For the AutomationDirect T1K-DEVNETS

Page 10

1–4

Getting Started

Installation and Safety Guidelines

Getting Started

Introduction to DeviceNet

DeviceNet Concepts

The ODVA

DeviceNet is a low-level network designed to connect factory-floor devices to control systems. There are a host of manufacturers of DeviceNet products, offering an array of products including sensors, motor drives and starters, PLCs, pushbuttons, remote I/O systems, etc. Here are some DeviceNet concepts you may find helpful. • DeviceNet supports various communication structures including Peer to Peer, Multi-master and Master/Slave. The T1K–DEVNETS uses the predefined Master/Slave connection. • DeviceNet has two types of messaging: Explicit Messaging and I/O Messaging. • Explicit Messaging is low priority, not time-critical and usually for configuration/diagnostic purposes. • I/O Messaging is time-critical and high priority for I/O data transfer. I/O Messaging comes in four types: • Strobed • Polled (The T1K–DEVNETS only supports Polled.) • Change of State (or COS) • Cyclic • A single DeviceNet network is limited to 64 nodes. A node can be a single-bit device, such as a limit switch, or a remote I/O slave with several I/O modules, such as the T1K–DEVNETS. The Master (Scanner) is usually assigned to node address 0, and many Slave devices have a factory default node address of 63. • DeviceNet has the following data rates (with maximum bus lengths): • 125 kbps (bus length = 500m max.) • 250 kbps (bus length = 250m max.) • 500 kbps (bus length = 100m max.) • The 24V DeviceNet power supply must be grounded at only one point. The V– terminal must be tied to Protective Earth Ground at the power supply only. The DeviceNet standard is maintained by the ODVA (Open DeviceNet Vendor Association, Inc.). Contact the ODVA for detailed information about DeviceNet. Open DeviceNet Vendor Association, Inc. 20423 State Road 7 Suite 499 Boca Raton, FL 33498 Phone: (954) 340–5412 Fax: (954) 340–5413 Internet: www.odva.org Email: odva@powerinternet.com

Page 11

Introduction

1–5

Terminator I/O System

Power Supply

DeviceNet Base Controller

Getting Started

Terminator I/O is a modular system which combines the functions of terminal blocks and I/O modules for distributed I/O. Each Terminator I/O system has the following components: a Power Supply, a Base Controller, and one or more I/O Module(s).

I/O Modules

I/O Module

Installation and Safety Guidelines

I/O Base

Mini Glossary

Below is a small glossary of terms used in this manual. Scanner or Master

The DeviceNet Master of which the T1K–DEVNETS is a slave. This can be either a PLC module or a card in your PC.

Controller or Slave

Short for the T1K–DEVNETS Base Controller. The controller is also referred to as a Network Interface Module elsewhere.

Node Address or MAC ID

The unique device address on a DeviceNet network. There are a maximum of 64 total (0–63). Usually the scanner is node 0.

Page 12

1–6

Getting Started

Getting Started

T1K–DEVNETS Base Controller

T1K–DEVNETS Base Controller Features

The T1K–DEVNETS Base Controller is a slave module that functions as a controller for Terminator I/O on a DeviceNet network. The Controller has the following features: • Status LEDs (Module and Network) • Serial Port • Node Address Switches • Output Enable Switch • DeviceNet Connector

Clip Arm

Status LEDs

Output Enable/Disable Switch Node Address Switches

Installation and Safety Guidelines

Serial Port

DeviceNet Connector Locking Tab

Page 13

Installing the T1K–DEVNETS Base Controller

12

In This Chapter. . . ., Installing the T1K–DEVNETS Base Controller, Configuring the Controller, Master/Slave Communications, Terminator I/O Backplane Communications

Page 14

2–2

Installing the T1K–DEVNETS Base Controller

Installing the T1K–DEVNETS

Installing the DeviceNet Base Controller

Mounting on DIN Rail

2

3

1 NOTE: Do not force the base controller onto the DIN rail. Due to slight size variations in different manufacturer’s DIN rail, it may be necessary to first unlatch the locking tab, rotate the module into place, then latch the locking tab.

1. Make sure the locking tab is in the latched position (pushed in).

Installation and Safety Guidelines

2. Hook upper tab over upper flange of DIN rail. 3. Tilt the unit toward DIN rail until it snaps securely to DIN rail.

Connecting the Controller to a Power Supply

Slide the controller onto the DIN rail until the clip arm attaches securely to the power supply. WARNING: Power to the T1K Power Supply must be disconnected before installing or removing the T1K–DEVNETS. Failure to disconnect power could result in serious damage to the module, to the power supply or both.

