SC22-3/-3E Safety Controller Instruction Manual: 7 Operating Instructions

Pages 68 to 71 of 122, from SC22-3/-3E Safety Controller Instruction Manual

The original document is the PDF (6.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Banner SC22-3E

Page 68

SC22-3/-3E Safety Controller Instruction Manual

7 Operating Instructions 7.1 Monitoring Controller Operation The Safety Controller can be operated using either the OBI or the PCI interfaces to monitor ongoing status.

7.2 Display Controller Information, PC Interface (PCI) To display real-time Run mode information on a PC, the computer must be connected to the Controller, via a USB cable (see Section 1.3 for connection instructions). Open the Banner Safety Controller program and click on the Live Display button in the PCI screen to launch the Live Display screen. This feature continually updates Run mode data and displays it in a pop-up screen. The Live Display screen provides the same information that can be viewed on the Controller’s LCD. It shows the status of each Safety Output and reports on any input device or system event that can cause a Safety Output to turn OFF.

Figure 47. Live Display screen, PCI

7.3 Display Controller Information, Onboard Interface (OBI) To display current information on the Controller's Onboard Interface screen (OBI), use the Controller's arrow buttons to step through the Run mode menu, as shown.

Run Mode

ESC →

Configuration Mode

View Current Faults

View Fault Log

← OK

ESC →

← OK

Clear Fault Log

Model Number

Configuration Summary

(Section 5.3)

ESC →

← OK

Fault Diagnostics

Terminal Assignments software and hardware versions

ESC →

← OK

System Menu

Input/Outpu t Mapping

Status Output Settings

View Response Times

Figure 48. Run mode menu selections, OBI

7.3.1 Run Mode Screen - OBI The OBI Run mode screen displays current information about the Safety Controller, including: • The configuration name • Safety Output status 68 www.bannerengineering.com - Tel: 763.544.3164

Set Display Contrast

View Network Settings

Configuration Checksum

Page 69

SC22-3/-3E Safety Controller Instruction Manual • • •

Input status System status XM card status

Configuration Name Arrowhead designates selected Safety Output Safety Output Status Input Status Cause of Output SO1 Status, or Required Action Figure 49. Run mode screen - OBI

Configuration Name: The top line of the display reads either the name of the configuration stored in the Safety Controller, if it has been confirmed, or Configuration not confirmed, if it has not. Safety Output Status: Lines 2, 3, and 4 of the screen display the status of the three Safety Outputs. The selected output will have a small arrowhead to its left, on the screen. (The arrowhead scrolls through the Safety Outputs that are OFF, at 2-second intervals.) Line 5 of the display states the reason for the status of the selected Safety Output. NOTE: Output faults are recoverable via a system reset (see section System Resets and Lockout Conditions on page 70). Safety Output Status Message

Cause and/or Required Action

ON

The Safety Output is ON.

ON-Delay

The Safety Output will turn ON when the ON-delay time expires.

OFF

The Safety Output is OFF. Line 5 of the display indicates the reason the Safety Output is OFF.

OFF-Delay

The Safety Output will turn OFF when the OFF-delay expires. Line 5 of the display indicates the reason the Safety Output is in an OFF-delay.

Reset Needed

A manual reset operation needs to be performed. Line 5 of the display indicates the name of the manual reset input to press.

Fault

A problem has been detected with the Safety Output. See section Fault Code Table on page 79 to find additional information regarding the fault. If the fault is due to an external device monitor (EDM) fault, line 5 of the display indicates the name of the EDM.

Enable Mode

Line 5 of the display indicates Enable Mode if a Safety Output is in Enable mode.

Input Status: If a Safety Output is OFF or turning OFF, line 5 of the display indicates information about the input that is keeping the output OFF. Line 5 also indicates when a manual reset operation needs to be performed. NOTE: • Line 5 changes to indicate each input when the status of more than one input must be displayed • Press the Up arrow to pause the screen on the current input • Press the Down arrow to change the last line to the next input (Press the Down arrow repeatedly to quickly cycle through the inputs) • If more than one output is OFF, a small arrowhead indicates the Safety Output to which the input messages correspond, as shown in the preceding figure Input Device Status Message Stop

Cause and/or Required Action The safety input is in a state that causes the Safety Output to turn OFF.

www.bannerengineering.com - Tel: 763.544.3164

69

Page 70

SC22-3/-3E Safety Controller Instruction Manual

Input Device Status Message

Cause and/or Required Action

Test

A start-up test needs to be completed on the safety input. To perform the test, cycle the input (Run-Stop-Run) to turn the Safety Output ON.

