Page 21

Automotion, Inc. LC4/5 User's Manual

16 AC NEUTRAL POWER INPUT PORT. LC4- 115 VOLTS AC,50/60 Hz. LC5- 208/220 VOLTS AC, 50/60 Hz, (Not Fused.).

cally shut down. If the surface temperature of the mounting base of heat sink is around or above 50 degrees Celsius, additional forced air cooling will be required. Do not place the LC4/5 in an environment subject to high vibrational stress. If this is necessary, contact AUTOMOTION.

17 AC HOT POWER INPUT PORT. LC4- 115 VOLTS AC, 50/60Hz. LC5- 208/220 VOLTS AC, 50/60 Hz, (Fused).

This product contains capacitors which store a high voltage electric charge for several minutes after all outside power is removed. Beware that at least 12 minutes must pass after all external power is disconnected before this product may be physically handled.

18 MOTOR PHASE #1 OUTPUT. 19 MOTOR PHASE #2 OUTPUT. 20 MOTOR PHASE #3 OUTPUT.

10.0

Installation: Mechanical:

10.1

General Information for all Installations:

10.2

Never mount this product in the vicinity of combustible materials. Never use this product in an atmosphere of potentially explosive or highly combustible gas and/or dust. Direct contact with liquids, corrosive chemicals, or corrosive gases must be avoided. The LC4/5 10.3 must be used in environments which have a supply of clean and dry air. High humidity is to be avoided where there is a risk of condensation. The LC4/5 must always be located inside an enclosure which is both intrinsically fire safe and electric shock safe. This may necessitate the need for safety interlocks on the outside enclosure to disconnect all power whenever service is performed. Mount the LC4/5 vertically on a clean and flat surface. This will provide natural convection air cooling. The need for forced air cooling may be required in environments with high ambient air temperatures and/or heavy duty cycles. Whenever the heat sink temperature reaches approximately 50 degrees Celsius (122 degrees Fahrenheit), the LC4/5 will automati-

20

Packaged Models: The LC4/5 model "P" unit is a packaged device designed to conform to NEMA type 1 standards. The control is designed to mount vertically so that convection air flows naturally through the heat sink fins. If the control is mounted in any other manner, forced air cooling may be required. Notches in the side brackets are provided for mounting the unit. Never drill holes into or mount brackets upon the case.

Open Frame Models: The LC4/5 model "O" unit is an open frame device. It has no cover wrapped around it which is designed to provide complete mechanical or electrical protection. This requires the user to provide adequate protection as needed. In particular the user must mount and use the LC4/5 open frame control inside of a protective enclosure which is both fire safe and electric shock safe. The open frame device is designed to be mounted upon a cold plate surface. This means it must be placed upon a surface which has sufficient thermal mass to draw the heat away from the rear mounting surface of the control.

Page 22

Automotion, Inc. LC4/5 User's Manual

11.0

Running the Motor With the LC4/5 Control - OPEN LOOP:

11.1

Set up:

The Appendix shows several examples of how an external speed control may be provided in the open loop mode.

To operate the LC4/5 control in an open loop mode means that there is not any built-in means of speed regulation. Rather, the speed will be governed based upon the analog signal supplied on Terminal #9. Other factors influencing speed stability in an open loop mode are the load applied to the motor, the AC line voltage stability, and the maximum current delivery of the LC4/5 model being used. To set up the control for open loop operation, examine FIGURE 4 or FIGURE 5. Locate and adjust the Velocity Set #1 and the Tach Gain pots fully counter-clockwise. Locate and adjust the Velocity Set #2 pot fully clockwise. These three pots are approximately 17 turn devices and to adjust them will usually produce a noticeable "click" when they are at the fully CCW or CW extremes. Also decide how much, if any, "Soft Start" time is needed, and how much current limited output is required. Refer to Section 17.0, "Setting the Maximum Current Limited Output" and Section 16.0, "Using Soft Start."

