Value Binary representation (decimal 0-65535)

Set signal New Pset selected or updated

Reset signal No signal. On until new Pset is selected or current Pset updated.

275

Page 276

Appendix D Pset Final Target / Final Torque Min / Final Torque Max / Start Final Angle Shows Pset parameters from the running Pset in selected engineering units. Data type String length Value Set signal Fixed Point 4 bytes See final torque New Pset selected or updated

Reset signal No signal. On until new Pset is selected or current Pset updated.

PVT Mon status / Run Down Angle status / Self-tap status Status on one of the result parameters PVT mon / rundown angle or SelfTap. Data type String length Value Set signal Character 1 byte ASCII O = OK Tightening result L = Low H = High Bit Field 2 bits 00 = Not used 01 = OK 10 = High 11 = Low

Reset signal Start new tightening or new Pset selected.

PVT Mon Status- / Run Down Angle status- / Self-tap Status- HIGH A result is above max limit. There are three different variables in the set-up. Data type String length Value Set signal Bit 1 bit 0 = Not used Tightening result 1 = High

Reset signal Start new tightening or new Pset selected.

PVT Mon Status- / Run Down Angle status- / Self-tap Status- LOW A result is below min limit. There are three different items in the set-up. Data type String length Value Bit 1 bit 0 = Not used 1 = Low

Set signal Tightening result

Reset signal Start new tightening or new Pset selected.

PVT Mon Status- / Run Down Angle status- / Self-tap Status- OK A result is within limits. There are three different variables in the set-up. Data type String length Value Bit 1 bit 0 = Not used 1 = OK

Set signal Tightening result

Reset signal Start new tightening or new Pset selected.

Set signal Received Identifier

Reset signal Start new tightening

Received Identifier Indicates identifier has been received by PF Data type String length Bit 1 Bit

Value 0 = not used 1 = Received identifier

Service Indicator Alarm Indicates that the number of tightenings in the tool memory has reached the service interval limit. Data type String length Value Set signal Bit 1 bit 0 = Alarm Off Service indicator alarm 1 = Alarm On on

Reset signal Reset counter

Sync Channel # Green / Red / Yellow Led [# = 1 – 10] A result from a sync channel. Follow tool light. There are 30 (3x10) different items in the set-up. Data type String length Value Set signal Bit 1 bit 0 = Not used Tightening result 1 = green / red / yellow

276

Reset signal Start new tightening or new Pset selected

Page 277

Appendix D Tightening Time The tightening time taken from the most recent result. Format HH:MM:SS Data type String length Value Character s tring 64 bit (8 characters) i.e. 08:15:08 (8 ASCII change characters) 24 hour

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Tightening Time Hour The tightening time (hour part only) taken from the most recent result. Data type String length Value U16 16 bit (one word) 0 - 24 hour

Tightening Time Min The tightening time (minutes only) taken from the most recent result. Data type String length Value U16 16 bit (one word) 0 - 60 min

Tightening Time Sec The tightening time (seconds only) taken from the most recent result. Data type String length Value U16 16 bit (one word) 0 - 60 sec

Tightening Date The tightening date taken from the most recent result. Format YYYY:MM:DD Data type String length Value Character string 80 bit (10 characters/ i.e. 2000:05:07 (10 ASCII change bytes) characters)

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Tightening Date Day The tightening date (day part only) taken from the most recent result. Data type String length Value U16 16 bit (one word) 1 – 31

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Tightening Date Month The tightening date (month part only) taken from the most recent result. Data type String length Value U16 16 bit (one word) 1 – 12

Tightening Date Year The tightening date (year part only) taken from the most recent result. Data type String length Value U16 16 bit (one word) Year number 4 digits

277

Page 278

Appendix D Tightening Status Combined status for all tightening result parameters that is used. All results OK = OK. One or more NOK = NO Data type String length Value Character 1 byte ASCII OK = O NOK = N Bit Field 2 bits 00 = Not used 01 = OK 10 = NOK

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Value 0 = Not used 1 = OK

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Value 0 = Tool enabled 1 = Tool disabled

Set signal Tool disable

Reset signal Tool enable

Value 0 = Tool disabled 1 = Tool enabled

Set signal Tool enable

Reset signal Tool disable

Value 0 = Not used 1 = Green

Set signal Tightening result or flash green light

Reset signal Start new tightening or Reset Led

Value 0 = Not used 1 = Red

Set signal Tightening result

Reset signal Start new tightening

Value 0 = Not used 1 = Yellow

Set signal Tightening result or fatal error*

Reset signal Start new tightening or error Ack*

Tightening Status NOK Tightening result have one or more Not OK results. Data type String length Value Bit 1 bit 0 = Not used 1 = NOK

Tightening Status OK All tightening result are OK. Data type String length Bit 1 bit

Tool Disabled Indicates if the tool is disabled or not. Data type String length Bit 1 bit

Tool Enabled Indicates if the tool is enabled or not. Data type String length Bit 1 bit

Tool Green Light This item follows the tool green light. Data type String length Bit 1 bit

Tool Red Light This item follows the tool red light. Data type String length Bit 1 bit

Tool Yellow Light This item follows the tool yellow light. Data type String length Bit 1 bit

* If ”PF_Control_3” is selected in Cset, yellow led shows the fatal error and reset when error acknowledged.

