The text of a manual · part 11 of 18
SC22-3/-3E Safety Controller Instruction Manual: 8 System Checkout
Pages 72 to 78 of 122, from SC22-3/-3E Safety Controller Instruction Manual
The original document is the PDF (6.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Banner SC22-3E
Page 72
SC22-3/-3E Safety Controller Instruction Manual
8 System Checkout 8.1 Schedule of Required Checkouts Verifying the configuration and proper functioning of the Safety Controller includes checking each safety and non-safety input device, along with each output device. As the inputs are individually switched from the Run state to the Stop state, the safety outputs must be validated that they turn On and Off as expected. WARNING: Do Not Use Machine Until System Is Working Properly If all of these checks cannot be verified, do not attempt to use the safety system that includes the Banner device and the guarded machine until the defect or problem has been corrected. Attempts to use the guarded machine under such conditions may result in serious bodily injury or death. A comprehensive test must be used to verify the operation of the Safety Controller and the functionality of the intended configuration. Initial Setup, Commissioning and Periodic Checkout Procedures on page 73 is intended to assist in developing a customized (configuration-specific) checklist for each application. This customized checklist must be made available to maintenance personnel for commissioning and periodic checkouts. A similar, simplified daily checkout checklist should be made for the operator (or Designated Person6). It is highly recommended to have copies of the wiring and logic diagrams and the configuration summary available to assist in the checkout procedures. WARNING: Periodic Checkouts The commissioning, periodic and daily safety system checks must be performed by appropriate personnel at the appropriate times (as described in this manual) in order to ensure that the safety system is operating as intended. Failure to perform these checks may create a potentially dangerous situation which could lead to serious injury or death. Commissioning Checkout: A Qualified Person6 must perform a safety system commissioning procedure before the safeguarded machine application is placed into service and after each Safety Controller configuration is created or modified. Periodic (Semi-Annual) Checkout: A Qualified Person6 must also perform a safety system re-commissioning semiannually (every 6 months) or at periodic intervals based on the appropriate local or national regulations. Daily Operational Checks: A Designated Person6 must also check the effectiveness of the protective devices per the device manufacturers’ recommendation each day that the safeguarded machine is in service. WARNING: Before Applying Power to the Machine Verify that the guarded area is clear of personnel and unwanted materials (such as tools) before applying power to the guarded machine. Failure to do so may result in serious bodily injury or death.
8.2 Commissioning Checkout Procedure Before proceeding, verify that: • •
The safety output terminal strip is not connected to the Safety Controller; unplug the 7-pin connector so that the safety outputs SO1 (A and B), SO2 (A and B) and SO3 (A and B) are not connected to the machine) Power has been removed from the machine, and no power is available to the machine controls or actuators
Permanent connections are made at a later point.
8.2.1 Verifying System Operation The commissioning checkout procedure must be performed by a Qualified Person7. It must be performed only after configuring the Controller and after properly installing and configuring the safety systems and safeguarding devices connected to its inputs (see Input Device and Safety Category Reference on page 86 and the appropriate standards). The commissioning checkout procedure is performed on two occasions: 1. When the Controller is first installed, to ensure proper installation 6 See Glossary on page 120 for definitions. 7 See Glossary on page 120 for definitions.
72 www.bannerengineering.com - Tel: 763.544.3164
Page 73
SC22-3/-3E Safety Controller Instruction Manual 2. Whenever any maintenance or modification is performed on the System or on the machine being guarded by the System, to ensure continued proper Controller function (see Schedule of Required Checkouts on page 72) For the initial part of the commissioning checkout, the Controller and associated safety systems must be checked without power being available to the guarded machine. Final interface connections to the guarded machine cannot take place until these systems have been checked out. Verify that: • •
• •
The Safety Output leads are isolated - not shorted together, and not shorted to power or ground If used, the external device monitoring (EDM) connections have been connected to +24 V dc via the N.C. monitoring contacts of the device(s) connected to the safety outputs, as described in External Device Monitoring (EDM) on page 37 and the wiring diagrams The proper Controller configuration file for your application has been installed into the Safety Controller All connections have been made according to the appropriate sections and comply with NEC and local wiring codes
This procedure allows the Controller and the associated safety systems to be checked out, by themselves, before permanent connections are made to the guarded machine.
