The text of a spec sheet · part 1 of 2
CPUs: CP430, CP470, CP474, CP770 and CP774, pages 1 to 7
Pages 1 to 7 of 13
The original document is the PDF (1.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the B & R Automation CP430 and B & R Automation CP474
Page 1
CPUs • CP430, CP470, CP474, CP770 and CP774
1. CP430, CP470, CP474, CP770 and CP774 1.1 Order data
CP430, CP470, CP770
CP474, CP774
Model number
Short description
7CP430.60-1
2003 CPU, 100 KB SRAM, 256 KB FlashPROM, 24 VDC, 7 W supply, 1 RS232 interface, 1 CAN interface, CAN: electrically isolated, network capable, max. 64 digital / 32 analog I/O points
7CP470.60-2
2003 CPU, 350 KB SRAM, 512 KB FlashPROM, 24 VDC, 14 W supply, 1 RS232 interface, 1 CAN interface, CAN: electrically isolated, network capable, max. 128 digital / 64 analog I/O points
7CP474.60-2
2003 CPU, 750 KB SRAM, 512 KB FlashPROM, 24 VDC, 12.6 W supply, 1 RS232 interface, 1 CAN interface, CAN: electrically isolated, network capable, 4 slots for screw-in modules, max. 208 digital / 80 analog I/O points
7CP770.60-1
2003 CPU, 100 KB SRAM, 256 KB FlashPROM, 100-240 VDC, 14 W supply, 1 RS232 interface, 1 CAN interface, CAN: electrically isolated, network capable, max. 128 digital / 64 analog I/O points
7CP774.60-1
2003 CPU, 100 KB SRAM, 512 KB FlashPROM, 100-240 VDC, 12.6 W supply, 1 RS232 interface, 1 CAN interface, CAN: electrically isolated, network capable, 4 slots for screw-in modules, max. 208 digital / 80 analog I/O points Optional accessories
4A0006.00-000
Lithium battery, 3 V / 950 mAh, button cell Note: Backup battery included in delivery
0AC201.9
Lithium batteries, 5 pcs., 3 V / 950 mAh, button cell
0G0001.00-090
Cable PC <-> PLC/PW, RS232, online cable
7AC911.9
Bus connector, CAN
0AC912.9
Bus adapter, CAN, 1 CAN interface
0AC913.92
Bus adapter, CAN, 2 CAN interfaces, including 30 cm attachment cable (DSUB connector)
0MC111.9-1
PC card, 2 MB FlashPROM
0MC112.9-1
PC card, 4 MB FlashPROM
0MC211.9
PC card, 2 MB SRAM
Table 1: Order data
Data sheet V 1.10
1
Page 2
CPUs • CP430, CP470, CP474, CP770 and CP774
1.2 Technical data Name
CP430
CP470 / CP770
CP474 / CP774
Short description System module
CPU
Interfaces
1x RS232, 1x CAN bus
Processor Fastest task class cycle time Typical instruction cycle time Standard memory User RAM System PROM User PROM Data buffering Backup battery Buffer current Typical Maximum
1 ms 1.6 µs
1.6 µs
0.8 µs
100 KB SRAM 256 KB FlashPROM 256 KB FlashPROM
350/100 KB SRAM 512/256 KB FlashPROM 512/256 KB FlashPROM
750/100 KB SRAM 512 KB FlashPROM 512 KB FlashPROM
Lithium battery 3 V / 950 mAh
Lithium battery 3 V / 950 mAh
Lithium battery 3 V / 950 mAh
1.6 µA 60 µA
1.6 µA 60 µA
2.2 µA 110 µA
Hardware watchdog
Yes
Voltage monitoring
Internal supply monitored for overvoltage and undervoltage
Peripherals Real-time clock Resolution
Nonvolatile memory 1s
Status indicators
LEDs
I/O bus interface
9-pin DSUB socket
Slots for screw-in modules Suitable for IF modules
No
No
4 1-3
Interfaces Interface IF1 Type Electrical isolation Design Max. distance Max. transfer rate
RS232 No 9-pin DSUB plug 15 m / 19200 bit/s 57.6 kBit/s
Interface IF2 Type Electrical isolation Design Max. distance Maximum transfer rate
CAN Yes 9-pin DSUB plug 1000 m 500 kBit/s
General information Operation on module slot
1
1
1+2
Logical module slots
Max. 4
Max. 8
Max. 12 analog module slots
Max. 2
Max. 4
Max. 4
Possible module addresses for analog modules
1-4
1-8
1-8
Table 2: Technical data
2
Data sheet V 1.10
Page 3
CPUs • CP430, CP470, CP474, CP770 and CP774 Name
CP430
CP470 / CP770
Visual Components capability
CP474 / CP774
No
ACOPOS capability
No
No
Certification
Yes
CE, C-UL-US, GOST-R
Mechanical characteristics Dimensions
System 2003 single-width
Protection type
System 2003 double-width IP20
Operating temperature Horizontal installation Vertical installation
0°C to +60°C 0°C to +50°C
Storage temperature
-25°C to +60°C
Relative humidity
5 to 95%, non-condensing
Comment
Backup battery included in delivery
Power supply
CP430
CP470/CP474
CP770/CP774
Input voltage Minimum Rated Maximum
18 VDC 24 VDC 30 VDC
18 VDC 24 VDC 30 VDC
85 VAC 100 - 240 VAC 264 VAC
Input voltage frequency
-
-
47 - 63 Hz
Power consumption
Max. 9.5 W
Max. 20 W
Max. 20 W
7 W 1)
14/12.6 W 1)
14/12.6 W 1)
Output power for I/O ports
Table 2: Technical data (cont.) 1) Integrated power supply on pin 4 of the RS232 interface for simple PANELWARE controllers, e.g. P126.
