SC22-3/-3E Safety Controller Instruction Manual: 9 Troubleshooting
Pages 79 to 85 of 122, from SC22-3/-3E Safety Controller Instruction Manual
The original document is the PDF (6.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Banner SC22-3E
Page 79
SC22-3/-3E Safety Controller Instruction Manual
9 Troubleshooting 9.1 Cleaning Disconnect power to the Controller. Wipe down the polycarbonate enclosure and the display with a soft cloth that has been dampened with a mild detergent and warm water solution.
9.2 Repairs and Warranty Service The Controller is designed and tested to be highly resistant to a wide variety of electrical noise sources that are found in industrial settings. However, intense electrical noise sources that produce EMI or RFI beyond these limits may cause a random trip or lockout condition. If random trips or lockouts occur, check that: • The supply voltage is within 24 V dc ± 20% • The Safety Controller’s plug-on terminal blocks are fully inserted • Wire connections to each individual terminal are secure • No high-voltage or high-frequency noise sources or any high-voltage power lines are routed near the Controller or alongside wires that are connected to the Controller • Proper transient suppression is applied across the output loads Contact Banner Engineering for troubleshooting of this device. Do not attempt any repairs to this Banner device; it contains no field-replaceable parts or components. If the device, device part, or device component is determined to be defective by a Banner Applications Engineer, they will advise you of Banner's RMA (Return Merchandise Authorization) procedure. Important: If instructed to return the device, pack it with care. Damage that occurs in return shipping is not covered by warranty.
9.3 Finding and Fixing Faults Depending on the configuration, the Safety Controller is able to detect a number of input, output, and system faults, including: • • • • • • • • •
A stuck contact An open contact A short between channels A short to ground A short to a voltage source A short to another input A loose or open connection An exceeded operational time limit A power drop
When a fault is detected, a message describing the fault displays in the Fault Diagnostics menu. An additional message may also be displayed to help remedy the fault. The following troubleshooting table summarizes the faults and suggests additional checks to find the cause of the problem. The following sections describe how to recover from a lockout and how to access fault information, using either the PC Interface or the Onboard Interface. A network user’s guide, available on www.bannerengineering.com, may be helpful if a problem with network communications occurs.
9.3.1 Fault Code Table Fault Code 0.0
Displayed Message Input Fault
Additional Message Cycle Input
Further Steps and Checks • •
Check for unstable input signal Turn input OFF to clear the fault indication www.bannerengineering.com - Tel: 763.544.3164
79
Page 80
SC22-3/-3E Safety Controller Instruction Manual
Fault Code
1.1
Displayed Message
Output Fault
Additional Message
Further Steps and Checks
Check for Shorts
A safety output appears ON when it should be OFF. • Check for short to external voltage source • Check the DC common wire size connected to the safety output loads. The wire must be a heavy-gauge wire or be as short as possible to minimize resistance and voltage drop. If necessary, use a separate DC common wire for each pair of outputs and/or avoid sharing this DC common return path with other devices (see Common Wire Installation on page 46)
Check for Shorts
A safety output is sensing a fault to another voltage source while the output is ON. • Check for short between safety outputs • Check for short to external voltage source • Check load device compatibility (too much capacitance?) • Check the DC common wire size connected to the safety output loads. The wire must be a heavy-gauge wire or be as short as possible to minimize resistance and voltage drop. If necessary, use a separate DC common wire for each pair of outputs and/or avoid sharing this DC common return path with other devices (see Common Wire Installation on page 46)
