One-page AutomationDirect sheet with the I/O specifications and wiring diagram of the DL06 version D0-06DR. It gives its AC power supply rating, DC input and relay output specifications, equivalent input and output circuits, a derating chart for the relay outputs and typical relay life. Only the D0-06DR is covered.

Version
D0-06DR: DL06 with DC inputs and relay outputs p. 1
Power supply
D0-06DR: 100-240VAC (40VA) p. 1
High-speed inputs
D0-06DR: X0-X3 are high-speed inputs; X4-X23 are standard inputs p. 1
Relay outputs
D0-06DR: outputs Y0 - Y17, maximum voltage 264VAC, 30VDC p. 1
Relay current
D0-06DR: 2A per point, 6A per common p. 1

What this sheet walks you through

  • Wiring power, inputs and outputs of the D0-06DR p. 1
  • Estimating relay life by load type and current p. 1

Good to know

  • The relay outputs carry no fuses; external fuses are recommended. p. 1
  • Auxiliary 24VDC current is given on a Power Budgeting page (2–29) that is not part of this sheet. p. 1

Questions this sheet answers

What power does the D0-06DR need?

The sheet gives an AC power supply range of 100-240VAC at 40VA. p. 1

How much current can a D0-06DR relay output switch?

2A per point and 6A per common. p. 1

Which D0-06DR inputs are high-speed?

Inputs X0-X3 are the high-speed inputs; X4-X23 are standard inputs. p. 1

The file

Size and text

Pages1
PDF251 KB
TextText from the PDF itself.

Every page · 1

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of AutomationDirect Direct Logic DL06 Spec Sheet

The text of page 1, from the PDF itself

DL06 I/O Specifications D0-06DR

<--->

Note: Refer to page 2–29, Power Budgeting, for Auxillary 24VDC current available.

Wiring diagram and specifications

Power input wiring

D0-06DR Specifications AC Power Supply Voltage Range Specifications Number of Input Pts. Number of Commons Input Voltage Range

100-240VAC (40VA) 20 (sink/source) 5 (isolated) 12-24VDC (X0-X3) 1.8K @ 12-24VDC (X4-X23) 2.8K @ 12-24VDC

Input Impedance

DC Input Specifications

Output point wiring

On Current/ Voltage Level OFF Current/ Voltage Level Response Time OFF to ON Response ON to OFF Response Fuses Number of Output Points Number of Commons

>5mA/10VDC <0.5mA/<2VDC X0-X3

X4-X23

<100µs <8ms <100µs <8ms None 16 4 (isolated) 6-240VAC,

Output Voltage Range 47-63Hz

Input point wiring

6-27VDC

Relay Output Specifications

Maximum Voltage264VAC,30VDCMaximum Current2A/point 6A/common

Maximum Leakage Current Smallest Recommended Load OFF to ON Response ON to OFF Response Status Indicators Fuses

Equivalent input circuit, Standard inputs (X4-X23)

Equivalent input circuit, High-speed inputs (X0-X3)

0.1mA @ 246VAC 5mA @ 5VDC <15ms <10ms Equivalent output circuit

Logic side None (external recommended)

Derating chart for relay outputs

Y0 - Y17

Typical Relay Life (Operations) at Room Temperature

2–46

PLC Products

Voltage and Type of Load

Load Current At 1A At 2A

24 VDC Resistive500K24 VDC Inductive100K50K110 VAC Resistive500K250K110 VAC Inductive200K100K220 VAC Resistive350K200K220 VAC Inductive100K50K250K01737-824600