The text of a manual · part 4 of 7
Terminator I/O DeviceNet Base Controller User Manual (T1K-DEVNETS), pages 28 to 36
Pages 28 to 36 of 63
The original document is the PDF (4.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect T1K-DEVNETS
Page 28
B–2
Tables
Data Input and Output Tables Input Register Object Class (107) Instance = 1 Attribute = 3 Data
Address
Service
Input Register
Vn+00
+00
Get
Vn+01
+02
Vn+02
+04
Vn+03
+06
Vn+04
+08
:
:
Vn+62
+124
Vn+63
+ 126
Appendix B Tables
Name
The Data Register equals one Word (16 bits). A maximum of 64 V–memory words can be accessed. Input Register
Register Input (V–memory) Image Table Mapping I/O Image
Inputs Data Vn+00 Inputs Data Vn+01 Inputs Data Vn+02 Inputs Data Vn+03
Input Size Read
Inputs Data Vn+04
Low Byte High Byte Low Byte High Byte Low Byte High Byte Low Byte High Byte Low Byte High Byte
2 to 128 bytes
Inputs Data Vn+61 Inputs Data Vn+62 Inputs Data Vn+63
Low Byte High Byte Low Byte High Byte Low Byte High Byte
Page 29
Tables
Bit
07
06
05
04
03
02
01
00
B–3
Size
Vn + 00 V memory Low byte data
Read Byte 1
Vn + 00 V memory High byte data
Read Byte 2
Vn + 01 V memory Low byte data
Read Byte 3
Vn + 01 V memory High byte data
Read Byte 4
Vn + 02 V memory Low byte data
Read Byte 5
Vn + 02 V memory High byte data
Read Byte 6
:
:
:
: Read Byte 121
Vn + 60 V memory High byte data
Read Byte 122
Vn + 61 V memory Low byte data
Read Byte 123
Vn + 61 V memory High byte data
Read Byte 124
Vn + 62 V memory Low byte data
Read Byte 125
Vn + 62 V memory High byte data
Read Byte 126
Vn + 63 V memory Low byte data
Read Byte 127
Vn + 63 V memory High byte data
Read Byte 128
Appendix B Tables
Vn + 60 V memory Low byte data
Page 30
B–4
Tables
Output Register Object Class (108)
Appendix B Tables
Instance = 1 Attribute = 3 Name
Data
Address
Service
Output Register
Vn+00
+00
Set
Vn+01
+02
Vn+02
+04
Vn+03
+06
Vn+04
+08
:
:
Vn+62
+124
Vn+63
+ 126
The Data Register equals one Word (16 bits). A maximum of 64 V–memory words can be accessed. Output Register
Register Output (V–memory) Image Table Mapping I/O Image
Outputs Data Vn+00 Outputs Data Vn+01 Outputs Data Vn+02 Outputs Data Vn+03
Input Size Write
Outputs Data Vn+04
Low Byte High Byte Low Byte High Byte Low Byte High Byte Low Byte High Byte Low Byte High Byte
2 to 128 bytes
Outputs Data Vn+61 Outputs Data Vn+62 Outputs Data Vn+63
Low Byte High Byte Low Byte High Byte Low Byte High Byte
Page 31
Tables
Bit
07
06
05
04
03
02
01
00
Size
Vn + 00 V memory Low byte data
Write Byte 1
Vn + 00 V memory High byte data
Write Byte 2
Vn + 01 V memory Low byte data
Write Byte 3
Vn + 01 V memory High byte data
Write Byte 4
Vn + 02 V memory Low byte data
Write Byte 5
Vn + 02 V memory High byte data
Write Byte 6
:
:
:
: Write Byte 121
Vn + 60 V memory High byte data
Write Byte 122
Vn + 61 V memory Low byte data
Write Byte 123
Vn + 61 V memory High byte data
Write Byte 124
Vn + 62 V memory Low byte data
Write Byte 125
Vn + 62 V memory High byte data
Write Byte 126
Vn + 63 V memory Low byte data
Write Byte 127
Vn + 63 V memory High byte data
Write Byte 128
Data Register Range RJ12 serial port supports the following registers. No.
Register Number
Comment
Description
1
V40400–V40477
Input Register
Read/Write
2
V40500–V40577
Output Register
Read/Write
3
V00000–V02777
Data Register
Read/Write
4
V03000–V03077
Explicit Get Command Area
Read/Write
5
V03100–V03177
Explicit Set Command Area
Read/Write
6
V03200–V07377
Data Register
Read/Write
7
V07640–V07613
Special Register
Resave
8
V07614–V07617
Parameter Register
Read
9
V07620–V07777
Special Register
Resave
Appendix B Tables
Vn + 60 V memory Low byte data
Note: Not all registers back up data.
