Page 283

Appendix D PSET Select Select a PSET. PSET select source must be set to FieldBus. PSET0 = no Pset selected. Data type String length Value Set signal Bit Field 2 – 8 bits in the same 0000 0001 = Pset 1 PSET select byte. 0001 0000 = Pset 16 U16 16 bits in one word 00….0001 = Pset 1 00….1000 = Pset 8

Reset signal No signal

PSET select 0 Is 1 Select a PSET. PSET select source must be set to FieldBus. PSET0 = no Pset selected. Number 0 = Pset 1 number 1 = Pset 2 etc. Data type String length Value Set signal Bit Field 2 – 8 bits in the same 0000 0001 = Pset 2 PSET select byte. 0001 0000 = Pset 17

Reset signal No signal

Relay Pos # [# = 1 – 4] Control a relay from FieldBus. In I/O set-up the selected relay must be programmed to FieldBus relay x. There are four different items. Data type String length Value Set signal Reset signal Bit 1 bit 0 = Rely OFF Set FieldBus relay x Reset FieldBus relay x 1 = Relay ON

Reset Batch Reset the batch c ounter to 0. Data type String length Bit 1 bit

Value 0 = Not used 1 = Reset the batch

Set signal Reset batch

Reset signal No signal

Set signal Reset result status

Reset signal No signal

Set signal Restart job

Reset signal No signal

Reset Result Status Reset all result status on relay, re-alarm and FieldBus. Data type String length Value Bit 1 bit 0 = Not Used 1 = Reset result

Restart Job Stop current job and restart the same job from 0. Data type String length Value Bit 1 bit 0 = Not used 1 = Restart job

Tool Disable Disable the tool. To avoid conflicts this parameter shall not be selected if Tool Enable is used. Data type String length Value Set signal Bit 1 bit 0 = Enable tool Tool disable 1 = Disable tool

Reset signal Tool Enable

Tool Enable Enable the tool. To avoid conflicts this parameter shall not be selected if Tool Disable is used. Data type String length Value Set signal Bit 1 bit 0 = Disable tool Tool enable 1 = Enable tool

Reset signal Tool disable

283

Page 284

Appendix D Tool Lights Flash Green Starts to flash the tool green light. Resets any existing light pattern on the tool. Data type String length Value Set signal Bit 1 bit 0 = Not used Tool light flash green 1 = Tool light flash

Reset signal No signal

Tool Start Loosening Start the tool in loosening direction. Direction depends on CW / CCW in PF. Tool start input source must be set to FieldBus. Data type String length Value Set signal Reset signal Bit 1 bit 0 = Stop tool Start loosening Stop tool 1 = Start loosening

Tool Start Tightening Start the tool in tightening direction. Direction depends on CW / CCW in PF. Tool start input source must be set to FieldBus. Data type String length Value Set signal Reset signal Bit 1 bit 0 = Stop tool Start tightening Stop tool 1 = Start tightening

Tool stop Stops the tool. Data type Bit

284

String length 1 bit

Value 0 = Not used 1 = Stop tool

Set signal Stop tool

Reset signal No signal

Page 285

Appendix D

24.5

Profibus-DP

Profibus DP is a FieldBus normally used in industrial automation, to transfer fast data for motor controllers, MMI, I/O units and other industrial equipment. Profibus has an international user organisation called Profibus International, PI, and other local and national organisations. General technical questions regarding the FieldBus should be addressed to your local Profibus User Group in the first instance. A contact address list is available on the Profibus Internet site; www.Profibus.com. For general help on Profibus, contact Profibus International on: Profibus_international@compuserve.com. Power Focus Profibus DP description Protocol & Supported Functions

• • • •

FieldBus type: PROFIBUS DP EN 50 170 (DIN 19245) Protocol version: ver. 1.10 Protocol stack supplier: SIEMENS Auto baud rate detection supported. Baud rate range: 9.6 kbit-12Mbit

Physical Interface

• • • • • •

Transmission media: ProfiBus bus line, type A or B specified in EN50170 Topology: Master-Slave communication FieldBus connectors: 9 pin female DSUB (standard) Cable: Shielded copper cable, Twisted pair Isolation: The bus is galvanically separated from the other electronics with an on board DC/DC converter. Bus signals (A-line and B- line) are isolated via optics couplers. Profibus DP communication ASIC: SPC3 chip from Siemens

285

Page 286

Appendix D Facts in brief

The table below gives a brief summary of facts for Power Focus ProfiBus DP module. Variable Node Address

Limits 1 – 124 (1-99 with HW setting)

Information Set Switches to 00 if you want to set the node address from SW (TTPF)

Number of nodes in a Profibus-DP network Max 126

Baud rate Data to PF length Data from PF length The module only supports cyclic I/O data transmission

Automatic (9.6 kbaud – 12 Mbaud) Automatically set from PLC at connection 0 - 122 bytes * Must be the same in PF and PLC 0 - 122 bytes * Must be the same in PF and PLC

* The string length in PF is limited to 122 bytes. Profibus-DP standard allows 244 bytes.

