For the AutomationDirect T1K-DEVNETS

Page 19

Installing the T1K–DEVNETS Base Controller

2–7

Wiring the Connect the DeviceNet cable (Belden 3085A, YR–29832 or equivalent) to the removable connector as shown below. The wire colors are also labeled on the Controller to a DeviceNet Network Controller front. Be sure to connect a terminating resistor (121 Ohm 1%, 1/4W). V– (black) CAN* Low (blue) Shield (bare) CAN* High (white) V+ (red)

Tip: Be sure that each end of the DeviceNet network ’trunk” has a proper terminating resistor connected as shown above.

The T1K–DEVNETS serial port is used to update the firmware of the base controller when necessary. Use cable part number D2–DSCBL to connect the T1K–DEVNETS to a PC, or use the following information to make a cable. 1234 56

Serial Port (RS–232)

Installing the DeviceNet Base Controller

* Controller Area Network (CAN)

Connect a terminating resistor across the CAN High (white) and CAN Low (blue) screw terminals. The terminating resistor is 121 Ohm 1%, 1/4 Watt. (2 resistors are included with each T1K–DEVNETS).

1 2 3 4 5 6

Serial Port Pinout Signal

1

0V

2

+5V

3

RXD

4

TXD

5

RTS

6

CTS

Installation and Safety Guidelines

Pin

Page 20

2–8

Installing the T1K–DEVNETS Base Controller

Configuring the Controller

Installation and Safety Guidelines

Installing the DeviceNet Base Controller

Configuring the DeviceNet Base Controller

Use the software of your DeviceNet master to configure the controller for your network. Refer to the software Help file and/or manual for help with configuration. Follow these basic steps when configuring your T1K–DEVNETS controller. 1. Set the Controller Node Address: In the DeviceNet master software, make sure the Controller node address is set to an available node number on the DeviceNet network (from 0 to 63). 2. Add the EDS file (if required by the software): In your DeviceNet software, add the T1K–DEVNETS Electronic Data Sheet (EDS) file from the disk which came with this manual or from our web site www.automationdirect.com. Some software may not provide for the use of EDS files. 3. Commission the Node: Use the DeviceNet software to “Commission the Node” of your Controller. Again, some software may not require this. 4. Add the T1K–DEVNETS to the Scan List: Add the T1K–DEVNETS to the Scan List in your DeviceNet Master software. 5. Set the Input/Output Bytes: If required by your DeviceNet software, set the I/O Parameters to Tx = Output bytes and Rx = Input bytes (on the Scanner’s Scan List tab), for Polled I/O. Either use the tables located in the appendixes or go to page E–18 and follow the steps in the example. 6. Map the I/O to the Master: Map the T1K–DEVNETS I/O to the Scanner using Auto Map, or map the I/O to another location if desired. 7. Scan: Go Online (or Scan) to verify the configuration and check for errors. 8. View Indicators on the Controller: Refer to the Status Indicators when connecting to the network.

Page 21

Installing the T1K–DEVNETS Base Controller

Status Indicators

2–9

The Controller has two Status Indicators, one for Module Status and the other for Network Status.

MS (Module Status) Indicator Status

OFF

No power to Controller. Check wiring.

ON (Green)

Power applied to Controller, no fault

ON (Red)

Critical Controller Fault NS (Network Status) Indicator

Outputs Switch

Indication

Status

OFF

No power to Controller or no Network Access

Flashing Green

Online but not connected

Solid Green

Online, link okay and connected

Flashing Red

Recoverable fault

Solid Red

Critical Controller Fault (Duplicate ID or Bus off)

Installing the DeviceNet Base Controller

Indication

The Outputs switch enables or disables outputs connected to the Controller.

Installation and Safety Guidelines

Note: It is good safe practice to disable outputs before Hot Swapping modules if the application allows this.

Page 22

2–10

Installing the T1K–DEVNETS Base Controller

Master/Slave Communications The T1K–DEVNETS controller (slave) communicates with the DeviceNet scanner (master) by sending Input Data and receiving Output Data. The controller reads Inputs from I/O Modules and writes Outputs to I/O Modules.