1.3 Status indicators LED
Meaning
CAN
Data transfer to or from CAN controller
RS232
Indicates if data is being transmitted or received
ERR
Lit when in Service mode
RUN
Lit in RUN and in Service mode
RDY
Lit when in Service mode
MODE
Lit when programming FlashPROM
1, 2, 3, 4 Not lit Blinking slowly
These LEDs show the operating state of the respective screw-in module. Screw-in module defective or not inserted Communication error with screw-in module Exception: On the IF361 and IF371 modules, a slow-blinking LED means that frame driver communication is running correctly. Screw-in module is new or has been exchanged with another module type Screw-in module is ready for operation
Blinking quickly Lit
Table 3: Status indicators
Data sheet V 1.10
3
Page 4
CPUs • CP430, CP470, CP474, CP770 and CP774
1.4 Power supply The CPUs are either supplied with 24 VDC or with 100 to 240 VAC. The pin assignments are printed on the module. CP430, CP470, CP474
CP770, CP774
Both "+" and "-" pins are connected to each other internally
Both "N" and "L" pins are connected to each other internally
Table 4: Power supply
1.5 Interfaces The CPU has two interfaces:
CAN RS232
Figure 1: Interfaces
4
Data sheet V 1.10
Page 5
CPUs • CP430, CP470, CP474, CP770 and CP774
1.6 CAN bus The electrically isolated standard fieldbus interface is used for the following tasks: •
Communication with other control systems
•
System decentralization and remote I/O expansion using System 2003 components and a CAN bus controller
We recommend using the 7AC911.9 T-connector for coupling to a CAN network. A terminal resistor is integrated into the T-connector for the bus termination, which can be switched on or off. CAN interface Pin
Assignment
1
NC
2
CAN_L
3
CAN_GND
4
NC
5
NC
6
Reserved
7
CAN_H
8
NC
9
NC
9-pin DSUB plug
Table 5: Pin assignments for CAN interface
1.7 RS232 interface This interface, which is not electrically isolated, is primarily intended for programming the CPU. The RS232 interface can also be used as a general interface (e.g. P126 visualization, printer, bar code reader, etc.). RS232 interface Pin
Assignment
Name
1
NC
Reserved
2
RXD
Receive signal
3
TXD
Transmit signal
4
+5 VDC / max. 500 mA
Panel supply
5
GND
Ground
6
NC
Reserved
7
RTS
Request To Send
8
CTS
Clear To Send
9
GND
Ground
9-pin DSUB plug
Table 6: Pin assignments for RS232 interface
Data sheet V 1.10
5
Page 6
CPUs • CP430, CP470, CP474, CP770 and CP774
1.8 Mode switch
Figure 2: Mode switch
The operating mode is set with the Mode switch. The switch setting can be evaluated by the application program at any time. The operating system only interprets the switch position when switched on. Switch position
Operating mode
$0
Boot
In this switch position, the operating system can be installed via the RS232 interface configured as online interface. User Flash is only deleted after the update begins.
Description
$1 - $8
Run
RUN mode, the application is running. These switch settings are freely available for use in an application (e.g. CAN node number).
$9 - $E
Reserved
Reserved for B&R expansions – these settings are not allowed to be used!
$F
Diagnostics
The CPU boots in diagnostics mode. Program sections in User RAM and User FlashPROM are not initialized. After diagnostics mode, the CPU always boots with a cold restart.
Table 7: Operating modes
1.9 Programming the System Flash 1.9.1 General information CPUs are delivered with a runtime system. The node number switch is set to switch position $0 when delivered i.e. bootstrap loader mode is set. A corresponding switch position must be set ($1 to $8) in order to boot the PLC in RUN mode. A runtime system update is only possible in RUN mode. 1.9.2 Runtime system update The runtime system can be updated using the programming system. When updating the runtime system (online runtime system update), the following procedure must be carried out: 1) An online runtime system update is only possible if the processor is in RUN mode. To do this, the set node number must be in the range from $1 to $8. 2) Switch on the power. 3) The runtime system update is performed via the existing online connection. An online runtime update is possible using the serial RS232 onboard interface. 4) Start B&R Automation Studio.
6
Data sheet V 1.10
Page 7
CPUs • CP430, CP470, CP474, CP770 and CP774 5) Start the update procedure by calling the Services command from the Project menu. Select Transfer Operating System... from the menu shown. Now follow the instructions from B&R Automation Studio. 6) A dialog box is displayed for configuring the runtime system version. The runtime system version is already pre-selected by the user's project settings. Using the drop-down menu, the runtime system versions stored in the project can be selected. Clicking on the Browse button allows the selected runtime system version to be loaded from the hard drive or from the CD. Pressing Next > opens a pop-up window, which allows the user to select whether the modules should also be downloaded with SYSTEM ROM as the target memory during the following runtime system update. Otherwise, modules can also be downloaded later together with an application download. After pressing Next >, a dialog box appears where the user can set the CAN transfer rate, CAN ID and the CAN node number (the CAN node number set here is only relevant if an interface module does not have a CAN node number switch). The CAN node number must be between decimal 01 and 99. It's made up of the switch position 1 - 8 and a decimal offset entry. Assigning a unique node number is especially important with online communication over a CAN network (INA2000 protocol). 7) The update procedure is started by pressing Next >. The update progress is shown in a message box.
Information: User flash is cleared. 8) When the update procedure is complete, the online connection is automatically reestablished. 9) The PLC is now ready for use. A runtime system update is not only possible using an online connection, but also using a CAN network or a serial network (INA2000 protocol), depending on the system configuration.
Data sheet V 1.10
7