B–5
Page 32
B–6
Tables
I/O Diagnostic Information DIP Switch SW4
The position of DIP Switch SW4 determines whether or not you receive Terminator I/O diagnostic information. If SW4 is in the OFF (default) position, you will receive this diagnostic information and you must allow for two additional bytes on the input (RX) and two additional bytes on the output (TX) for Terminator I/O diagnostic functions. If SW4 is placed in the ON position, you will not receive this diagnostic information and there is no need to allow for the additional bytes.
Appendix B Tables
Following is a description of the diagnostic codes. Diagnostic (polling) information whenT1K–DEVNETS (slave) transmits to a master. Address Bytes +0
1
Data
Comment
I/O Status
Bit 0: Missing module error ON: Error / OFF: Normal Bit 1: New module present error ON: Error / OFF: Normal Bit 2: I/O diagnostic error ON: Error / OFF: Normal Bit 3: Node error (the node number has changed) ON: Error / OFF: Normal Bit 4: Idle (Output is idle) ON: Idle / OFF: Normal Bit 5: Multiple error (Two or more errors occurred) ON: Multiple / OFF: Normal Bit 7: Output status ON: Enable / OFF: Disable
+1
1
Error Slot
01h: Slot 1 02h: Slot 2 . . 1Fh: Slot 31
Module Missing error or New Module Error
21h: Slot 1 22h: Slot 2 . . 3Fh: Slot 31
24V Error or Fuse Error
The slot number in which the error has occurred. When the same error occurs by multiple slots, priority is given to low slot number. Priority is given to 24V Error or Fuse Error when multiple errors occur at the same time. +2 . +nn n
Bit Data
T1K–DEVNETS input module data.
Page 33
Tables
B–7
Diagnostic (polling) information when a master transmits to a T1K–DEVNETS (slave). The command to select I/O configuration is transferred from peripheral and written here. When the I/O configuration error occurs the command is executed. Address
Bytes
Data
+0
1
Code of except the following
Comment No request
5Ah
Select I/O reconfiguration
C3h
Select Output Enable
3Ch
Select Output Disable
1
Reserved
Not used
+2 . +nn n
Bit data
T1K–DEVNETS output module data.
System DeviceNet object that T1K–DEVNETS supports are: Information Object Item Instance Specifications Special Object
System Information Object
1–4
Class Number 106
Appendix B Tables
+1
Page 34
Image Table Mapping
In This Appendix. . . . Ċ Image Table Mapping
1C
Page 35
C–2
Image Table Mapping
Image Table Mapping Read, Write and Status Byte References T1K–DEVNETS can access data bytes.
Discrete Input Discrete Input Point (X,Y,C,S,T,CT,SP) Image Table Mapping Inputs Inputs I/O Image
7
6
5
4
3
17
16
15
14
27
26
25
24
2
1
0
12
11
10
22
21
20
32
31
30
42
41
40
52
51
50
62
61
60
72
71
70
Inputs
Input Size
13
Inputs Read
1 to 8 bytes
23
Inputs 37
36
35
34
33
Inputs
Appendix C Image Table Mapping
47
46
45
44
43
Inputs 57
56
55
54
53
Inputs 67
66
65
64
63
Inputs 77
Dec. Bit Oct. Bit
76
75
74
73
07 07
06 06
05 05
04 04
03 03
02 02
01 01
00 00
7 17 27 37 47 57 67 77
6 16 26 36 46 56 66 76
5 15 25 35 45 55 65 75
4 14 24 34 44 54 64 74
3 13 23 33 43 53 63 73
2 12 22 32 42 52 62 72
1 11 21 31 41 51 61 71
0 10 20 30 40 50 60 70
Not Supported
Size Read Byte 1 Read Byte 2 Read Byte 3 Read Byte 4 Read Byte 5 Read Byte 6 Read Byte 7 Read Byte 8 Write Byte 1
Page 36
Image Table Mapping
C–3
Discrete Output Point (X,Y,C,S,T,CT,SP) Image Table Mapping Inputs Outputs
7
I/O Image
6
5
4
3
2
1
0
12
11
10
22
21
20
32
31
30
42
41
40
52
51
50
62
61
60
72
71
70
Outputs 17
16
15
14
13
Outputs 27
26
25
24
37
36
35
34
Output Size Write
23
Outputs
1 to 8 bytes
33
Outputs 47
46
45
44
43
Outputs 57
56
55
54
53
Outputs 67
66
65
64
77
76
75
74
63
Outputs
07 07
06 06
05 05
04 04
03 03
02 02
01 01
00 00
Not Supported 7 6 5 17 16 15 27 26 25 37 36 35 47 46 45 57 56 55 67 66 65 77 76 75
4 14 24 34 44 54 64 74
3 13 23 33 43 53 63 73
2 12 22 32 42 52 62 72
1 11 21 31 41 51 61 71
0 10 20 30 40 50 60 70
Size Size Read Byte 1 Write Byte 1 Write Byte 2 Write Byte 3 Write Byte 4 Write Byte 5 Write Byte 6 Write Byte 7 Write Byte 8
Appendix C Image Table Mapping
Dec. Bit Oct. Bit
73