The text of a manual · part 3 of 7
Terminator I/O DeviceNet Base Controller User Manual (T1K-DEVNETS), pages 19 to 27
Pages 19 to 27 of 63
The original document is the PDF (4.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect T1K-DEVNETS
Page 19
Installing the T1K–DEVNETS Base Controller
2–7
Wiring the Connect the DeviceNet cable (Belden 3085A, YR–29832 or equivalent) to the removable connector as shown below. The wire colors are also labeled on the Controller to a DeviceNet Network Controller front. Be sure to connect a terminating resistor (121 Ohm 1%, 1/4W). V– (black) CAN* Low (blue) Shield (bare) CAN* High (white) V+ (red)
Tip: Be sure that each end of the DeviceNet network ’trunk” has a proper terminating resistor connected as shown above.
The T1K–DEVNETS serial port is used to update the firmware of the base controller when necessary. Use cable part number D2–DSCBL to connect the T1K–DEVNETS to a PC, or use the following information to make a cable. 1234 56
Serial Port (RS–232)
Installing the DeviceNet Base Controller
* Controller Area Network (CAN)
Connect a terminating resistor across the CAN High (white) and CAN Low (blue) screw terminals. The terminating resistor is 121 Ohm 1%, 1/4 Watt. (2 resistors are included with each T1K–DEVNETS).
1 2 3 4 5 6
Serial Port Pinout Signal
1
0V
2
+5V
3
RXD
4
TXD
5
RTS
6
CTS
Installation and Safety Guidelines
Pin
Page 20
2–8
Installing the T1K–DEVNETS Base Controller
Configuring the Controller
Installation and Safety Guidelines
Installing the DeviceNet Base Controller
Configuring the DeviceNet Base Controller
Use the software of your DeviceNet master to configure the controller for your network. Refer to the software Help file and/or manual for help with configuration. Follow these basic steps when configuring your T1K–DEVNETS controller. 1. Set the Controller Node Address: In the DeviceNet master software, make sure the Controller node address is set to an available node number on the DeviceNet network (from 0 to 63). 2. Add the EDS file (if required by the software): In your DeviceNet software, add the T1K–DEVNETS Electronic Data Sheet (EDS) file from the disk which came with this manual or from our web site www.automationdirect.com. Some software may not provide for the use of EDS files. 3. Commission the Node: Use the DeviceNet software to “Commission the Node” of your Controller. Again, some software may not require this. 4. Add the T1K–DEVNETS to the Scan List: Add the T1K–DEVNETS to the Scan List in your DeviceNet Master software. 5. Set the Input/Output Bytes: If required by your DeviceNet software, set the I/O Parameters to Tx = Output bytes and Rx = Input bytes (on the Scanner’s Scan List tab), for Polled I/O. Either use the tables located in the appendixes or go to page E–18 and follow the steps in the example. 6. Map the I/O to the Master: Map the T1K–DEVNETS I/O to the Scanner using Auto Map, or map the I/O to another location if desired. 7. Scan: Go Online (or Scan) to verify the configuration and check for errors. 8. View Indicators on the Controller: Refer to the Status Indicators when connecting to the network.
Page 21
Installing the T1K–DEVNETS Base Controller
Status Indicators
2–9
The Controller has two Status Indicators, one for Module Status and the other for Network Status.
MS (Module Status) Indicator Status
OFF
No power to Controller. Check wiring.
ON (Green)
Power applied to Controller, no fault
ON (Red)
Critical Controller Fault NS (Network Status) Indicator
Outputs Switch
Indication
Status
OFF
No power to Controller or no Network Access
Flashing Green
Online but not connected
Solid Green
Online, link okay and connected
Flashing Red
Recoverable fault
Solid Red
Critical Controller Fault (Duplicate ID or Bus off)
Installing the DeviceNet Base Controller
Indication
The Outputs switch enables or disables outputs connected to the Controller.
Installation and Safety Guidelines
Note: It is good safe practice to disable outputs before Hot Swapping modules if the application allows this.
