Page 46
E–2 RSNetWorxt Setup
Setup T1K–DEVNETS with RSNetWorxt For those who are using the T1K–DEVNETS as a slave with an Allen–Bradley PLC, the examples on the following pages have worked for us, and will be a guide for you. These steps should help you through the process of setting up your Allen–Bradley DeviceNet network using RSNetWorxt. If you encounter any difficulties with the setup process, please contact your local Rockwell International representative. RSLinx
Begin by opening your RSLinx to configure the DeviceNet driver. 1. Click on Communications.
Appendix C Error Codes
2. Click on Configure Drivers.
3. Click on the down arrowhead, , and select a driver from the drop–down list. 4. Click Add New.
Appendix E RSNetWorx Setup
A DF1 driver is selected in this example.
Note: Selecting a new driver may prompt you to reboot or to restart your computer.
Page 47
E–3 RSNetWorxt Setup
5. Click OK in the pop–up window.
This window will appear. 6. Click on Auto–Configure to setup the communication parameters.
Appendix C Error Codes
Auto Configuration Successfull will appear. 7. Click OK.
Appendix E RSNetWorx Setup
Page 48
E–4 RSNetWorxt Setup
The Configure Drivers window will now appear showing the Status as Running.
The next step is to add a DeviceNet driver.
Appendix C Error Codes
8. Click on the down arrowhead, , and select your choice of drivers from the drop–down list. 9. Click on Add New.
This window will appear.
Appendix E RSNetWorx Setup
10. Select the proper driver, then click Select.
Page 49
E–5 RSNetWorxt Setup
The DeviceNet Interface Configuration window will appear briefly.
This window will appear for you to setup the pass through port. Be sure that you select the proper slot where the scanner module is located.
Appendix C Error Codes
If this does not match, you will need to reconfigure the I/O in RSLogix.
11. Type in a name for the driver, then click OK.
This window will appear indicating that both drivers are Running.
Appendix E RSNetWorx Setup
Page 50
E–6 RSNetWorxt Setup
RSLogix
You are ready to connect to the PLC using your RSLogix software. 1. Click on Communications and select Who Active Go Online.
2. When this window appears, select the PLC to connect to.
Appendix C Error Codes
3. Click OK.
This window will appear with the relay ladder program. You now want to configure the I/O. This must be done OFFLINE in order to change the configuration.
Appendix E RSNetWorx Setup
4. Select I/O Configuration.
Page 51
E–7 RSNetWorxt Setup
The I/O Configuration window will come into view. When you select the scanner module, verify that it is in the correct slot. 5. Click Adv Config.
The Advanced I/O Configuration window will appear. The M0 and M1 Lengths will show the default of 256. Change this to 361. 6. Click OK.
Appendix C Error Codes Appendix E RSNetWorx Setup
Page 52
E–8 RSNetWorxt Setup
Configure T1K–DEVNETS with RSNetWorx
You are now ready to configure the T1K–DEVNETS. First, open RSNetWorx. Look for Koyo Electronics in the hardware tree listed under Vendor. Click on the + to show the devices for Koyo. The following example shows two devices, D0–DEVNETS and T1K–DEVNETS.
Appendix E RSNetWorx Setup
Appendix C Error Codes
RSNetWorx opened.
Using the EDS file
If you do not see your device listed, it will need to be added from the EDS file (refer to page 2–8). The following example will guide you through the procedure of installing the device from the EDS file. Click Tools and select EDS Wizard....
Page 53
E–9 RSNetWorxt Setup
The EDS Wizard will open. Simply follow the instructions to register the device.
Register the EDS file.
Appendix C Error Codes
Enter the path for the EDS file.
Appendix E RSNetWorx Setup
Page 54
E–10 RSNetWorxt Setup
EDS file installation results.
Appendix C Error Codes
You can change the icon image for your device in this window.
Appendix E RSNetWorx Setup
Review what you have done.