Page 10
1–4
Getting Started
Installation and Safety Guidelines
Getting Started
Introduction to DeviceNet
DeviceNet Concepts
The ODVA
DeviceNet is a low-level network designed to connect factory-floor devices to control systems. There are a host of manufacturers of DeviceNet products, offering an array of products including sensors, motor drives and starters, PLCs, pushbuttons, remote I/O systems, etc. Here are some DeviceNet concepts you may find helpful. • DeviceNet supports various communication structures including Peer to Peer, Multi-master and Master/Slave. The T1K–DEVNETS uses the predefined Master/Slave connection. • DeviceNet has two types of messaging: Explicit Messaging and I/O Messaging. • Explicit Messaging is low priority, not time-critical and usually for configuration/diagnostic purposes. • I/O Messaging is time-critical and high priority for I/O data transfer. I/O Messaging comes in four types: • Strobed • Polled (The T1K–DEVNETS only supports Polled.) • Change of State (or COS) • Cyclic • A single DeviceNet network is limited to 64 nodes. A node can be a single-bit device, such as a limit switch, or a remote I/O slave with several I/O modules, such as the T1K–DEVNETS. The Master (Scanner) is usually assigned to node address 0, and many Slave devices have a factory default node address of 63. • DeviceNet has the following data rates (with maximum bus lengths): • 125 kbps (bus length = 500m max.) • 250 kbps (bus length = 250m max.) • 500 kbps (bus length = 100m max.) • The 24V DeviceNet power supply must be grounded at only one point. The V– terminal must be tied to Protective Earth Ground at the power supply only. The DeviceNet standard is maintained by the ODVA (Open DeviceNet Vendor Association, Inc.). Contact the ODVA for detailed information about DeviceNet. Open DeviceNet Vendor Association, Inc. 20423 State Road 7 Suite 499 Boca Raton, FL 33498 Phone: (954) 340–5412 Fax: (954) 340–5413 Internet: www.odva.org Email: odva@powerinternet.com
Page 11
Introduction
1–5
Terminator I/O System
Power Supply
DeviceNet Base Controller
Getting Started
Terminator I/O is a modular system which combines the functions of terminal blocks and I/O modules for distributed I/O. Each Terminator I/O system has the following components: a Power Supply, a Base Controller, and one or more I/O Module(s).
I/O Modules
I/O Module
Installation and Safety Guidelines
I/O Base
Mini Glossary
Below is a small glossary of terms used in this manual. Scanner or Master
The DeviceNet Master of which the T1K–DEVNETS is a slave. This can be either a PLC module or a card in your PC.
Controller or Slave
Short for the T1K–DEVNETS Base Controller. The controller is also referred to as a Network Interface Module elsewhere.
Node Address or MAC ID
The unique device address on a DeviceNet network. There are a maximum of 64 total (0–63). Usually the scanner is node 0.
Page 12
1–6
Getting Started
Getting Started
T1K–DEVNETS Base Controller
T1K–DEVNETS Base Controller Features
The T1K–DEVNETS Base Controller is a slave module that functions as a controller for Terminator I/O on a DeviceNet network. The Controller has the following features: • Status LEDs (Module and Network) • Serial Port • Node Address Switches • Output Enable Switch • DeviceNet Connector
Clip Arm
Status LEDs
Output Enable/Disable Switch Node Address Switches
Installation and Safety Guidelines
Serial Port
DeviceNet Connector Locking Tab
Page 13
Installing the T1K–DEVNETS Base Controller
12
In This Chapter. . . ., Installing the T1K–DEVNETS Base Controller, Configuring the Controller, Master/Slave Communications, Terminator I/O Backplane Communications
Page 14
2–2
Installing the T1K–DEVNETS Base Controller
Installing the T1K–DEVNETS
Installing the DeviceNet Base Controller
Mounting on DIN Rail
2
3
1 NOTE: Do not force the base controller onto the DIN rail. Due to slight size variations in different manufacturer’s DIN rail, it may be necessary to first unlatch the locking tab, rotate the module into place, then latch the locking tab.
1. Make sure the locking tab is in the latched position (pushed in).
Installation and Safety Guidelines
2. Hook upper tab over upper flange of DIN rail. 3. Tilt the unit toward DIN rail until it snaps securely to DIN rail.
Connecting the Controller to a Power Supply
Slide the controller onto the DIN rail until the clip arm attaches securely to the power supply. WARNING: Power to the T1K Power Supply must be disconnected before installing or removing the T1K–DEVNETS. Failure to disconnect power could result in serious damage to the module, to the power supply or both.