11.2

Speed Control To control the speed a 0 to +10 volt signal must be applied to Terminal #9. This variable analog 12.0 voltage should be referenced to Terminal #5 (LOGIC GROUND). The amplitude of the analog voltage applied to Terminal #9 linearly 12.1 modulates the duty cycle of the PWM controlled output voltage to the motor windings. At 100% duty cycle modulation the motor will rotate at maximum speed. If the motor is unloaded, the speed will only be limited by the peak-to-peak voltage applied to the motor, which is a nominal +160 volts for the LC4 and +320 volts for the LC5. If the load upon the motor increases enough to cause excessive current to be drawn, the PWM duty cycle will automatically be reduced to limit the peak current level, causing the speed to fall off.

21

Before running the motor, pre-select the commutation phase code, set the motor drive direction by using Terminal #7, and disable the Dynamic Brake by applying 0 volts to Terminal #8. Limitations apply for rapid direction changes at rotational speeds above 1000 RPM. See Section 14.0, "Reversing the Motor, 4 Quadrant Operation." Remember, upon initial power up or after a momentary power loss, the LC4/5 default condition is stop. The start/stop input must be toggled once to start the motor. To start the control, Terminal #6 must be activated by a +5 volt TTL signal. Now the analog voltage may be increased on Terminal #9. If the motor is wired correctly, it should begin to turn slowly, but smoothly, as the analog voltage increases at Terminal #9. Also wire Terminals #10 and #11 to Terminal #5 (LOGIC GROUND) if the internal closed loop speed control is not to be used. When running in the open loop mode, the signal applied to Terminal #9 proportionally controls the amount of modulation applied to the motor. However, the speed of the motor in the open loop mode will NOT necessarily vary in direct proportion to the voltage applied to Terminal #9.

Running the Motor With the LC4/5 Control - CLOSED LOOP: Set up: To operate in a closed loop mode the speed is regulated through a means of feedback control. This feedback system will automatically try to compensate for fluctuations in either the motor load or the supply voltage, which would otherwise change the speed. The built-in closed loop speed control system on the LC4/5 is 2 quadrant only. If the motor speed should overshoot the setpoint or if there is an overriding load, the control will not produce a negative torque on the motor to slow it down. Rather, the LC4/5 will simply stop

Page 23

Automotion, Inc. LC4/5 User's Manual sourcing power to the motor until the speed drops. More elaborate 4 quadrant performance may be achieved with the Forward/ Reverse and/or Dynamic Brake functions, however, certain limitations apply. AUTOMOTION does not recommend toggling the Forward/Reverse line while under closed loop control unless the Current Limit pot setting is set midway. (i.e., 8 turns off fully CCW). The built-in closed loop speed control system on the LC4/5 is designed for 2 quadrant velocity loop control only.

speed. The maximum allowable voltage input on Terminal #10 is +24 volts DC and the minimum voltage input is -0.3 volts DC. The maximum speed level using pot #2 can never exceed the speed setting for pot #1. These two pots can be used for dual RPM level shifting while under closed loop speed control. Just remember to select the desired pot using Terminal #10 as described above.

12.3

The built-in closed loop speed control system on the LC4/5 allows two options for creating a tachometer signal necessary for speed regulation. They are: 1. 2.

1. Internal speed pots 2. Externally supplied voltage reference

12.2

To supply an external reference voltage to set the closed loop speed, adjust both pot #1 and pot #2 to their fully CCW positions. These pots are 17 turn types. Use Terminal #11 as the input port for this externally supplied signal. The signal amplitude applied to Terminal #11 should range from 0 to +10 volts for full range control. The maximum voltage should not exceed +12 volts or be less than -0.3 volts. When Terminal #11 is not in use it should be left disconnected or strapped to Terminal #5 (LOGIC GROUND). After the Tach Gain Pot is adjusted, the voltage span to attain full speed may become very narrow. External scaling may be effected through the use of a series resistor with terminal #11.

