Page 55
E–11 RSNetWorxt Setup
EDS Wizard complete.
Go on line
You will want to go on line with the network now. In the main RSNetWorx window,
Appendix C Error Codes
1. Click on Network to select Online.
2. Select your network from the pop–up window. 3. Click OK.
Appendix E RSNetWorx Setup
Page 56
E–12 RSNetWorxt Setup
This message will appear. 4. Click OK.
Browsing network message.
Once the nodes are found, each node icon will appear on the RSNetWorx window.
Appendix C Error Codes
After all of the nodes have been found, browse can be cancelled.
Set up I/O parameters
Now you can set up the I/O paramerters for the devices. The scanner needs to be configured first. This is done by accessing the scanner properties.
Appendix E RSNetWorx Setup
1. Selecting the scanner module can be done in two different ways. Either click on the scanner name and right click the mouse or click on Device then click on Properties in the pop–up window.
Page 57
E–13 RSNetWorxt Setup
The properties window will appear. 2. Click Module.
3. Click Upload.
Appendix C Error Codes
Uploading network information.
Note: Do not cancel. The entire network data must be allowed to upload. The data appears. 4. Select the correct slot number which the DeviceNet scanner module is residing.
5. Click Scanlist.
Appendix E RSNetWorx Setup
Page 58
E–14 RSNetWorxt Setup
If the node that you want is not in the Scanlist, it needs to be moved to the list. 6. Highlight T1K–DEVNETS 7. Click the right arrow.
Appendix C Error Codes
Now that T1K–DEVNETS is in the list, be sure that it is selected. 8. Click Edit I/O Parameters.
Appendix E RSNetWorx Setup
9. Set the Rx Size and the Tx Size to match the polled data size for the number of I/O bytes (refer to tables in Appendix C). 10. Click OK.
Refer to page E–18 (Set Class Instance Attribute) if the total number of Rx and Tx bytes are not known.
Page 59
E–15 RSNetWorxt Setup
This window will appear. 11. Click Yes.
Map the nodes
Map each node. 1. Click the Input tab in the properties window. Be sure that T1K–DEVNETS is selected. 2. Select Discrete for Memory, and 0 for Start Word. 3. Click AutoMap.
NOTE: M file is used with explicit messaging. Appendix C Error Codes
At the completion of the input AutoMapping, the window will look like this example. The T1K–DEVNETS node is now shown.
Appendix E RSNetWorx Setup
Page 60
E–16 RSNetWorxt Setup
Now, map the outputs just the way you mapped the inputs. This time: 1. Click the Output tab in the properties window. Be sure that T1K–DEVNETS is selected. 2. Select Discrete for Memory, and 0 for Start Word.
Appendix E RSNetWorx Setup
Appendix C Error Codes
3. Click AutoMap.
At the completion of the output AutoMapping, the window will appear like this example. The T1K–DEVNETS node is now shown.
Page 61
E–17 RSNetWorxt Setup
Download the scanlist to the scanner. 1. Select the Scanlist tab in the properties window. 2. Select Download to Scanner. In the pop–up window: 3. Check All Records, then 4. Click Download.
Note: Verify that the processor is in program mode before downloading the scanlist.
Appendix C Error Codes
This is an error message that may appear.
When the download indication ends, download is complete.
Appendix E RSNetWorx Setup
Page 62
E–18 RSNetWorxt Setup
Set Class Instance Use the Service Class Instance Attribute Editor to set the I/O to read and write to the T1K –DEVNETS. Attribute 1. Select the T1K–DEVNETS node. Either click on Device or right click on the node symbol in theRSNetWorx window.
Appendix C Error Codes
2. Select Class Instance Editor in the pop–up window.
3. Setup input attributes in this window. Object Address must be set to: Class = 5, Instance = 2, Attribute = 7 Size = Word (2 bytes).
Appendix E RSNetWorx Setup
4. Click on Execute. Read the data here.
Page 63
E–19 RSNetWorxt Setup
5. Setup output attributes in this window. Object Address must be set to: Class = 5, Instance = 2, Attribute = 8 Size = Word (2 bytes). 6. Click on Execute. Read the data here.
Appendix C Error Codes Appendix E RSNetWorx Setup