1.2
Output Fault
1.3 – 1.4
Internal Fault
Internal failure – Contact Banner Factory (see Repairs and Warranty Service on page 79)
1.5
Output Fault
A safety output appears ON prematurely. • Check the DC common wire size connected to the safety output loads. The wire must be a heavy-gauge wire or be as short as possible to minimize resistance and voltage drop. If necessary, use a separate DC common wire for each pair of outputs and/or avoid sharing this DC common return path with other devices (see Common Wire Installation on page 46)
1.6
Internal Fault
Internal failure – Contact Banner Engineering (see Repairs and Warranty Service on page 79)
1.7
Output Fault
An overload is detected on the safety outputs . • Check each output terminal for a short to ground or overload condition (a fault on only one output may cause other outputs to indicate a fault) • Verify system power supply rating with system load requirements
1.8
Internal Fault
Internal failure – Contact Banner Factory (see Repairs and Warranty Service on page 79)
AVM Input Fault
Perform System Reset
After this safety output turned OFF, an AVM input associated with this output did not close before its AVM monitoring time expired. • The AVM may be disconnected or its response to the safety output turning OFF may be too slow • Check the AVM input and then perform a System Reset to clear the fault
Perform System Reset
An AVM input associated with this safety output was not closed when the safety output was commanded to turn ON. • The AVM may be disconnected; check the wiring • Perform a System Reset to clear the fault and cause another test to occur
Cycle Input
On a dual-channel input with both inputs in the Run state, one input went to the Stop state then back to Run. • Check the wiring • Check the input signals • Consider adjusting the debounce times
Cycle Input
On a dual-channel input, one input went into the Run state but the other input did not follow within 3 seconds. • Check the wiring • Check the input signal timing
1.9
1.10
AVM Input Fault
2.1
Concurrency Fault
2.2
Simultaneity Fault
80
Check Output Wiring
Check for Shorts www.bannerengineering.com - Tel: 763.544.3164
Page 81
SC22-3/-3E Safety Controller Instruction Manual
Fault Code
Displayed Message
Additional Message
Further Steps and Checks
Cycle Input
On a complementary pair with both inputs in the Run state, one of the inputs changed to Stop then back to Run • Check the wiring • Check the input signals • Check the power supply providing input signals • Consider adjusting the debounce times
Simultaneity Fault
Cycle Input
On a complementary pair, one input went into the Run state but the other input did not follow within the time limit. • Check the wiring • Check the input signal timing
2.7
Internal Fault
Check Terminal xx
Internal failure – Contact Banner Engineering (see Repairs and Warranty Service on page 79).
2.8 – 2.9
Input Fault
Check Terminal xx
Input stuck high. • Check for shorts to other inputs or other voltage source • Check the input device compatibility
2.10
Input Fault
Check Terminal xx
•
Check for a short between inputs
2.11 2.12
Input Fault
Check Terminal xx
•
Check for a short to ground
2.13
Input Fault
Check Terminal xx
Input stuck low. • Check for a short to ground
2.14
Input Fault
Check Terminal xx
Missing test pulses. • Check for a short to other inputs or other voltage source
2.15
Open Lead
Check Terminal xx
2.16 – 2.18
Input Fault
Check Terminal xx
2.19
Open Lead
Check Terminal xx
2.20
Input Fault
Check Terminal xx
2.21
Open Lead
Check Terminal xx
•
Check for an open lead
2.22 – 2.23
Input Fault
Check Terminal xx
•
Check for an unstable signal on the input
2.24
Input Activated While Bypassed
Perform System Reset
2.3 or 2.5
Concurrency Fault
2.4 or 2.6
•
Missing test pulses. • Check for shorts to other inputs or other voltage source •
Input Fault
Check for an open lead
Missing test pulses • Check for a short to ground
A two-hand control input was activated (turned ON) while it was bypassed.