Hall Signal feedback External encoder feedback

The Hall signal feedback is provided by the motor. It is not as effective as a high resolution encoder at low speeds or where tight speed regulation is required (< +/- 1%). In general, the Hall signal approach is suitable for speeds above 350 RPM. To select the Hall signal feedback mode, place the jumper in Group 1 in position "A". Place it in position "B" to select the external encoder feedback mode. Speed stability with either approach is influenced by the setting of the Tach Gain pot, the Slew pot, the load, and the total dynamic speed range of the motor. To control the closed loop speed, the LC4/5 allows two options. They are:

Use of Internal Speed Pots: To use the internal speed pots, note the front panel layout in FIGURE 4 or FIGURE 5. There are two on-board pots used for setting the closed loop speed. They are designated "Vel. Set #1" and "Vel. Set #2." With a TTL logic level "0" input on Terminal #10, pot #1 is automatically selected as the primary speed control pot. "Vel. Set #2" is your secondary speed control pot selected by TTL logic level "1" input on Terminal #10. Both pots are 17 turn devices with full CW producing maximum

22

Use of an External Voltage Reference:

12.4

Tach Gain and Slew Adjustments: When using closed loop control, the proper adjustment of the tach gain pot will impact the performance of the motor under changing load conditions. Automotion recommends that, initially, the tach gain pot, which is a 17 turn device, be set approximately halfway. This establishes a moderate tach gain. Higher or lower gain may be needed later, depending upon the desired system response and stiffness. In general, a higher tach gain setting will provide for a lower speed drop as the motor load increases. If the motor vibrates, or the speed is erratic, the LC4/5 could be in a current limit mode or there could be too much system gain, or poor loop compensation. One possible solution is to adjust the slew pot to reduce the loop response {i.e.,CCW}. If the LC4/5 is in a

Page 24

Automotion, Inc. LC4/5 User's Manual current limit mode the "Current Limit" red LED will glow.

14.0

The slew pot helps produce a lag in overall loop response when operating under closed loop conditions. This pot should be left in the fully CW position for the fastest loop response. Before operating the LC4/5 under internal closed loop control disconnect any input connection to Terminal #9. It could prevent proper performance of the internal closed loop system. Please refer to Appendices for additional information and suggested wiring connections.

The LC4/5 control permits the reversal of the motor while in motion. However, some discretion is required when under closed loop or operating above the 1000 RPM level. Please refer to Appendix for additional information and suggested wiring connections. A 4 quadrant drive means the motor and control can produce a negative torque which opposes the direction of shaft rotation. This negative torque is limited by the maximum output current and the torque constant of the motor. This operation is different than dynamic braking since the effects of negative torque by dynamic braking decrease with lower shaft speeds.

13.0 External PWM Speed Control: An external digital PWM signal can be used to control the output modulation to the motor. If one is used, AUTOMOTION recommends that the base frequency be no higher than 20 KHz. To set-up external PWM, place the LC4/5 in the Stop mode. Next, strap Terminal #9 to Terminal #4. Examine FIGURE 4 or FIGURE 5 to locate and place the Group 1 jumper in position "C". The external PWM signal source must be fed into the LC4/5 via Terminal #12. This signal source should be TTL compatible. The logic inside the LC4/5 is positive true. A logic high level for the PWM signal translates into an ON condition in the output amplifier. The external PWM source will have complete speed control over the motor. except when the output is in a current limited state. Whenever the motor goes into current limit the output modulation and override the external PWM source. If the motor goes into a current limit mode, the Current Limit LED on the front panel will glow. The brighter the glow, the higher the peak current draw. Precise speed may be difficult to maintain when operating in a current limit mode.

23

Reversing the Motor, 4 Quadrant Operation:

Under closed loop control, if the motor is to be subject to direction reversals AUTOMOTION requires that the Current Limit setpoint be reduced. Looking at the front panel find the Current Limit pot. This pot should be adjusted for a halfway position (approximately 8 turns off the fully CCW position).

15.0

Dynamic Braking the Motor: When it is desirable to dynamically brake the motor, Terminal #8 should be toggled to a TTL logic ``1'' level. The maximum signal amplitude allowed here is +24 volts. To release the dynamic brake pull Terminal #8 down to LOGIC GROUND potential as found on Terminal #5 or apply a TTL logic ``0'' level signal. Do not take the voltage on Terminal #8 below LOGIC GROUND potential, which is 0 volts. In order for the dynamic brake to be fully effective, the voltage on Terminal #9 during the braking cycle must be +10 volts DC. Any voltage less than +10 volts DC will begin to diminish the effectiveness of the dynamic brake. This has the benefit in allowing the deceleration rate to be controlled. However, the effect of the brake drops off rapidly with

Page 25

Automotion, Inc. LC4/5 User's Manual

16.0 voltage levels much below +9 volts DC on Terminal #9 during a dynamic brake cycle.