Hardware

FieldBus Connectors

The Profibus-DP standard EN 50170 (DIN 19245) recommends the use of a 9 pin female D-sub connector. Depending on the protection class and type of application, other connector designs are also allowed.

286

Page 287

Appendix D Connector 9-pin female DSUB Pin Housing 1 2 3 4 5 6 7 8 9

Name Shield Not connected Not connected B-Line RTS GND BUS +5V BUS Not connected A-Line Not connected

Function Connected to PE

Positive RxD/TxD according to RS485 specification Request to send * Isolated GND from RS484 side* Isolated +5V from RS484 side* Negative RxD/TxD according to RS485 specification

* +5V BUS and GND BUS are used for bus termination. Some devices, like optical transceivers (RS485 to fibre optics) may require an external power supply from these pins. Node Address

Node addresses are set with the two rotary switches on the FieldBus module, this enables address settings from 1-99 in decimal form. Switch 1 x10 Switch 2 x1 (See switches on the top drawing) Example : Address = (Left Switch Setting x 10) + (Right Switch Setting x 1) Left switch is set to 5 and right switch is set to 2. This gives a node address of 52. If you want to set the node address from ToolsTalk the switches must be set to 00. Note! The node address cannot be changed when the power is switched on. Baud rate

The baud rate on a Profibus DP network is set during configuration of the master and only one baud rate is possible in a Profibus DP installation. As the Power Focus Profibus DP module has an auto baud rate detection function, you will not have to configure the baud rate on the module. Baud rates supported by the Power Focus Profibus-DP module are:

9.6 kbit/s 187.5 kbit/s 3 Mbit/s

19.2 kbit/s 500 kbit/s 6 Mbit/s

93.75 kbit/s 1.5 Mbit/s 12 Mbit/s

287

Page 288

Appendix D Functionality of the indication LEDs

The module is equipped with four bicolour LEDs, used for debugging purposes. The function of the LEDs are described in the table and figure below. Name FieldBus Diagnostics (LED 4)

Colour Red

On-Line (LED 2)

Green

Off-Line (LED 3)

Red

Function Indicates certain faults on the FieldBus side. Flashing Red 1 Hz - Error in configuration: IN and/or OUT length set during initialisation of the module is not equal to the Length set during configuration of the network. Flashing Red 2 Hz - Error in User Parameter data: The Length/contents of the User Parameter data set during initialisation of the module is not equal to the length/contents set during configuration of the network. Flashing Red 4 Hz– Error in initialisation of the Profibus communication ASIC. Turned Off - No diagnostics present Indicates that the module is On-Line on the FieldBus. Green - Module is On-Line and data exchange is possible. Turned Off – Module is not On-Line Indicates that the module is Off-Line on the FieldBus. Red - Module is Off-Line and no data exchange is possible. Turned Off – Module is not Off-Line

Bus termination

The end nodes in a Profibus DP network have to be terminated to avoid reflections on the bus line. Use cable connectors with built- in termination. GSD file

Each device on a Profibus DP network is associated with a GSD file, containing all necessary information about the device. The network configuration program during configuration of the network uses this file. Contact your local Atlas Copco company for a copy of the GSD file File name: pf3profb.gsd Icon file

Contact you local Atlas Copco representative to get a copy of the Icon file for Power Focus. This file can be used to have a PF Icon in PLC configuration SW. The file is a bitmap. File name: pf3profb.bmp

288

Page 289

Appendix D

24.6

DeviceNet

DeviceNet is used for industrial automation, normally for the control of valves, sensors and I/O units and other automation equipment. The DeviceNet communication link is based on a broadcast-oriented communications protocol, Controller Area Network (CAN). This protocol has I/O response and high reliability even for demanding applications, e.g. brake control. DeviceNet has a user organisation, the Open DeviceNet Vendor Association (ODVA) that assists members in matters concerning DeviceNet. Website: http://www.ODVA.org The media for the FieldBus is a shielded copper cable composed of one twisted pair and two cables for the external power supply. The baud rate can be changed between 125k, 250k and 500kbit/s. This can be done in two different ways. The first is simply by using the DIP switch, second is via SW configuration. There are several different DeviceNet Scanners available on the market, both for PLC systems and for PCs. Power Focus DeviceNet description Facts in brief