Figure 51. Safety Output terminal block
8.3 Initial Setup, Commissioning and Periodic Checkout Procedures
NOTE: If any of the status outputs are mapped to functions within the configuration, monitor the function of each status output as the associated operation is tested. 1. Make sure that the indicators for indicators for the safety outputs (SO1, SO2, and SO3) of the Safety Controller and for the associated output devices can be observed and verified to operate correctly and without a risk of injury. Do not apply power to the Safety Controller or to the guarded machine. 2. Safety System and Safeguarding Device Checkout a. Verify that the guarded machine is compatible with this safeguarding system, as described in section Appropriate Application on page 25. b. Verify the installation and perform the checkout procedures for the external safety/safeguarding systems and devices connected to the Safety Controller inputs as described by the appropriate manuals. Do not proceed until all checkout procedures are completed successfully and all problems have been corrected. c. Verify that: • Access to any dangerous parts of the guarded machine is not possible from any direction not protected by the safeguarding system, hard (fixed) guarding, or supplemental safeguarding • Supplemental safeguarding and hard (fixed) guarding, as described by the appropriate safety standards, are in place and functioning properly d. Verify that all Reset switches are mounted outside and in full view of the guarded area, out of reach of anyone inside the guarded area, and the means of preventing inadvertent use are in place. e. Examine the electrical wiring connections between the Safety Controller’s OSSD outputs and the guarded machine’s control elements to verify that the wiring meets the requirements stated in External Device Monitoring (EDM) on page 37. 3. Verify that all Two-Hand Control devices, enabling devices, muting sensors, and bypass switches are in the inactive (Stop) state.
NOTE: In all cases, outputs associated with a Two-Hand Control or a Bypass device should not turn on at power-up. In addition, bypass or enabling devices in the active (Run) state at powerup will not function until they are seen as Off first. 4. Ensure that all other input devices are in the active (Run) state. 5. Power-Up and Reset Functions: a. Ensure that no individual is exposed to the hazardous motion/situation of the guarded machine during the checkout procedure. Observe the SO status indicators or the messages on the front panel display to verify whether a safety output is On or Off.
www.bannerengineering.com - Tel: 763.544.3164
73
Page 74
SC22-3/-3E Safety Controller Instruction Manual b. Apply power to the Safety Controller and all input devices that require power, but not to the guarded machine. c. Verify that the configuration file is appropriate for the application. At a minimum, have a copy of the Configuration Summary from the PC Interface software available for reference during the checkout procedure. d. Verify that status outputs configured for a monitored mute lamp (if used) turn on after power-up. 6. Power-Up Configuration (see “System Settings” in the Configuration Summary). In all cases, safety outputs associated with a Two-Hand Control do not turn on at power-up. Enabling devices and bypass functions are not available at power-up, they must begin in a Stop state (Off): • If configured for Normal Power-Up (default): Verify that safety outputs associated only with device inputs configured for automatic reset turn on • If configured for Automatic Power-Up: Verify that all safety outputs turn on within 5 seconds (outputs with a configured On-delay may extend this time) • If configured for Manual Power-Up: 1. Verify that all safety outputs remain Off. 2. Wait at least 10 seconds after power-up and then apply a system reset. 3. Verify that safety outputs turn on, even if an associated non-safety input is configured for a manual reset. 7. Reset Configuration • If configured for Automatic Reset: Verify that the corresponding Safety Output indicator is On Green, indicating that the safety output(s) is On (assuming that other inputs configured for manual reset are not associated with the safety output). If a Red status indicator begins to flash at any time, refer to Troubleshooting on page 79 for more information. • If configured for Manual Reset: Verify that the Green status LED is flashing to indicate that a reset is being requested, and that the message “Reset Needed” appears on the Diagnostic Display. If the Red status indicator begins to flash at any time, refer to Troubleshooting on page 79 for more information.