LC4/5, the Start/Stop input must be toggled from OFF to ON.

The standard dynamic brake feature can absorb energy at a rate of 10 Watts continuously and 650 Watts intermittently. This translates into a maximum duty cycle rate 2% ON and 98% OFF, or 3 Seconds ON and 150 Seconds (or longer) OFF. If higher rates are required, consult AUTOMOTION.

You can remotely control the trip level of current limit by feeding a digital pulse signal, between 2 and 10 uSec. in duration, into Terminal #14. This signal must be +12 volts in amplitude as referenced to Terminal #5 (LOGIC GROUND). When a +12 volt digital pulse with a fast leading edge is applied to Terminal #14, the LC4/5 will turn off output amperage to the motor until the next cycle begins on the internal 18 KHz PWM oscillator.

Using Soft Start: The LC4/5 control has a built-in Soft Start feature. This permits the acceleration rate for the motor to be controlled. To locate the Soft Start pot, refer to FIGURE 4 or FIGURE 5. When adjusted to the maximum setting clockwise, the motor will accelerate at the slowest rate. Acceleration at this rate may take 60 seconds or more to reach setpoint speed. When the Soft Start pot is set for the minimum setting (i.e., maximum acceleration) it must be in the fully counter-clockwise position. This pot is a 12 turn device. The Soft Start feature is useful in accelerating delicate loads up to running speeds. The Soft Start feature is only in effect after the Start/Stop input signal on Terminal #6 is toggled. Once the Soft Start cycle times out, it cannot be repeated until the Start/Stop input is again toggled OFF and back ON.

17.0

Setting the Maximum Current Limited Output:

This is useful when used in conjunction with the Current Signal Output Option which can be ordered with the LC4/5. The combination of this option and a simple comparator circuit will allow the user to remotely control the current limit setpoint.

18.0

In Case of Trouble: Should your motor and LC4/5 control not perform properly after following the installation and operation procedures, read through this list of symptoms.

18.1

Symptom 1: Running the motor in the open loop mode nothing happens (i.e., the rotor does not move at all once power is applied). * SOLUTION *

The Current Limit pot located on the front panel of the LC4/5 (See FIGURE 1) is used to set the maximum current limited delivery from the LC4/5 control. The peak current output will reach a maximum level after approximately 17 full CW turns on the Current Limit pot. The relationship between the actual current limit and the pot setting is linear. When the LC4/5 is in a current limit mode, the ``Current Limit'' red LED will glow. Should the rotor of the motor ever become firmly locked during a run condition, the LC4/5 will automatically shut down after a few seconds and the ``Current Limit'' red LED will glow brightly. To restart the

24

Check that only the Green LEDs are lit. If all LEDs are off, check that the AC power supply connections are correct and that 115 volt AC power is applied. Check the fuse. If the fuse is blown check each output connection for shorts or otherwise improper wiring. If the fuse blows a second time contact AUTOMOTION immediately. Should any red LEDs be lit, see the LED diagnostics chart for advice. The motor will not run in the open loop speed control mode without a voltage above LOGIC GROUND up to +10 volts being applied to Terminal #9. Try toggling the Start/Stop input port, Terminal #6,

Page 26

Automotion, Inc. LC4/5 User's Manual first to 0 volts DC and then to +5 volts DC. Remember that a 0 volt DC signal is required at the Dynamic Brake input port, Terminal #8. Both closed loop speed control pots, Vel. Set #1 and #2, must be set FULLY CCW and the Tach Gain pot must be set FULLY CCW in order to attain full open loop rotor speed. Note that all external logic control signals applied to the LC4/5 must be referenced to Terminal #5 (LOGIC GROUND).

commutation efficiency. When the commutation is properly ``NEUTRALIZED,'' the motor will run at the same RPM in both directions while unloaded using a constant speed control signal into Terminal #9. Has jumper Group 2 (See FIGURE 4 or FIGURE 5) been properly programmed to select either 120 or 60 degree phase shift for the commutation signals?