Page 15
Installing the T1K–DEVNETS Base Controller
2–3
Setting the Node Address
Connecting the Components on the DIN Rail
Installing the DeviceNet Base Controller
Use a small flat screwdriver to set the Node Address to an available Node Address (or MAC ID), from 0 – 63. Note that X10 represents the tens place and X1 represents the units place.
Slide the module assembly onto the DIN rail until the clip arm attaches securely to the adjacent module. Installation and Safety Guidelines
WARNING: Again, be sure that the power to the T1K Power Supply is disconnected before installing or removing the module assemby. Failure to disconnect power could result in serious damage to the modules, to the power supply or to the entire assembly.
Page 16
2–4
Installing the T1K–DEVNETS Base Controller
Installing the DeviceNet Base Controller
Removing I/O Modules from the Base
To remove the module from the base, grip the center of the base arm and rotate outward releasing the module. To remove the module assembly from the DIN rail, lift the clip arm up and slide the module assembly away from the adjacent module. Pull the locking tab down (out) and lift the assembly off the DIN rail. Refer to the “I/O Module Hot Swap Feature”, page 3–17, in the Terminator I/O Installation and I/O Manual (T1K–INST–M), to remove an I/O module with Terminator I/O system power ON. Assembling the I/O Modules and Bases
Installation and Safety Guidelines
1
3 2
Insert Module into Base 1. Pull base arm back to allow space for module to enter base 2. Align module slides with base track 3. Press module firmly into base
Page 17
Installing the T1K–DEVNETS Base Controller
DIP Switch Settings
2–5
The T1K–DEVNETS controller has a DIP Switch which is used to set baud rates, initializing and the state of outputs if a communication error occurs. The DIP Switch is located on the side of the unit, opposite the power supply.
Note: Be sure to look closely at the default settings below. If you are connecting to an existing DeviceNet network, you may need to change the DeviceNet Baud Rate on your T1K–DEVNETS. The factory default baud rate is 125kbps.
OFF ON SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
DeviceNet Baud Rate 16/32 Bit/Channel Analog Selection
I/O Polling Diagnostics Enable/Disable Hold Outputs (on Comm. Error) Maintenace Port Baud Rate Maintenace Port Protocol Selection Maintenace Port RTS/CTS Control Enable/Disable Factory Default Settings Shown (all OFF)
The DIP Switch is on this side.
Installing the DeviceNet Base Controller
DIP SW
Set the DeviceNet baud rate. DeviceNet Baud Rate SW1
SW2
125 kbps
OFF
OFF
250 kbps
ON
OFF
500 kbps
OFF
ON
Reserved
ON
ON
Installation and Safety Guidelines
Baud Rate
Analog Bit Selection No. of Bits
SW3
Description
32
OFF
Defaults to original 2–word (32 bits) per analog channel.
16
ON
N/A
Parameter Table System V–Memory
Description
SW3=OFF
SW3=ON
Comment
V7614
Input register: Starting location
V3000
V3000
Read only
V7615
Input Register: Number of bytes
58 Bytes
128 Bytes
Read only
V7616
Output Register: Starting location
V3100
V3100
Read only
V7617
Output Register: Number of bytes
52 Bytes
128 Bytes
Read only
Page 18
2–6
Installing the T1K–DEVNETS Base Controller
Disable I/O Polling Diagnostics * I/O Diagnostics
SW 4
Enable
OFF
Disable
ON
Installing the DeviceNet Base Controller
* If DIP Switch 4 is in the OFF (default) position, you must allow for two additional bytes on the input (RX) and two additional bytes on the output (TX) for Terminator I/O diagnostic functions. Refer to page B–6 for the I/O diagnostic information. Maintenance Port Protocol Selection
Outputs
SW5
Baud Rate
SW 6
Protocol
SW7
Turn Off
OFF
9600 bps
OFF
Normal
OFF
Hold
ON
19200 bps
ON
ASCII
ON
Maintenance Port RTS/CTS Control
T1K–DEVNETS setup parameters
SW 8
RTS/CTS
Description
OFF
Disable
RTS/CTS not available
ON
Enable
RTS/CTS available
Setting up the parameters of the T1K–DEVNETS will set the values to special registers when power is applied to it. When the registers are set to the correct range, their parameters will be stored in EEPROM, and the parameters will be retained when power is turned off. Refer to the following table.
Parameter Table System V–Memory Installation and Safety Guidelines
Maintenance Port Baud Rate
Hold Outputs
Description
Value when the scratch pad is initialized
Range
V7614
Input register: Starting location
V3000
V0 – V7377
V7615
Input Register: Number of bytes
58 Bytes
0 – 128
V7616
Output Register: Starting location
V3100
V0 – V7377
V7617
Output Register: Number of bytes
52 Bytes
0 – 128