Page 37

C–4

Image Table Mapping

Register Input (V–memory) Image Table Mapping I/O Image

Low Byte High Byte Low Byte High Byte

Inputs Data Vn+00 Inputs Data Vn+01

Low Byte High Byte Low Byte

Inputs Data Vn+02 Inputs Data Vn+03 Input Size Read

High Byte Low Byte High Byte

Inputs Data Vn+04

2 to 128 bytes

Low Byte High Byte Low Byte High Byte Low Byte

Appendix C Image Table Mapping

Inputs Data Vn+61 Inputs Data Vn+62 Inputs Data Vn+63

Bit

07

06

05

04

03

02

High Byte 01

00

Size

Vn + 00 V memory Low byte data

Read Byte 1

Vn + 00 V memory High byte data

Read Byte 2

Vn + 01 V memory Low byte data

Read Byte 3

Vn + 01 V memory High byte data

Read Byte 4

Vn + 02 V memory Low byte data

Read Byte 5

Vn + 02 V memory High byte data

Read Byte 6

Vn + 03 V memory Low byte data

Read Byte 7

Vn + 03 V memory High byte data

Read Byte 8

Vn + 04 V memory Low byte data

Read Byte 9

Vn + 04 V memory High byte data

Read Byte 10

Vn + 05 V memory Low byte data

Read Byte 11

Vn + 05 V memory High byte data

Read Byte 12

Vn + 06 V memory Low byte data

Read Byte 13

Vn + 06 V memory High byte data

Read Byte 14

Vn + 07 V memory Low byte data

Read Byte 15

Vn + 07 V memory High byte data

Read Byte 16

Page 38

Image Table Mapping

Read Byte 17

Vn + 08 V memory High byte data

Read Byte 18

Vn + 09 V memory Low byte data

Read Byte 19

Vn + 09 V memory High byte data

Read Byte 20

:

:

:

:

:

:

:

:

Vn + 30 V memory Low byte data

Read Byte 61

Vn + 30 V memory High byte data

Read Byte 62

Vn + 31 V memory Low byte data

Read Byte 63

Vn + 31 V memory High byte data

Read Byte 64

:

:

:

:

:

:

:

:

Vn + 60 V memory Low byte data

Read Byte 121

Vn + 60 V memory High byte data

Read Byte 122

Vn + 61 V memory Low byte data

Read Byte 123

Vn + 61 V memory High byte data

Read Byte 124

Vn + 62 V memory Low byte data

Read Byte 125

Vn + 62 V memory High byte data

Read Byte 126

Vn + 63 V memory Low byte data

Read Byte 127

Vn + 63 V memory High byte data

Read Byte 128

Not Supported

Write Byte 1

Appendix C Image Table Mapping

Vn + 08 V memory Low byte data

C–5

Page 39

C–6

Image Table Mapping

Register Output (V–memory) Image Table Mapping I/O Image

Low Byte High Byte Low Byte High Byte

Outputs Data Vn+00 Outputs Data Vn+01

Low Byte High Byte Low Byte

Outputs Data Vn+02 Outputs Data Vn+03 Input Size Write

High Byte Low Byte High Byte

Outputs Data Vn+04

2 to 128 bytes

Low Byte High Byte Low Byte High Byte Low Byte

Appendix C Image Table Mapping

Outputs Data Vn+61 Outputs Data Vn+62 Outputs Data Vn+63

Bit

07

06

05

04

03

02

High Byte 01

00

Size

Not Supported

Read Byte 1

Vn + 00 V memory Low byte data

Write Byte 1

Vn + 00 V memory High byte data

Write Byte 2

Vn + 01 V memory Low byte data

Write Byte 3

Vn + 01 V memory High byte data

Write Byte 4

Vn + 02 V memory Low byte data

Write Byte 5

Vn + 02 V memory High byte data

Write Byte 6

Vn + 03 V memory Low byte data

Write Byte 7

Vn + 03 V memory High byte data

Write Byte 8

Vn + 04 V memory Low byte data

Write Byte 9

Vn + 04 V memory High byte data

Write Byte 10

Vn + 05 V memory Low byte data

Write Byte 11

Vn + 05 V memory High byte data

Write Byte 12

Vn + 06 V memory Low byte data

Write Byte 13

Vn + 06 V memory High byte data

Write Byte 14

Vn + 07 V memory Low byte data

Write Byte 15

Vn + 07 V memory High byte data

Write Byte 16

Page 40

Image Table Mapping

Write Byte 17

Vn + 08 V memory High byte data

Write Byte 18

Vn + 09 V memory Low byte data

Write Byte 19

Vn + 09 V memory High byte data

Write Byte 20

:

:

:

:

:

:

:

:

Vn + 30 V memory Low byte data

Write Byte 61

Vn + 30 V memory High byte data

Write Byte 62

Vn + 31 V memory Low byte data

Write Byte 63

Vn + 31 V memory High byte data

Write Byte 64

:

:

:

:

:

:

:

:

Vn + 60 V memory Low byte data

Write Byte 121

Vn + 60 V memory High byte data

Write Byte 122

Vn + 61 V memory Low byte data

Write Byte 123

Vn + 61 V memory High byte data

Write Byte 124

Vn + 62 V memory Low byte data

Write Byte 125

Vn + 62 V memory High byte data

Write Byte 126

Vn + 63 V memory Low byte data

Write Byte 127

Vn + 63 V memory High byte data

Write Byte 128

Appendix C Image Table Mapping

Vn + 08 V memory Low byte data

C–7

Page 41

C–8

Image Table Mapping

PLC Mode Image Table Mapping I/O Image Input Size

Inputs Read

2 byte

00:RUN Mode 03:STOP Mode

Output Size

Outputs

Appendix C Image Table Mapping

Write

2 byte

01:RUN Request 02:STOP Request

Dec. Bit Oct. Bit

07 07

06 06

05 05

04 04

03 03

02 02

01 01

00 00

Size

RUN Mode

0

0

0

0

0

0

0

0

Read Byte 2

STOP Mode

0

0

0

0

0

0

1

1

0

0

0

0

0

0

0

1

0

0

0

0

0

0

1

0

RUN Request STOP Request

Write Byte 2

Adapter Input/Output Status Word Polling format that the T1K–DEVNETS (slave) transmits to a master.

Address

Bytes

Data

+0

1

I/O Status

+1

1

PLC Mode

Comment Bit 0: Not used Bit 1: Not used Bit 2: Not used Bit 3: Node Error (Node number has changed) ON: Error/OFF: Normal Bit 4: IDLE (Output is IDLE) ON: Idle/OFF: Normal Bit 7: OUTPUT Status ON: Disable/OFF: Enable 00h: Mode = STOP 03h: Mode = RUN

Polling format that a master transmits to a DO–DEVNETS (slave).

Address

Bytes

Data No Code

+0

+1

1

1

Comment No request

C3h

Enable OUTPUT

3Ch

Disable OUTPUT

PLC Mode

01h: RUN request 02h: STOP request

Page 42

T1K–DEVNETS Think & Do Setup In This Appendix. . . . Ċ T1K-DEVNETS T & D Setup

1D

Page 43

D–2

Think & Do Setup

T1K–DEVNETS Think & Do Setup For those who are using the T1K–DEVNETS as a slave with Think & Do Studio, the following example shows how to setup Think & Do on your network. T & D Studio setup Use the following procedure to setup the T1K–DEVNETS adapter with Think & Do Studio. Be sure that the Node Address switches have been set to a proper address. for PC control 1. Click on Add Driver and SST card is installed. 2. Set MAC ID to 62. 3. Set baud rate (500K, SW1–1 OFF, –2 ON, in this example). 4. Set scanner interval to 0. 5. Set timeout shutdown to 5.

Appendix D Think & Do Setup

6. EDS not needed.

Page 44

Think & Do Setup

7. Click on connection.

D–3

Think & Do will display T1K–DEVNETS MacID–2. Inputs and outputs are displayed.

Appendix C Error Codes

8. Click on Scan and communication will begin.

Appendix D Think & Do Setup

Page 45

1 T1K–DEVNETS and RSNetWorxt Setup In this Appendix. . . . Ċ Setup T1K-DEVNETS with RSNetWorxt