Are the three motor phase output connections connected? Are all of the LC4/5 wiring connections placed into their respective terminals securely?

18.3

The rotor jerks erratically back and forth, or the motor vibrates while in motion.

Are the front panel connectors snapped into place securely?

* SOLUTION *

Check your three rotor positional sensors for proper electrical connections and check that you have properly selected your sensor signal phase angle. Are the three rotor position sensor signals, designated S1, S2 and S3, of proper amplitude? (i.e., +12 volts DC for a ``1'' state and 0 volts for a ``0'' state. See FIGURE 3). The Appendix contains suggested wiring connections for several popular brushless motor manufacturers.

18.2

Symptom 3:

Are motor output phase connections connected and in the correct order? Also perform the same check upon the three rotor positional sensor connections. Has jumper Group 2 (See FIGURE 4 or FIGURE 5) been properly programmed to select either 120 or 60 degree phase shift for the commutation signals? Check the dynamic balance of your motor and load.

Symptom 2: When running the motor without a load, the operating current seems to be excessive, or the motor vibrates at low RPM. Alternatively, the motor must be hand-turned to start rotation.

If you are using internal closed loop speed control, try reducing the slew pot setting or reducing the tach gain setting. See Section 12.4 for details.

18.4

* SOLUTION * Check the position of your commutation sensors located within or upon the motor frame. They must be adjusted for optimum commutation efficiency. Rotate the sensor assembly a few degrees both CW and CCW relative to the stator and again try running the motor. If the current begins to increase or decrease, the sensor assembly may be misaligned. Adjust it accordingly to reduce the unloaded current drawn and improve

25

Symptom 4: When running the motor, the rotor hums and moves very little or not at all. * SOLUTION * Check status of all LEDs. If they are all OFF, read symptom #1 carefully or compare status with the LED Diagnostics Chart in FIGURE 8. Disconnect all power from the LC4/5 control and try to free spin the rotor. Does it bind or

Page 27

Automotion, Inc. LC4/5 User's Manual

LED Diagnostics Chart For use in conjunction with Figures 4 and 5.

FIGURE 8 NOTE! See the manual for additional details on each individual condition listed in the chart above.

26

Page 28

Automotion, Inc. LC4/5 User's Manual feel excessively stiff? Investigate for possible motor bearing misalignment or damage.

Check for shorts in the motor phase lines either phase-to-phase or phase-to-ground.

Is the load which is coupled to the rotor shaft excessive or binding? Check this carefully. Try running the motor without the load.

Check your 115 VAC ( for a LC4) or 220 VAC (for a LC5) supply line for severe line transients or surges with high peak voltages. It may be necessary to add an external line filter. Contact AUTOMOTION for suggestions.

Are there any commutation dead spots? Monitor the signals from the three rotor positional sensors, designated S1, S2 and S3 one at a time. Use a voltmeter with power applied to the drive then slowly rotate the motor shaft by hand through one complete revolution. Each transition to a ``1'' state should produce a +12 volt DC signal into the appropriate LC4/5 input terminal. Each transition to a ``0'' state should produce a near 0 volt signal into the appropriate LC4/5 input terminal. Contact AUTOMOTION for details. Check solution for Symptom 3.

18.5

Symptom 7: When dynamically braking the motor, the ``Power/OT Fault'' red LED comes on and the motor shuts down. * SOLUTION * The duty cycle of the dynamic brake may be excessive. Reduce the frequency of braking if possible. Otherwise an auxiliary braking resistor may need to be installed. Contact AUTOMOTION for assistance.

Symptom 5: When the motor begins to accelerate the control shuts down and the motor coasts to a stop. The ``Power/OT Fault'' red LED comes on.

18.6

18.7

18.8

Symptom 8: The dynamic brake has little effect in slowing the motor.

* SOLUTION *

* SOLUTION *

The AC line voltage may be low. Check this carefully.

When the dynamic brake is applied, check the voltage at Terminal #9. This voltage needs to be +10 volts DC. See Section 15.0 for details.

Symptom 6: When attempting to run the motor, the ``Power/OT Fault'' red LED comes on and/or the motor shuts down.

18.9

Symptom 9: When running motor under closed loop control, the speed is not stable.