Monitoring 2.25
Check for an open lead
Timer Expired Before AVM Closed
2.26
Input Fault
AVM Not Closed When Output Turned ON
3.1
EDMxx Fault
Check Terminal xx
After the associated safety output turned OFF, the AVM input did not close before its AVM monitoring time expired. • Either the AVM is disconnected, or its response to the safety output turning OFF is too slow • Check the wiring to the AVM • Check the timing setting; increase the setting if necessary • Contact Banner Engineering The AVM input was open, but should have been closed, when the associated safety output was commanded ON. • The AVM may be disconnected; check the wiring to the AVM EDM contact open prior to turning ON the safety outputs. • Check for a stuck-ON contactor or relay • Check for an open wire www.bannerengineering.com - Tel: 763.544.3164
81
Page 82
SC22-3/-3E Safety Controller Instruction Manual
Fault Code
Displayed Message
Additional Message
Further Steps and Checks EDM contact(s) failed to close within 250 ms after the safety outputs turned OFF. • Check for a slow or stuck-ON contactor or relay • Check for an open wire
3.2
EDMxx Fault
Check Terminal xx
3.3
EDMxx Fault
Check Terminal xx
EDM contact(s) open prior to turning ON the safety outputs. • Check for a stuck-ON contactor or relay • Check for an open wire
3.4
EDMxx Fault
Check Terminal xx
EDM contact pair mismatched for longer than 250 ms. • Check for a slow or stuck-ON contactor or relay • Check for an open wire
3.5
EDMxx Fault
Check Terminal xx
•
Check for an unstable signal on the input
3.6
EDMxx Fault
Check Terminal xx
•
Check for a short to ground
3.7
EDMxx Fault
Check Terminal xx
•
Check for shorts between inputs
4.1
Supply Voltage Low
Check Power Supply
The supply voltage dropped below the rated voltage for longer than 6 ms. • Check the power supply voltage and current rating • Check for an overload on the outputs that might cause the power supply to limit the current
4.2
Internal Fault
A configuration parameter has become corrupt. To fix the configuration: • Replace the configuration by sending a backup copy of the configuration using the PC Interface or an XM card • Or, erase and recreate the configuration using the on-board user interface
4.3 – 4.11
Internal Fault
Internal failure – Contact Banner Engineeing (see Repairs and Warranty Service on page 79).
4.12
Configuration Timeout
Check Configuration
Safety Controller was left in Configuration mode for more than one hour without pressing any keys.
4.13
Configuration Timeout
Check Configuration
Safety Controller was left in Configuration mode for more than one hour without receiving any commands from the PC Interface.
4.14
Configuration Unconfirmed
Confirm Configuration
Configuration was not confirmed after being edited. • Confirm configuration using the Onboard Interface or the PC Interface
4.15 – 4.19
Internal Fault
4.20
Unassigned Terminal in Use
4.21 – 4.33
Internal Fault
5.1
Mute Lamp Fault
Check Lamp and Wiring
The monitored status output voltage should be low when the lamp is OFF and is sensing a high, indicating an open in the mute lamp circuit.
5.2
Mute Lamp Fault
Check for Shorts
The monitored status output voltage should be high when the lamp is ON and is sensing a low, indicating a short in the mute lamp circuit.
5.3
Internal Fault
Internal failure – Contact Banner Engineering (see Repairs and Warranty Service on page 79).
6.xx
Internal Fault
Invalid configuration data. Possible internal failure. • Try to load a new configuration using the PC Interface, Onboard Interface, or XM card
82
Internal failure – Contact Banner Factory (see Repairs and Warranty Service on page 79) Check Terminal xx
This terminal is not mapped to any device in the present configuration and should not be active. • Check the wiring Internal failure – Contact Banner Engineering (see Repairs and Warranty Service on page 79).
www.bannerengineering.com - Tel: 763.544.3164
Page 83
SC22-3/-3E Safety Controller Instruction Manual
9.4 Recovering from a Lockout To recover from a lockout condition: • Follow the recommendation in the fault display • Follow the recommended steps and checks listed in the Fault Code Table on page 79 • Perform a system reset • Cycle the power and perform a system reset, if needed If these steps do not remedy the lockout condition, contact Banner Engineering (see Repairs and Warranty Service on page 79).
9.5 Fault Diagnostics The first step in diagnosing faults via the PCI is to open the Live Display screen (see Display Controller Information, PC Interface (PCI) on page 68). The Live Display screen shows in real time, the status of each safety output, which device caused an output to turn off, if any, and basic information about the Safety Controller model and the configuration.
9.5.1 Fault Log - PCI While the Controller is powered up and connected to the PC, every fault that occurs is stored in the fault log. The PCI displays real-time fault information via the Fault Log screen shown in the following figure. The fault information includes the following information about each fault; expand the size of the window as needed to see all the faults. • • • •
Date and time of the fault Device name General description of the fault, and Fault code (for lookup table reference).