278

Page 279

Appendix D Tool Loosening Indicates that the tool is loosening. Data type String length Bit 1 bit

Value Set signal 0 = Tool is not loosening Tool is loosening 1 = Tool is loosening

Reset signal Tool is stopped

Value 0 = Tool is not ready 1 = Tool is ready

Set signal Tool is ready

Reset signal Tool is not ready

Value 0 = Tool is not run 1 = Tool is running

Set signal Tool is running

Reset signal Tool is stopped

Value 0 = Tool is not tighten 1 = Tool is tightening

Set signal Tool is tightening

Reset signal Tool is stopped

Value O= OK L = Low H = High 00 = Not used 01 = OK 10 = High 11 = Low

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Value 0 = Not used 1 = High

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Value 0 = Not used 1 = Low

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Value 0 = Not used 1 = OK

Set signal Tightening result

Reset signal Start new tightening or new Pset selected

Tool Ready Indicates that the tool is ready for tightening. Data type Data length Bit 1 bit

Tool Running Indicates that the tool is rotating CW or CCW. Data type String length Bit 1 bit

Tool Tightening Indicates that the tool is tightening. Data type String length Bit 1 bit

Torque Status Status torque result. Data type Character

String length 1 byte ASCII

Bit Field

2 bits

Torque Status HIGH Torque result is above max limit Data type String length Bit 1 bit

Torque Status LOW Torque result is below min limit Data type String length Bit 1 bit

Torque Status OK Torque result is within limits Data type String length Bit 1 bit

279

Page 280

Appendix D VIN Input Shows the VIN number inputted from FieldBus, serial or Ethernet. Changes as soon as the number is given. This is not the VIN used in the tightening result. Data type String length Value Set signal Reset signal Character string input 24 – 208 bit (3-26 bytes) One ASCII sign for New VIN input No signal. On until each character.* new Vin is inputted First byte is counter. Character string 16 – 200 bit (2-25 bytes) One ASCII sign for change each character *

VIN Used In Tightening Shows the VIN number used in a tightening. This is the VIN used in the tightening result. Data type String length Value Set signal Character string 16 – 200 bit (2-25 bytes) One ASCII sign for each Tightening result change character**

Reset signal Start new tightening Or new Pset selected

* If the VIN is longer then the VIN input length the Power Focus will take the first x characters and cut the end. If the VIN number is shorter then this parameter length the Power Focus will not fill with zero.

280

Page 281

Appendix D

24.4

Items to PF

This section contains a description of the items that can be selected when data to the Power Focus is configured. Set signal = when a bit is set in the PLC, this signal is sent to PF. Reset signal = when a bit resets in the PLC, this signal is sent to PF. Abort Job Aborts the running Job. Data type String length Bit 1 bit Character

8 bit (1 byte)

Value 0 = Not used 1 = Abort A = Abort

Set signal Abort job

Reset signal No signal

Value 0 = Not Used 1 = Ack Error

Set signal Ack error message

Reset signal No signal

Value 0 = Not used 1 = Decrement

Set signal Batch decrement

Reset signal No signal

Value 0 = Not used 1 = Increment

Set signal Batch increment

Reset signal No signal

Set signal Bypass Pset

Reset signal No signal

Ack Error Message Acknowledge error message Data type String length Bit 1 bit

Batch Decrement Decrement the batch counter with one. Data type String length Bit 1 bit

Batch Increment Increment the batch counter with one Data type String length Bit 1 bit

Bypass Pset In Job Stop current Pset and jump to next Pset in the Job. Data type String length Value Bit 1 bit 0 = Not used 1 = Bypass Pset in job

281

Page 282

Appendix D Identifier Input the VIN number from the PLC. To get this working you must set identifier input source in PF to FieldBus. Data type String length Value Set signal Reset signal Character string input 24 – 208 bit (3-26 bytes) One ASCII sign for New VIN input No signal each character. First byte is counter. Character string 16 – 200 bit (2-25 bytes) One ASCII sign for change each character U16 2 bytes in the same word * U32 4 bytes in two words ** U32_HNW 4 bytes in two words

*U 16: If the value is less then 5 digits decimal, PF will fill with zeroes in front. ** U32: If the value is less then 10 digits decimal, PF will fill with zeroes in front.

Job Select Select a Job. Job select source must be set to FieldBus. Job 0 = no job selected. Data type String length Value Set signal Bit Field 2 – 8 bits in the same 0000 0001 = job 1 Job select byte. 0001 0000 = job 16 U16 16 bits in one word 00….0001 = job 1 00….1000 = job 8

Reset signal No signal

Job Off Gets off job mode and unlocks tool. Data type String length Bit 1 bit

Value 0 = Job On 1 = Job Off

Set signal Job Off

Reset signal Job On

Value 0 = Not Used 1 = Line Control alert 1

Set signal Line control alert 1

Reset signal No signal

Value 0 = Not Used 1 = Line Control alert 2

Set signal Line control alert 2

Reset signal No signal

Value 0 = Not Used 1 = Line Control

Set signal Line control start

Reset signal No signal

Line Control Alert 1 Job not finished alarm 1 Data type String length Bit 1 bit

Line Control Alert 2 Job not finished alarm2 Data type String length Bit 1 bit

Line Control Start Input signal to start the line control function Data type String length Bit 1 bit

282