* SOLUTION *

* SOLUTION *

Check your supply line voltage. If it is below 95 volts AC for a LC4; or if it is below 190 VAC for a LC5; the control will shutdown automatically. Check the temperature of the LC4/5 chassis. If it is near or above 50 degrees Celsius (122 degrees Fahrenheit) the control is too hot and will shutdown automatically.

Check the ``Current Limit'' red LED. If it is glowing then the motor is drawing enough current while spinning to force the drive into a current limit mode. This can adversely affect speed stability because the motor is being starved for sufficient current to operate. Set the Current Limit pot at its maximum CW limit. Check the load upon the motor. Is it excessive

27

Page 29

Automotion, Inc. LC4/5 User's Manual or binding? Does the motor shaft spin freely when the external load is removed? The load upon the motor shaft may be excessive and more power may be required than either the LC4/5 or the motor can deliver. Check the solutions for Symptoms 2 and 4. If the above steps fail to correct the problem, contact AUTOMOTION. DO NOT attempt to service the LC4/5 control. To do so will immediately void the warranty and expose the user to hazardous voltages.

19.0

Optional Equipment:

19.1

Current Signal Output Option:

VEL. SET #1 VEL SET #2 TACH GAIN SLEW

The optional current signal output feature must be configured at the time of purchase and cannot be added in the field. This option produces an analog signal output which is proportional to the delivered amperage through the motor. The calibration factor for this analog signal is approximately +.05 volts per Amp. There is a built-in offset voltage of approximately +6 volts DC. The amperage signal will ride on top of this offset voltage. Some low pass filtration may be needed for this signal because the drive's 18 KHz chopping rate will cause this signal to have some high frequency ringing upon it. The appropriate time constant for this filter will vary depending upon the application. AUTOMOTION will be pleased to provide application support if needed. The maximum load impedance on Terminal #13 should be no less than 10K ohm. Refer to Section 9.0, ``Input/Output Terminal Identification,'' and FIGURE 9 for additional information.

19.2

Terminal #9 on the LC4/5. Please note that Terminal #9 is the open loop input port for the LC4/5. The speed may then be throttled and the direction of rotation controlled by using a singular bipolar analog signal into Terminal #9 when using this option. However, the LC4/5 will NOT regulate speed under varying load conditions when using this option. The user must provide for the closed loop speed regulation in their external system hardware. When the LC4/5 is equipped with this option the following pots are disabled permanently:

+/- 10 Volt Analog Control Option: The LC4/5 may be purchased with an option to permit the user to use an external +/- 10 Volt signal to control the motor velocity. If your drive is equipped with this option, your +/- 10 Volt control signal must be coupled into

28

This means that the LC4/5's on board 2 quadrant speed control system is nonfunctional. To use the LC4/5 when equipped with this option, the absolute amplitude of the applied signal on Terminal #9 controls in direct proportion the amount of applied voltage modulation to the motor. This means 0 Volts translates into approximately 0% PWM output and +/-10 Volts translates into approximately 100% PWM output to the motor. The level of applied modulation may or may not vary the speed of the motor in a linear fashion. Linearity is a function of a number of factors, such as motor design and motor load. This is why if precise speed control is needed, an external speed regulator system is required. The input impedance looking into Terminal #9 on the LC4/5 equipped with this option is approximately 5K Ohm. The polarity of the applied signal into Terminal #9 controls the direction of shaft rotation. The relative direction of shaft rotation for positive or negative signal polarity may be programmed into the LC4/5 by the user if a jumper wire is connected between Terminal #7 and either Terminal #4 or Terminal #5. Do NOT ever short Terminals #4 and #5 together.

Page 30

Automotion, Inc. LC4/5 User's Manual

19.3

External Variable DC Bus Input Option: The LC4/5 product may be purchased with an option to permit the user to supply a variable DC rail input to the drive. This substitutes for the fixed voltage AC power source normally used as a power supply for the motor rail. This option must be configured at the factory. It allows the user to supply an external rail of either 15 to 200 volts DC for a LC4 model, or 15 to 400 volts DC for a LC5 model. This is done through a separate 2 pin power connector that is installed when this option is specified. See APPENDIX for details.

The bottom of this page left intentionally blank.

29