The text of a manual · part 5 of 7
Terminator I/O DeviceNet Base Controller User Manual (T1K-DEVNETS), pages 37 to 45
Pages 37 to 45 of 63
The original document is the PDF (4.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect T1K-DEVNETS
Page 37
C–4
Image Table Mapping
Register Input (V–memory) Image Table Mapping I/O Image
Low Byte High Byte Low Byte High Byte
Inputs Data Vn+00 Inputs Data Vn+01
Low Byte High Byte Low Byte
Inputs Data Vn+02 Inputs Data Vn+03 Input Size Read
High Byte Low Byte High Byte
Inputs Data Vn+04
2 to 128 bytes
Low Byte High Byte Low Byte High Byte Low Byte
Appendix C Image Table Mapping
Inputs Data Vn+61 Inputs Data Vn+62 Inputs Data Vn+63
Bit
07
06
05
04
03
02
High Byte 01
00
Size
Vn + 00 V memory Low byte data
Read Byte 1
Vn + 00 V memory High byte data
Read Byte 2
Vn + 01 V memory Low byte data
Read Byte 3
Vn + 01 V memory High byte data
Read Byte 4
Vn + 02 V memory Low byte data
Read Byte 5
Vn + 02 V memory High byte data
Read Byte 6
Vn + 03 V memory Low byte data
Read Byte 7
Vn + 03 V memory High byte data
Read Byte 8
Vn + 04 V memory Low byte data
Read Byte 9
Vn + 04 V memory High byte data
Read Byte 10
Vn + 05 V memory Low byte data
Read Byte 11
Vn + 05 V memory High byte data
Read Byte 12
Vn + 06 V memory Low byte data
Read Byte 13
Vn + 06 V memory High byte data
Read Byte 14
Vn + 07 V memory Low byte data
Read Byte 15
Vn + 07 V memory High byte data
Read Byte 16
Page 38
Image Table Mapping
Read Byte 17
Vn + 08 V memory High byte data
Read Byte 18
Vn + 09 V memory Low byte data
Read Byte 19
Vn + 09 V memory High byte data
Read Byte 20
:
:
:
:
:
:
:
:
Vn + 30 V memory Low byte data
Read Byte 61
Vn + 30 V memory High byte data
Read Byte 62
Vn + 31 V memory Low byte data
Read Byte 63
Vn + 31 V memory High byte data
Read Byte 64
:
:
:
:
:
:
:
:
Vn + 60 V memory Low byte data
Read Byte 121
Vn + 60 V memory High byte data
Read Byte 122
Vn + 61 V memory Low byte data
Read Byte 123
Vn + 61 V memory High byte data
Read Byte 124
Vn + 62 V memory Low byte data
Read Byte 125
Vn + 62 V memory High byte data
Read Byte 126
Vn + 63 V memory Low byte data
Read Byte 127
Vn + 63 V memory High byte data
Read Byte 128
Not Supported
Write Byte 1
Appendix C Image Table Mapping
Vn + 08 V memory Low byte data
C–5
Page 39
C–6
Image Table Mapping
Register Output (V–memory) Image Table Mapping I/O Image
Low Byte High Byte Low Byte High Byte
Outputs Data Vn+00 Outputs Data Vn+01
Low Byte High Byte Low Byte
Outputs Data Vn+02 Outputs Data Vn+03 Input Size Write
High Byte Low Byte High Byte
Outputs Data Vn+04
2 to 128 bytes
Low Byte High Byte Low Byte High Byte Low Byte
Appendix C Image Table Mapping
Outputs Data Vn+61 Outputs Data Vn+62 Outputs Data Vn+63
Bit
07
06
05
04
03
02
High Byte 01
00
Size
Not Supported
Read Byte 1
Vn + 00 V memory Low byte data
Write Byte 1
Vn + 00 V memory High byte data
Write Byte 2
Vn + 01 V memory Low byte data
Write Byte 3
Vn + 01 V memory High byte data
Write Byte 4
Vn + 02 V memory Low byte data
Write Byte 5
Vn + 02 V memory High byte data
Write Byte 6
Vn + 03 V memory Low byte data
Write Byte 7
Vn + 03 V memory High byte data
Write Byte 8
Vn + 04 V memory Low byte data
Write Byte 9
Vn + 04 V memory High byte data