Deactivate

A two-hand control input or an enabling device needs to be cycled (Run-Stop-Run) before the Safety Output will turn ON.

Fault

A problem has been detected with an input that controls the output.

Timed Out

The Safety Output is in enable mode and the enabling device active time limit has expired. Cycle the enabling device to turn the output back ON, or turn the enabling device OFF and perform a system reset to exit Enable mode.

Test Active

An AVM test is running. The output will turn ON when the test is complete.

When a Safety Output is ON, no input information is displayed unless a mapped input is muted, bypassed, or in a fault condition. Status Output: Line 5 of the screen displays Mute Lamp Fault when a mute lamp fault exists. System Status: Line 5 of the screen displays System Reset Needed whenever a system reset is needed to turn the Safety Outputs ON. However, when a fault condition exists, the fault must be corrected before the system reset operation will turn the Safety Outputs ON. External Memory Card (XM Card) Status: The status of the XM card is temporarily displayed when it is inserted while the Run mode screen is active. Remove and replace the correct XM card as necessary. XM Card Message XM matches the active configuration

Cause The configuration stored on the card is the same as the Safety Controller’s configuration.

XM does not match the active configuration

The configuration stored on the XM card is different from the Safety Controller’s configuration.

XM has no configuration

The XM card does not have a configuration stored in it.

Figure 50. XM Card status message screens - OBI

7.4 Manual Reset A manual reset operation is valid when all safety inputs mapped to the Safety Output are in the Run state when the manual reset is performed; see section Reset Signal Requirements on page 32. When a single manual reset device is mapped to two or more Safety Outputs, one of which has an OFF-delay, then the manual reset will not be able to turn ON either Safety Output until the OFF-delay time has expired. If a safety input device configured for manual reset changes from the Run state to Stop and back to Run, then any Safety Outputs to which that device is mapped will turn OFF and remain OFF until a valid manual reset is performed.

7.5 System Resets and Lockout Conditions A system reset is necessary under the following conditions: 70 www.bannerengineering.com - Tel: 763.544.3164

Page 71

SC22-3/-3E Safety Controller Instruction Manual • • • • • • •

Recovering from a lockout condition Starting the Controller after a new configuration has been downloaded Recovering from an output fault Entering Run mode after power-up, when configured for manual power-up Exiting Enable mode Recovering from an AVM fault Recovering from a two-hand control input fault

A system reset is used to clear lockout conditions not related to safety inputs. A lockout condition is a response where the Controller will turn Off all affected safety outputs when a safety-critical fault is detected. Recovery from this condition requires all faults to be remedied and a system reset to be performed. A lockout will recur after a system reset unless the fault that caused the lockout has been corrected. The reset device (a button or switch) connects to a dedicated input terminal on the Safety Controller, labeled SR. The reset signal type can be configured to be either monitored (default) or non-monitored (see Reset Signal Requirements on page 32). WARNING: Non-Monitored Resets If a non-monitored reset (either latch or system reset) is configured and if all other conditions for a reset are in place, a short from the Reset terminal to +24 V will turn On the safety output(s) immediately. WARNING: Check Before Reset When performing the system reset operation, it is the user’s responsibility to make sure that all potential hazards are clear and free of people and unwanted materials (such as tools) that could be exposed to the hazard. Failure to do so may result in serious bodily injury or death.

7.6 Reset Signal Requirements Both manual (latch) reset and system reset signals can be configured for monitored or non-monitored operation, as follows: Monitored reset: Requires the reset signal to transition from low (0 V dc) to high (24 V dc) and then back to low. The high state duration must be 0.3 to 2 seconds. This is called a trailing edge event. Non-monitored reset: Requires only that the reset signal transitions from low (0 V dc) to high (24 V dc) and stays high for at least 0.3 seconds. After the reset, the reset signal can be either high or low. This is called a leading-edge event.

www.bannerengineering.com - Tel: 763.544.3164

71