NOTE: If a monitored manual reset has been configured, perform a reset by closing the Reset input for at least ¼ second, but not longer than 2 seconds, and then reopening the contact. Verify that the Green status indicator comes On steady. a. Verify that all reset switches are: • Mounted in full view of the guarded area • Outside of the guarded area • Out of reach of anyone inside the guarded area • Protected from inadvertent use b. Actuate each (non-safety input) manual reset device to turn on remaining outputs not associated with a Two-Hand Control device. c. Verify that all safety outputs not associated with Two-Hand Control devices are now On. Exception: An output associated only with an enabling device will remain Off. If a particular function or device is not part of the application, skip that step and proceed to the next check or to the final step. 8. Two-Hand Control Functions a. Make sure that all inputs are in the On-state associated with safety outputs and activate each Two-Hand Control device to turn On the remaining outputs. b. Verify that the associated safety output remains Off unless both hand controls are activated within 0.5 seconds of each other. c. Verify that when one hand is removed and replaced, the safety output turns Off and remains Off. 9. Emergency Stop and Rope-Pull Functions a. While the outputs are on, individually actuate and re-arm each E-stop and/or rope-pull device, one device at a time. b. Verify that each associated safety output turns Off with the proper Off-delay, where applicable. c. As the E-stop or rope-pull device is returned to the Run state (armed): • If configured for Manual Reset or if associated with a Two-Hand Control device: verify that the safety output remains Off • If configured for Automatic Reset (assuming that another device is not holding it Off): verify that the safety output turns On 10. Apply a manual reset and/or activate the Two-Hand Control device as necessary to turn the output(s) back On. 11. Verify that each associated safety output turns On with the proper On-delay, where applicable. 12. Other Stopping Device Functions. Repeat the preceding three steps for each device type below, as applicable: a. Verify operation of all gate switches. b. Verify operation of all optical sensors. 74 www.bannerengineering.com - Tel: 763.544.3164
Page 75
SC22-3/-3E Safety Controller Instruction Manual c. Verify operation of all protective stops (for example, other safety/safeguarding devices not listed). d. Verify operation of all On/Off inputs. If Mute, Bypass and/or Enabling Device functions are not used, proceed to the final step in this procedure. 13. Mute Functions a. While the outputs are On, initiate a mute cycle by activating the mute enable input (if used) and then activate each mute sensor of a pair within 3 seconds. b. Verify that the mute lamp, if used, turns On. c. Generate a stop command from the safeguarding device that has been muted. a. Verify that the associated safety outputs remain On (Green status indicator remains On). b. If a time limit (backdoor timer) is associated with the mute, verify that the associated safety outputs turn Off when the mute timer expires. d. Repeat above steps for each muting sensor pair. e. Verify proper operation with each associated muted device f. Generate a stop command from the non-muted safeguarding device(s), one at a time. g. Verify that the associated safety outputs turn Off while the input is muted.
NOTE: The mute function will end when an associated output turns Off for any reason. In order to complete this test with the other non-muted safeguarding devices, a new mute cycle must be initiated for each one. 14. Directional Muting Option a. If 2 Mute Sensor Pairs have been configured and mapped to a mutable safety input, such as light screen, a setting of the mutable safety input in the PC Interface provides the option for Directional Muting. Check the "Enable directional muting" box in the PC Interface. Select sensor pair 1. Verify that all mute sensors and the light screen are clear, and the safety outputs are On. Block sensor pair 1 (the one selected in the PC Interface), followed by the light screen, and sensor pair 2. Verify, that the mute lamp, if used, turns On. If a time limit (backdoor timer) is associated with the mute, verify that the associated safety outputs turn Off when the mute timer expires. f. Repeat the test in the wrong direction (mute sensor pair 2, then the light screen, then mute sensor pair 1), and verify that the mute does not take place: the safety output(s) turn(s) Off as soon as the light screen is blocked. g. Repeat the steps above for all devices with directional muting. h. Mute an input device that is configured for directional muting. i. While the safety output(s) are On, generate a Stop command from a non-muted safeguarding device(s) mapped to the same safety output(s). j. Verify that the associated safety output(s) turns Off, even though an input is muted. 15. Mute on Power-Up Option b. c. d. e.
a. Turn the Safety Controller power Off. a. Activate the mute enable inputs (if used). b. Activate an appropriate muting sensor pair for starting a mute cycle. c. Ensure all input devices are in their Run (active) state (not including Two-Hand Control devices). d. Verify that all enabling devices and bypass switches are in the Stop (inactive) state. b. Verify proper operation at power-up.