Additional code information can be displayed, should factory applications assistance be required. Saves the displayed faults to a file for later reference.
Clears the faults displayed and gets the latest faults stored in the Safety Controller’s fault log.
Figure 52. Fault Log screen - PCI
9.5.2 Fault Log Recording - PCI To determine the cause of a persistent fault, compile an extended record of the faults and save it to a file. Select Edit in the Fault Log screen to establish the times at which the fault data record starts and stops. The Schedule Fault Log Capture menu will then appear. The menu settings at right show that any fault that occurs from Friday, June 29, 2007 at 11:00 pm until Saturday, June 30, 2007 at 6:00 am will be recorded to a user-designated file for future reference. Figure 53. Schedule Fault Log Capture menu
NOTE: The selected start and stop times must be later than the time at which this selection is made; the fault log capture will not capture past faults.
www.bannerengineering.com - Tel: 763.544.3164
83
Page 84
SC22-3/-3E Safety Controller Instruction Manual
9.6 Fault Diagnostics - OBI Troubleshooting the Controller and connected I/O devices is easy using the Onboard Interface. Any event that causes a safety output to turn OFF or stay OFF (either for fault or input stop events) will be immediately detected and displayed on the Controller’s display. Further information about current and past faults can be accessed using the Fault Diagnostics menu. To get to the Fault Diagnostics menu, press OK from the Run mode menu. Select Fault Diagnostics and press OK. The Diagnostics menu provides three choices: • View fault conditions that currently exist • View faults that have been stored in the fault log • Clear the fault log
Figure 54. Select Fault Diagnostics - OBI
9.6.1 View Current Faults - OBI To view current fault conditions, select View Current Faults using the up/down arrow buttons and press OK. The screen shows the fault conditions that currently exist, one at a time. Use the left/right arrow keys to view all of the faults. (Shortcut: To view current faults when the Run mode screen is displayed, simply press OK three times.) Figure 55. View current faults - OBI
• • • •
The top line of the Current Fault menu indicates which device has the fault The second and third lines provide a brief description of the fault The fourth line provides a suggestion for correcting the fault The fifth line provides the fault code. Use the Fault Code Table on page 79 to obtain more information about the fault and additional suggestions for correcting it
Use the left and right arrows (< and >) buttons to access fault information for all faulty devices.
Arrowheads designate location of additional fault screens Device Name Fault Description Suggested Remedy Fault Code Figure 56. Current Fault screens - OBI
9.6.2 View Fault Log - OBI The Safety Controller keeps a record of the last ten faults that have occurred. The faults are viewable from the View Fault Log menu. To view the fault log, select View Fault Log in the Diagnostics menu and press OK. The screen shows the first fault stored in the fault log. Use the left/right arrow keys to view additional faults in the fault log. • The top line of the fault log screen indicates which device had the fault • The second and third lines provide a brief description of the fault
84 www.bannerengineering.com - Tel: 763.544.3164
Page 85
SC22-3/-3E Safety Controller Instruction Manual •
•
The fourth line displays how long ago the fault occurred. For instance, a time of 01:30:23 indicates the fault occurred one hour, thirty minutes, and 23 seconds previous to the View Fault Log menu’s appearance on the screen. If a fault is added to the fault log while the fault log is being viewed, the time is displayed as New Fault. If a fault is older than twenty-four hours, the time is displayed as > 24 hours The fifth line provides the fault code. Use the Fault Code Table on page 79 to obtain more information about the fault and additional suggestions for correcting it NOTE: Removing power from the Safety Controller will clear the fault log, in addition to the method described next.
Device Name Fault Description Time Since Fault Fault Code Figure 57. Fault Log screens - OBI
9.6.3 Clear Fault Log - OBI To clear the fault log, select Clear Fault from the Diagnostics menu and press OK.
Figure 58. Clearing the fault log - OBI
When the fault is cleared, press OK to return to the Fault Diagnostics menu, then press ESC twice to return to the Run mode menu.
Figure 59. Fault log is cleared - OBI www.bannerengineering.com - Tel: 763.544.3164