Write Byte 10
Vn + 05 V memory Low byte data
Write Byte 11
Vn + 05 V memory High byte data
Write Byte 12
Vn + 06 V memory Low byte data
Write Byte 13
Vn + 06 V memory High byte data
Write Byte 14
Vn + 07 V memory Low byte data
Write Byte 15
Vn + 07 V memory High byte data
Write Byte 16
Page 40
Image Table Mapping
Write Byte 17
Vn + 08 V memory High byte data
Write Byte 18
Vn + 09 V memory Low byte data
Write Byte 19
Vn + 09 V memory High byte data
Write Byte 20
:
:
:
:
:
:
:
:
Vn + 30 V memory Low byte data
Write Byte 61
Vn + 30 V memory High byte data
Write Byte 62
Vn + 31 V memory Low byte data
Write Byte 63
Vn + 31 V memory High byte data
Write Byte 64
:
:
:
:
:
:
:
:
Vn + 60 V memory Low byte data
Write Byte 121
Vn + 60 V memory High byte data
Write Byte 122
Vn + 61 V memory Low byte data
Write Byte 123
Vn + 61 V memory High byte data
Write Byte 124
Vn + 62 V memory Low byte data
Write Byte 125
Vn + 62 V memory High byte data
Write Byte 126
Vn + 63 V memory Low byte data
Write Byte 127
Vn + 63 V memory High byte data
Write Byte 128
Appendix C Image Table Mapping
Vn + 08 V memory Low byte data
C–7
Page 41
C–8
Image Table Mapping
PLC Mode Image Table Mapping I/O Image Input Size
Inputs Read
2 byte
00:RUN Mode 03:STOP Mode
Output Size
Outputs
Appendix C Image Table Mapping
Write
2 byte
01:RUN Request 02:STOP Request
Dec. Bit Oct. Bit
07 07
06 06
05 05
04 04
03 03
02 02
01 01
00 00
Size
RUN Mode
0
0
0
0
0
0
0
0
Read Byte 2
STOP Mode
0
0
0
0
0
0
1
1
0
0
0
0
0
0
0
1
0
0
0
0
0
0
1
0
RUN Request STOP Request
Write Byte 2
Adapter Input/Output Status Word Polling format that the T1K–DEVNETS (slave) transmits to a master.
Address
Bytes
Data
+0
1
I/O Status
+1
1
PLC Mode
Comment Bit 0: Not used Bit 1: Not used Bit 2: Not used Bit 3: Node Error (Node number has changed) ON: Error/OFF: Normal Bit 4: IDLE (Output is IDLE) ON: Idle/OFF: Normal Bit 7: OUTPUT Status ON: Disable/OFF: Enable 00h: Mode = STOP 03h: Mode = RUN
Polling format that a master transmits to a DO–DEVNETS (slave).
Address
Bytes
Data No Code
+0
+1
1
1
Comment No request
C3h
Enable OUTPUT
3Ch
Disable OUTPUT
PLC Mode
01h: RUN request 02h: STOP request
Page 42
T1K–DEVNETS Think & Do Setup In This Appendix. . . . Ċ T1K-DEVNETS T & D Setup
1D
Page 43
D–2
Think & Do Setup
T1K–DEVNETS Think & Do Setup For those who are using the T1K–DEVNETS as a slave with Think & Do Studio, the following example shows how to setup Think & Do on your network. T & D Studio setup Use the following procedure to setup the T1K–DEVNETS adapter with Think & Do Studio. Be sure that the Node Address switches have been set to a proper address. for PC control 1. Click on Add Driver and SST card is installed. 2. Set MAC ID to 62. 3. Set baud rate (500K, SW1–1 OFF, –2 ON, in this example). 4. Set scanner interval to 0. 5. Set timeout shutdown to 5.
Appendix D Think & Do Setup
6. EDS not needed.
Page 44
Think & Do Setup
7. Click on connection.
D–3
Think & Do will display T1K–DEVNETS MacID–2. Inputs and outputs are displayed.
Appendix C Error Codes
8. Click on Scan and communication will begin.
Appendix D Think & Do Setup
Page 45
1 T1K–DEVNETS and RSNetWorxt Setup In this Appendix. . . . Ċ Setup T1K-DEVNETS with RSNetWorxt
E