One-page AutomationDirect sheet with the I/O specifications and wiring diagram of the DL06 version D0-06DR. It gives its AC power supply rating, DC input and relay output specifications, equivalent input and output circuits, a derating chart for the relay outputs and typical relay life. Only the D0-06DR is covered.
- Version
- D0-06DR: DL06 with DC inputs and relay outputs p. 1
- Power supply
- D0-06DR: 100-240VAC (40VA) p. 1
- High-speed inputs
- D0-06DR: X0-X3 are high-speed inputs; X4-X23 are standard inputs p. 1
- Relay outputs
- D0-06DR: outputs Y0 - Y17, maximum voltage 264VAC, 30VDC p. 1
- Relay current
- D0-06DR: 2A per point, 6A per common p. 1
What this sheet walks you through
- Wiring power, inputs and outputs of the D0-06DR p. 1
- Estimating relay life by load type and current p. 1
Good to know
- The relay outputs carry no fuses; external fuses are recommended. p. 1
- Auxiliary 24VDC current is given on a Power Budgeting page (2–29) that is not part of this sheet. p. 1
Questions this sheet answers
The file
Size and text
Every page · 1
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 1
Open in the PDF
The text of page 1, from the PDF itself
DL06 I/O Specifications D0-06DR
<--->
Note: Refer to page 2–29, Power Budgeting, for Auxillary 24VDC current available.
Wiring diagram and specifications
Power input wiring
D0-06DR Specifications AC Power Supply Voltage Range Specifications Number of Input Pts. Number of Commons Input Voltage Range
100-240VAC (40VA) 20 (sink/source) 5 (isolated) 12-24VDC (X0-X3) 1.8K @ 12-24VDC (X4-X23) 2.8K @ 12-24VDC
Input Impedance
DC Input Specifications
Output point wiring
On Current/ Voltage Level OFF Current/ Voltage Level Response Time OFF to ON Response ON to OFF Response Fuses Number of Output Points Number of Commons
>5mA/10VDC <0.5mA/<2VDC X0-X3
X4-X23
<100µs <8ms <100µs <8ms None 16 4 (isolated) 6-240VAC,
Output Voltage Range 47-63Hz
Input point wiring
6-27VDC
Relay Output Specifications
Maximum Voltage264VAC,30VDCMaximum Current2A/point 6A/common
Maximum Leakage Current Smallest Recommended Load OFF to ON Response ON to OFF Response Status Indicators Fuses
Equivalent input circuit, Standard inputs (X4-X23)
Equivalent input circuit, High-speed inputs (X0-X3)
0.1mA @ 246VAC 5mA @ 5VDC <15ms <10ms Equivalent output circuit
Logic side None (external recommended)
Derating chart for relay outputs
Y0 - Y17
Typical Relay Life (Operations) at Room Temperature
2–46
PLC Products
Voltage and Type of Load
Load Current At 1A At 2A
24 VDC Resistive500K24 VDC Inductive100K50K110 VAC Resistive500K250K110 VAC Inductive200K100K220 VAC Resistive350K200K220 VAC Inductive100K50K250K01737-824600