Page 15

Installing the T1K–DEVNETS Base Controller

2–3

Setting the Node Address

Connecting the Components on the DIN Rail

Installing the DeviceNet Base Controller

Use a small flat screwdriver to set the Node Address to an available Node Address (or MAC ID), from 0 – 63. Note that X10 represents the tens place and X1 represents the units place.

Slide the module assembly onto the DIN rail until the clip arm attaches securely to the adjacent module. Installation and Safety Guidelines

WARNING: Again, be sure that the power to the T1K Power Supply is disconnected before installing or removing the module assemby. Failure to disconnect power could result in serious damage to the modules, to the power supply or to the entire assembly.

Page 16

2–4

Installing the T1K–DEVNETS Base Controller

Installing the DeviceNet Base Controller

Removing I/O Modules from the Base

To remove the module from the base, grip the center of the base arm and rotate outward releasing the module. To remove the module assembly from the DIN rail, lift the clip arm up and slide the module assembly away from the adjacent module. Pull the locking tab down (out) and lift the assembly off the DIN rail. Refer to the “I/O Module Hot Swap Feature”, page 3–17, in the Terminator I/O Installation and I/O Manual (T1K–INST–M), to remove an I/O module with Terminator I/O system power ON. Assembling the I/O Modules and Bases

Installation and Safety Guidelines

1

3 2

Insert Module into Base 1. Pull base arm back to allow space for module to enter base 2. Align module slides with base track 3. Press module firmly into base

Page 17

Installing the T1K–DEVNETS Base Controller

DIP Switch Settings

2–5

The T1K–DEVNETS controller has a DIP Switch which is used to set baud rates, initializing and the state of outputs if a communication error occurs. The DIP Switch is located on the side of the unit, opposite the power supply.

Note: Be sure to look closely at the default settings below. If you are connecting to an existing DeviceNet network, you may need to change the DeviceNet Baud Rate on your T1K–DEVNETS. The factory default baud rate is 125kbps.

OFF ON SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8

DeviceNet Baud Rate 16/32 Bit/Channel Analog Selection

I/O Polling Diagnostics Enable/Disable Hold Outputs (on Comm. Error) Maintenace Port Baud Rate Maintenace Port Protocol Selection Maintenace Port RTS/CTS Control Enable/Disable Factory Default Settings Shown (all OFF)

The DIP Switch is on this side.

Installing the DeviceNet Base Controller

DIP SW

Set the DeviceNet baud rate. DeviceNet Baud Rate SW1

SW2

125 kbps

OFF

OFF

250 kbps

ON

OFF

500 kbps

OFF

ON

Reserved

ON

ON

Installation and Safety Guidelines

Baud Rate

Analog Bit Selection No. of Bits

SW3

Description

32

OFF

Defaults to original 2–word (32 bits) per analog channel.

16

ON

N/A

Parameter Table System V–Memory

Description

SW3=OFF

SW3=ON

Comment

V7614

Input register: Starting location

V3000

V3000

Read only

V7615

Input Register: Number of bytes

58 Bytes

128 Bytes

Read only

V7616

Output Register: Starting location

V3100

V3100

Read only

V7617

Output Register: Number of bytes

52 Bytes

128 Bytes

Read only

Page 18

2–6

Installing the T1K–DEVNETS Base Controller

Disable I/O Polling Diagnostics * I/O Diagnostics

SW 4

Enable

OFF

Disable

ON

Installing the DeviceNet Base Controller

* If DIP Switch 4 is in the OFF (default) position, you must allow for two additional bytes on the input (RX) and two additional bytes on the output (TX) for Terminator I/O diagnostic functions. Refer to page B–6 for the I/O diagnostic information. Maintenance Port Protocol Selection

Outputs

SW5

Baud Rate

SW 6

Protocol

SW7

Turn Off

OFF

9600 bps

OFF

Normal

OFF

Hold

ON

19200 bps

ON

ASCII

ON

Maintenance Port RTS/CTS Control

T1K–DEVNETS setup parameters

SW 8

RTS/CTS

Description

OFF

Disable

RTS/CTS not available

ON

Enable

RTS/CTS available

Setting up the parameters of the T1K–DEVNETS will set the values to special registers when power is applied to it. When the registers are set to the correct range, their parameters will be stored in EEPROM, and the parameters will be retained when power is turned off. Refer to the following table.

Parameter Table System V–Memory Installation and Safety Guidelines

Maintenance Port Baud Rate

Hold Outputs

Description

Value when the scratch pad is initialized

Range

V7614

Input register: Starting location

V3000

V0 – V7377

V7615

Input Register: Number of bytes

58 Bytes

0 – 128

V7616

Output Register: Starting location

V3100

V0 – V7377

V7617

Output Register: Number of bytes

52 Bytes

0 – 128