The table below provides a brief summary of facts for the Power Focus DeviceNet module. Variable Node Address (Mac ID) Number of nodes in a DeviceNet network Connection modes supported

Baud rate

Data to PF length Data from PF length

Limits 0-63 Max 63 Polled I/O Bit strobe I/O Change of status/ cyclic I/O 125kbit/sec (Default) 250kbit/sec 500kbit/sec 0 – 122 bytes * 0 – 122 bytes *

Information

Use same as in PLC

Must be the same in PF and PLC Must be the same in PF and PLC

* The data string is in PF limited to 122 bytes. DeviceNet standard allows 255 bytes.

289

Page 290

Appendix D Configuration

In a DeviceNet network, each node has a Mac ID (the address in the network). The Mac ID is a number between 0 and 63. Each node’s Mac ID has to be unique, since it is used to identify the node. In a DeviceNet network you can also set Baud rate, with the following baud rates being available: 125, 250 and 500 kbit / sec. All nodes in the network have to communicate at the same baud rate. On the Power Focus DeviceNet module it is possible to set the Mac ID and Baud rate using DIP switches mounted on the module or from SW using TTPF. Dip 1 and 2 are used to set the Baud rate and dips 3 to 8 are used to configure the node address (Mac ID). Dip 1 is the most significant bit on the DIP switch. See table on the next page. The Power Focus DeviceNet module is implemented in compliance with the ODVA specification for a Communication adapter (profile no 12). It acts as a “group two only server” on the DeviceNet network. Hardware

LED 1: Not used LED 2: Network status LED 3: Module status LED 4: Not used

290

Page 291

Appendix D Function AD0 AD1 AD2 AD3 AD4 AD5 BD2 BD1

DipSwitch # 8 7 6 5 4 3 2 1

On = 1 Off = 0 Baud rate Bit/sec 125k 250k 500k Reserve (SW-setting)

Dip 1 - 2

Address

Dip 3 – 8

00 01 10 11

0 1 2 3 … 62 63

000 000 000 001 000 010 000 011 … 111 110 111 111

Mac ID (Node Address)

If you want to set the Mac ID from TTPF all dip switches must be set to On (11 111 111). Note! The Mac ID cannot be changed when the power is switched on. FieldBus Connector

Connector 5-pin 5.08mm detachable screw terminal Pin 1 2 3 4 5

Colour code Black Blue Bare White Red

Description VCAN-L Shield CAN-H V+

Note! V- and V+ must come from a fully isolated power supply. That means that the voltage cannot have any reference to ground. This is to prevent the bus from interference caused by ground loop problems. If V- and V+ are sourced from a PF internal 24VDC (screw terminal) the same connection shall only power one DeviceNet module. This means that the DeviceNet cable connected to the PF must not include voltage wires. Normally you have a central power supply that feeds all nodes in the network.

291

Page 292

Appendix D Power consumption

Current consumption at 24 VDC (V- to V+) is max 70 mA at power up and 25-30 mA continuously. Functionality of the indication LEDs

The module is equipped with four bicolour LEDs, used for debugging purposes. The function of the LEDs is described in the table and figure below. LED # 1: Not used 2: Network status 3: Module status 4: Not used LED# 3: Module status 3: Module status 3: Module status 3: Module status 2: Network status 2: Network status 2: Network status 2: Network status 2: Network status

Condition Off Steady red Steady green Flashing red Off Steady green Steady red Flashing green Flashing red

Description No Power Unrecoverable fault Device operational Minor fault Not powered / Not on line Link OK on line. Connected Critical link failure On line not connected Connection time out

Bus termination Termination of the FieldBus requires a terminating resistor at each end of the FieldBus. These resistors should have a value of 121 ohm. EDS file

Each device on a DeviceNet network is associated with an EDS file, containing all necessary information about the device. The network configuration program during configuration of the network uses this file. Contact your local Atlas Copco representative for a copy of the EDS file. File name: pf3devn.eds Icon file

Contact you local Atlas Copco representative to get a copy of the Icon file for Power Focus. This file can be used to have a PF Icon in PLC configuration SW. File name: pf3devn.ico

292