T1K–DEVNETS Backplane

Installation and Safety Guidelines

Installing the DeviceNet Base Controller

To Master Input Data Network Read

Read Inputs

(Read Data) I/O Modules

From Master Network Write

Output Data (Write Data)

Write Outputs

Page 23

Installing the T1K–DEVNETS Base Controller

2–11

Terminator I/O Backplane Communications The Controller communicates with its I/O modules over the backplane. The I/O is mapped in consecutive order as shown.

T1K–DEVNETS Input Data

I/O Module, Slot 1

I/O Module, Slot N

Inputs

Inputs

Outputs

Outputs

Slot 1 Input Data Slot 2 Input Data Read

Slot N Input Data Output Data Network Write

Slot 1 Output Data Slot 2 Output Data

Installing the DeviceNet Base Controller

Network Read

Write Slot N Output Data

Refer to the Terminator I/O Installation and I/O Manual (T1K–INST–M) for the memory map for individual Discrete and/or Analog I/O Modules.

Installation and Safety Guidelines

I/O Module Memory Map

Page 24

Specifications

In This Appendix. . . . Ċ Specifications

1A

Page 25

A–2

Specifications

Appendix A Specifications

Specifications General Operating Temperature

32° F to 131° F (0° C to 55° C)

Storage Temperature

–4° F to 158° F (–20° C to 70° C)

Ambient Humidity

5% – 95% relative humidity (non–condensing)

Voltage Withstand

1500VAC, 1 minute (DeviceNet connector internal)

Insulation Resistance

500VDC, 10MΩ (DeviceNet connector internal)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Noise Immunity

NEMA (ICS3–304) Impulse noise 1µs, 1000V FCC class A RFI (145MHz, 435MHz 10W, 10cm)

Atmosphere

No corrosive gases Environmental Pollution Level 2

Size

189”Wx315”Hx326”D (48Wx80Hx83D)

Weight

6.0 oz (170 g)

Appendix C Error Codes

Communication Communication form

DeviceNet Communication Protocol (Slave) Predefined Master/Slave Group 2 Server only

Network Node Address

0 to 63 (Rotary switch setting)

Data Packet

0 to 8 Bytes (Data beyond eight bytes are divided.)

Communication Rate (Max. cable length)

125KB 250KB 500KB

Communication Status Indicator

MS: Module Status LED [Red/Green] NS: Network Status LED [Red/Green]

DeviceNet Power Consumption

11 to 25 VDC (45mA max.) DeviceNet

Device Type

Generic

Explicit Peer to Peer Message

No

I/O Peer to Peer Message

No

Configuration Consistency

No

Fault Node Recovery

No

Communication Baud Rate 125K, 250K, 500K

Yes

Master/Scanner

No

I/O Slave Message

Bit Strobe Polling Cyclic Change of State

No Yes No No

(1640 ft./ 500m) (820 ft./ 250m) (328 ft./ 100m)

Page 26

Specifications

A–3

Serial Port Communications 6 pin female modular (RJ12 phone jack)

Connection Port Type

RS–232C

Protocol

Auto detection K–Sequence (Slave)

Station Number

1 (fixed)

Baud Rate

9600 bps or 19.2 kbps Dip–Switch 6 (DIP SW6) Setting

Data Bits

8

Start Bits

1

Stop Bits

1

Parity

ODD

Communication Time out

Prescribed Time

Appendix A Specifications

Connector

I/O Modules Inputs: 1024 Points Outputs: 1024 Points

Number of Slots (I/O Modules)

1 to 16 slots

Self-diagnostics

Watch-dog Timer Memory check

I/O module types

Discrete Input Module Discrete Output Module Analog Input Module Analog Output Module

Install Module

Hot swappable (install / remove modules under power)

Internal Power Consumption

190mA at 5VDC

Max. time of external power loss

10ms

Appendix C Error Codes

Number of I/O points

Page 27

Tables

In This Appendix. . . . Ċ DeviceNet Tables

1B