Page 22
2–10
Installing the T1K–DEVNETS Base Controller
Master/Slave Communications The T1K–DEVNETS controller (slave) communicates with the DeviceNet scanner (master) by sending Input Data and receiving Output Data. The controller reads Inputs from I/O Modules and writes Outputs to I/O Modules.
T1K–DEVNETS Backplane
Installation and Safety Guidelines
Installing the DeviceNet Base Controller
To Master Input Data Network Read
Read Inputs
(Read Data) I/O Modules
From Master Network Write
Output Data (Write Data)
Write Outputs
Page 23
Installing the T1K–DEVNETS Base Controller
2–11
Terminator I/O Backplane Communications The Controller communicates with its I/O modules over the backplane. The I/O is mapped in consecutive order as shown.
T1K–DEVNETS Input Data
I/O Module, Slot 1
I/O Module, Slot N
Inputs
Inputs
Outputs
Outputs
Slot 1 Input Data Slot 2 Input Data Read
Slot N Input Data Output Data Network Write
Slot 1 Output Data Slot 2 Output Data
Installing the DeviceNet Base Controller
Network Read
Write Slot N Output Data
Refer to the Terminator I/O Installation and I/O Manual (T1K–INST–M) for the memory map for individual Discrete and/or Analog I/O Modules.
Installation and Safety Guidelines
I/O Module Memory Map
Page 24
Specifications
In This Appendix. . . . Ċ Specifications
1A
Page 25
A–2
Specifications
Appendix A Specifications
Specifications General Operating Temperature
32° F to 131° F (0° C to 55° C)
Storage Temperature
–4° F to 158° F (–20° C to 70° C)
Ambient Humidity
5% – 95% relative humidity (non–condensing)
Voltage Withstand
1500VAC, 1 minute (DeviceNet connector internal)
Insulation Resistance
500VDC, 10MΩ (DeviceNet connector internal)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Noise Immunity
NEMA (ICS3–304) Impulse noise 1µs, 1000V FCC class A RFI (145MHz, 435MHz 10W, 10cm)
Atmosphere
No corrosive gases Environmental Pollution Level 2
Size
189”Wx315”Hx326”D (48Wx80Hx83D)
Weight
6.0 oz (170 g)
Appendix C Error Codes
Communication Communication form
DeviceNet Communication Protocol (Slave) Predefined Master/Slave Group 2 Server only
Network Node Address
0 to 63 (Rotary switch setting)
Data Packet
0 to 8 Bytes (Data beyond eight bytes are divided.)
Communication Rate (Max. cable length)
125KB 250KB 500KB
Communication Status Indicator
MS: Module Status LED [Red/Green] NS: Network Status LED [Red/Green]
DeviceNet Power Consumption
11 to 25 VDC (45mA max.) DeviceNet
Device Type
Generic
Explicit Peer to Peer Message
No
I/O Peer to Peer Message
No
Configuration Consistency
No
Fault Node Recovery
No
Communication Baud Rate 125K, 250K, 500K
Yes
Master/Scanner
No
I/O Slave Message
Bit Strobe Polling Cyclic Change of State
No Yes No No
(1640 ft./ 500m) (820 ft./ 250m) (328 ft./ 100m)
Page 26
Specifications
A–3
Serial Port Communications 6 pin female modular (RJ12 phone jack)
Connection Port Type
RS–232C
Protocol
Auto detection K–Sequence (Slave)
Station Number
1 (fixed)
Baud Rate
9600 bps or 19.2 kbps Dip–Switch 6 (DIP SW6) Setting
Data Bits
8
Start Bits
1
Stop Bits
1
Parity
ODD
Communication Time out
Prescribed Time
Appendix A Specifications
Connector
I/O Modules Inputs: 1024 Points Outputs: 1024 Points
Number of Slots (I/O Modules)
1 to 16 slots
Self-diagnostics
Watch-dog Timer Memory check
I/O module types
Discrete Input Module Discrete Output Module Analog Input Module Analog Output Module
Install Module
Hot swappable (install / remove modules under power)
Internal Power Consumption
190mA at 5VDC
Max. time of external power loss
10ms
Appendix C Error Codes
Number of I/O points
Page 27
Tables
In This Appendix. . . . Ċ DeviceNet Tables