For the B & R Automation CP430 and B & R Automation CP474

Page 8

CPUs • CP430, CP470, CP474, CP770 and CP774

1.10 CP interface The CPUs CP474 and CP774 are equipped with four slots for screw-in modules. The required screw-in modules are inserted into the CP interface and screwed firmly into place. TPU mode is possible on all 4 slots. The screw-in interface modules can be operated in slots 1, 2 and 3.

Figure 3: CP interface

8

Data sheet V 1.10

Page 9

CPUs • CP430, CP470, CP474, CP770 and CP774 1.10.1 Overview The following screw-in modules can be used on the CP interface. Module

Type

7AI261.7

Analog IN

Description 1 input used to evaluate a full-bridge strain gauge

7AI294.7

Analog IN

4 inputs for potentiometer displacement gauge

7AI351.70

Analog IN

1x ±10 V or 1x 0 - 20 mA (1x ±20 mA also possible) potentiometer operation

7AI354.70

Analog IN

4x ±10 V

7AI774.70

Analog IN

4x 0 - 20 mA (4x ±20 mA also possible)

7AO352.70

Analog OUT

2x ±10 V / 0 - 20 mA

7AT324.70

Analog IN

4x temperature sensor (PT100, PT1000, KTY10 or KTY84)

7AT352.70

Analog IN

2x PT100 3-line

7AT664.70

Analog IN

4x thermocouple

7DI135.70

Digital IN

4x 24 VDC, 50 kHz

7DI138.70

Digital IN

10x 24 VDC, 20 kHz

7DI140.70

Digital IN

10x 24 VDC, 50 kHz

7DO135.70

Digital OUT

4x 12 - 24 VDC, 0.1 A, 100 kHz

7DO138.70

Digital OUT

8x 24 VDC, 0.5 A

7DO139.70

Digital OUT

8x 12 - 24 VDC, 0.5 A

7DO164.70

Digital OUT

4x 48 - 125 VAC, 50 mA, zero voltage input

7IF311.7

Interface

1x RS232

7IF321.7

Interface

1x RS485/RS422

7IF361.70-1

Interface

1x Profibus DP slave

7IF371.70-1

Interface

7NC161.7

Encoder module

1x CAN 1x 100 kHz, 5 / 24 VDC

Table 8: Screw-in modules

1.10.2 Commands The following commands can be used on the CP Interface: •

Reading the screw-in module type

•

Switching off automatic mode

•

Switching on automatic mode

1.11 Legend strips A legend sheet can be slid into the front of the CPUs CP474 and CP774 from above. These sheets can be used for labeling the screw in modules.

Data sheet V 1.10

9

Page 10

CPUs • CP430, CP470, CP474, CP770 and CP774

1.12 Data / real-time buffering The battery voltage is checked cyclically. The cyclic load test of the battery does not considerably shorten the battery life, instead it gives an early warning of weakened buffer capacity. The status information, "Battery OK" is available from the B&R TRAP function "SYS_battery".

1.13 System variable SYS2003 1.13.1 General information The system variable SYS2003 is a structure containing the elements "io_scan" and "io_refresh". It must be declared in a task as PLC global. Element

Variable type

Description io_scan

UINT

Duration of the last I/O cycle in µs io_refresh

SINT

0 ... I/O data is more than one cycle old 1 ... I/O data is current

Table 9: System variable SYS2003

Information: If digital IO data points are used in the HSTC (high speed task class), the system variable SYS2003 will also be placed in the HSTC. Values in lower task classes will therefore not be consistent. If no digital I/O data points are placed in the HSTC, the SYS2003 variable will use the 10 ms operating system clock.

10

Data sheet V 1.10

Page 11

CPUs • CP430, CP470, CP474, CP770 and CP774

1.14 Changing the battery 1.14.1 Battery data Model number 4A0006.00-000 0AC201.9

1 pcs. 5 pcs.

Short description

Lithium battery, 3 V / 950 mAh, button cell

Storage temperature

-20 to +60°C

Storage time

Max. 3 years at 30°C

Relative humidity

0 to 95% (non-condensing)

Table 10: Battery data

1.14.2 Buffer duration Buffer current Typical Maximum

CP470 / CP770

CP474 / CP774

1.6 µA

2.2 µA

60 µA

110 µA

Table 11: Buffer duration

Information: B&R recommends changing the batteries after five years of operation. 1.14.3 Procedure The product design allows the battery to be changed with the PLC switched either on or off. In some countries, safety regulations do not allow batteries to be changed while the module is switched on.

Information: Data stored in RAM will be lost if the battery is changed with the PLC switched off. 1) Touch the mounting rail or ground connection (not the power supply!) in order to discharge any electrostatic charge from your body. 2) Remove the cover from the lithium battery holder using a screwdriver.

Data sheet V 1.10

11

Page 12

CPUs • CP430, CP470, CP474, CP770 and CP774 3) Remove the battery from the holder by pulling the removal strip (do not use uninsulated tools -> risk of short circuiting). The battery should not be held by its edges. Insulated tweezers may also be used for removing the battery. Not like this:

Like this:

Figure 4: Handling the battery

4) Insert the new battery with correct polarity. The removal strip should be protruding from the battery holder and the "+" side of the battery should be facing downward. In order to be able to remove the battery again in future, the removal strip must protrude from the upper side of the battery.

The removal strip must protrude from the upper side of the battery

Figure 5: Removal strips

5) Now wrap the end of the removal strip over the top of the battery and insert it underneath the battery so that it does not protrude from the battery holder.

12

Data sheet V 1.10

Page 13

CPUs • CP430, CP470, CP474, CP770 and CP774 6) Replace cover. Ensure that the slot in the edge of the cover faces the front of the module (1). Insert the upper edge of the cover in the battery holder opening (2). Press the lower end of the cover home firmly (3). RDY

MODE

CP470

Œ Ž

Figure 6: Replace cover

Information: Lithium batteries are considered hazardous waste. Used batteries should be disposed of accordingly.

Data sheet V 1.10

13