NOTE: In all cases, safety outputs associated with a Two-Hand Control device will not turn On at power-up. The Mute on Power-Up feature does not apply to mutable TwoHand Control devices. •
If configured for Auto Power-Up:
•
1. Verify that all safety outputs turn On. 2. Verify that the mute status output (if used) turns On. If configured for Normal Power-Up:
•
1. Verify that all safety outputs associated with only auto-reset devices or mutable manualreset devices turn On. 2. Verify that the mute status output (if used) turns On. If configured for Manual Power-Up: 1. Verify that all safety outputs remain Off. www.bannerengineering.com - Tel: 763.544.3164
75
Page 76
SC22-3/-3E Safety Controller Instruction Manual 2. Wait at least 10 seconds after power-up and apply a system reset. 3. Verify that all safety outputs turn On. 4. Verify that the mute status output (if used) turns On. c. Generate a stop command from the safeguarding device that has been muted. Verify that the associated safety outputs remain On (for example, the input is muted); the Green status indicator should remain On. 16. Mute-Dependent Override Option a. Select Enable Mute-Dependent Override Function (default) for a bypass input. b. Clear all mute sensors and the light screen. c. Verify that the safety output(s) are On. d. Block the light screen. e. Verify that the safety output(s) turn Off. f. Block one of the mute sensors. g. Start the bypass by closing the bypass input. h. Verify that the safety output(s) turn On. i. Clear the light screen and all mute sensors. j. Verify that the safety output(s) remain On. k. Open the bypass input. l. Verify that the safety output(s) remain On. 17. Bypass Function (with Mute) a. Verify that each safety input, if it is both mutable and can be bypassed, is in the Stop state. If the Safety Controller is still muting, the associated safety outputs should remain On. Even if the timer expires and the outputs turn Off, go to the next step. b. Activate one or both mute sensors in a mute sensor pair. If there are two mute sensor pairs, at least one sensor in one of the pairs must be activated. Verify that the mute lamp, if used, is flashing. c. Verify that when the bypass switch is in the Run state: • The associated safety outputs turn On. • The mute lamp, if used, is now steady On. • The associated safety outputs turn Off when the bypass timer expires. d. Verify that when the bypass switch is in Stop state and goes back into Run state: The associated safety outputs turn On. e. Verify that when all other non-bypassed inputs associated with the same output are in a Stop state, one at a time: The associated safety outputs turn OFF while the input is bypassed. 18. Safety Mat Device Checkout Before connecting the mat to the Safety Controller, verify that the mat and the wiring to the mat does not exceed the maximum resistance specification: 1. Measure the resistance between wires connected to the same surface of the mat (see diagram): W1 and W2:______A______ ohms W3 and W4:______B______ ohms
W1
W2
W3
W4
2. While stepping on the mat, measure the resistance between W1 and W3. Repeat the measurement while stepping in various locations around the mat. Choose the location with the highest reading and record the following measurements: W1 and W3:______C______ ohms W2 and W4:______D______ ohms W2 and W3:______E______ ohms W1 and W4:______F______ ohms 3. If all measurements (A through F) are less than 20 ohms, the mat and leadwire resistance is acceptable and no further calculations are needed. 4. If A and B are both less than 300 ohms, the leadwire resistance is acceptable. 5. Calculate the mat resistance: R = E + F - ( A + B + C + D ) / 2 6. If R < 20 ohms, the mat resistance is acceptable. 76 www.bannerengineering.com - Tel: 763.544.3164
Page 77
SC22-3/-3E Safety Controller Instruction Manual 19. Bypass Function (without Mute) a. Verify that when the safety input to be bypassed is in the Stop state: The associated safety outputs are Off. b. Verify that when the bypass input is in the Run state: • The associated safety outputs turn On. • The associated safety outputs turn Off when the bypass timer (backdoor timer) expires. c. Verify that when the bypass switch is in the Stop state and goes back into the Run state: The associated safety outputs turn On. d. Generate a stop command from the non-bypassed safeguarding device(s), one at a time. Verify that the associated safety output(s) turns Off while the input is bypassed. 20. Cancel OFF-delay Function a. Configure a delayed output and check the box "Allow output to remain ON when off delay is cancelled" in the Advanced Setting menu. Turn the delayed output ON. Start the delay time by generating a stop command from a safety input, mapped to the delayed safety output. • If the safety input is a latch input, perform the following steps:
•
1. Close the safety input. 2. Push the Reset button. 3. Activate the Cancel Delay Input. If the safety input is a trip input, perform the following steps:
1. Close the safety input. 2. Activate the Cancel Delay Input. b. Verify that the delayed safety output stays closed, after the delay time has expired. c. Configure a delayed output and do not check the box "Allow output to remain On when off delay is cancelled" (turn the output Off immediately after a Cancel Off-Delay signal) in the Advanced Setting menu. d. Turn the delayed output On. e. Start the delay time by generating a stop command from a safety input, mapped to the delayed safety output. f. Close the safety input again during the Off-delay time. • If the safety input is configured for manual reset: Verify that the delayed output turns Off immediately and remains Off (a reset signal during the delay time is ignored). • If the safety input is configured for auto reset: Verify that the delayed safety output turns Off immediately for 500 ms, then turns back On. 21. Enabling Device Function a. Verify that all inputs associated with the same output as the enabling device are in the Run state to turn the output(s) On. The enabling device is to remain in the Stop state. Verify that the associated safety outputs are On. b. Verify that when the enabling device is in the Run state: The associated safety outputs remain On and the LCD displays ENABLE MODE. c. Verify that when the enabling device is in the Stop state: The associated safety outputs turn Off. d. Verify that when the enabling device is in the Run state: a. The associated safety outputs turn On. b. The associated safety outputs turn Off when the enabling device timer expires. e. Verify that when the enabling device is in the Stop state and goes back into the Run state: The associated safety outputs turn On. f. Verify that when all E-stop and rope-pull inputs associated with the same outputs are in the Stop state, one at a time (repeat step for each device, as needed): The associated safety outputs turn Off while in Enable mode. g. Verify that the enabling device is in the Stop state and then apply a system reset. a. Verify that the LCD no longer displays ENABLE MODE. b. Verify that the Safety Controller is back to normal operation. 22. System (Final) Checkout
WARNING: Do not continue checkout until all problems are corrected. The operation of the Safety Controller with the guarded machine must now be verified before the combined system may be put into service. To do this, a Qualified Person must perform the following checks. Remove power from the Safety Controller. Reinstall the safety output terminal strip to the Safety Controller. This is a permanent connection. a. Verify that all wiring complies with NEC and local wiring codes. b. Apply power to the guarded machine and verify that the machine does not start up. www.bannerengineering.com - Tel: 763.544.3164
77
Page 78
SC22-3/-3E Safety Controller Instruction Manual c. Apply power to the Safety Controller and apply resets as needed to turn the safety outputs On. d. Generate a stop command from each of the safety devices or safeguards connected to the input terminals of the Safety Controller and verify for each input device that: a. The safety outputs and status outputs operate as expected (for example, On-delays, Off-delays, etc.). Use the configuration summary to verify operation. b. It is not possible for the guarded machine to be put into motion. e. Initiate machine motion of the guarded machine and, while it is moving, generate a stop command from each of the safety devices or safeguards. Do not attempt to insert anything into the dangerous parts of the machine. Upon issuing the stop command, verify that the dangerous parts of the machine come to a stop. f. Upon reset of the safety device or safeguard and/or the Controller, verify that the machine does not automatically restart, and that the initiation devices must be engaged to restart the machine. g. Test the machine stopping response time, using an instrument designed for that purpose, to verify that it is the same or less than the overall system response time specified by the machine manufacturer. A Banner Applications Engineer may be able to recommend a suitable instrument. Important: If any of these checks fail, do not attempt to use the system until the reason for the failure(s) is identified and corrected.
78 www.bannerengineering.com - Tel: 763.544.3164