The text of a manual · part 13 of 18

SC22-3/-3E Safety Controller Instruction Manual: 10 Input Device and Safety Category Reference, pages 86 to 95

Pages 86 to 95 of 122, from SC22-3/-3E Safety Controller Instruction Manual

The original document is the PDF (6.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Banner SC22-3E

Page 86

SC22-3/-3E Safety Controller Instruction Manual

10 Input Device and Safety Category Reference For ease in finding information about them, the specific device types discussed are presented in the following order. Protective (Safety) Stop on page 88 Interlocked Guard or Gate on page 89 Optical Sensor on page 94 Two-Hand Control on page 96 Safety Mat on page 99 Emergency Stop Push Buttons on page 102 Rope (Cable) Pull on page 105 Enabling Device on page 106 Bypass Switches (Bypassing Safeguards) on page 108 Muting Function on page 110 Follow the device manufacturer’s installation, operation, and maintenance instructions and all relevant regulations. If there is any question about the device(s) that are to be connected to the Safety Controller, contact a Banner Applications Engineer for assistance.

10.1 Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles Safety circuits involve the safety-related functions of a machine that minimize the level of risk of harm. These safetyrelated functions can prevent initiation, or they can stop or remove a hazard. The failure of a safety-related function or its associated safety circuit usually results in an increased risk of harm. The integrity of a safety circuit depends on several factors, including fault tolerance, risk reduction, reliable and well-tried components, well-tried safety principles, and other design considerations. Depending on the level of risk associated with the machine or its operation, an appropriate level of safety circuit integrity (performance) must be incorporated into its design. Standards that detail safety performance levels include ANSI B11.19 Performance Criteria for Safeguarding and ISO 13849-1 Safety-Related Parts of a Control System.

10.1.1 Safety Circuit Integrity Levels The safety circuits in International and European standards have been segmented into categories, depending on their ability to maintain their integrity in the event of a failure. The most recognized standard that details safety circuit integrity levels is ISO 13849-1, which establishes five levels: Categories B, 1, 2, 3, and 4 (most strict). In the United States, the typical level of safety circuit integrity is called control reliability. Control reliability typically incorporates redundant control and self-checking circuitry and is relatively similar to ISO 13849-1 Categories 3 and 4 (see CSA Z432 and ANSI B11.19). Perform a risk assessment to determine the appropriate category to make sure that the expected risk reduction is achieved to implement the requirements described by ISO 13849-1. This risk assessment must also take into account the national regulations, such as U.S. control reliability or European "C" level standards, to comply with the mandated minimum levels of performance. The following sections deal only with Category 2, Category 3, and Category 4 applications, as described by ISO 13849-1 (1999). The following figure provides a snapshot of the possible safety categories that can be achieved for each device type, depending on the selected circuit option. Refer to the text sections following, as well as the appropriate standards, for further information.

86 www.bannerengineering.com - Tel: 763.544.3164

Page 87

SC22-3/-3E Safety Controller Instruction Manual

Circuit Symbol

E-Stop Safety Optical Gate Sensor

Two-Hand Control

Rope Pull

Protect. Safety Enabling Stop Mat Device

24V

Cat. 2

Cat. 2

Cat. 2, Cat. 2

Cat. 2, - Cat. 3

Cat. 2 Cat. 3

Cat. 2 Cat. 3

Type IIIa Cat. 1 Type IIIb Cat. 3

Cat. 3

Cat. 2 Cat. 3, Cat. 2 Cat. 3

Cat. 2 Cat. 3 Cat. 4

Cat. 2 Cat. 3 Cat. 4

Cat. 2 Cat. 3 Cat. 4

Type IIIa Cat. 1

Cat. 2 Cat. 3 Cat. 4

Cat. 2 Cat. 3 Cat. 4, Cat. 2 Cat. 3 Cat. 4

Cat. 4

Cat. 2 Cat. 3 Cat. 4

Cat. 2 Cat. 3 Cat. 4

Type IIIa Cat. 1 Type IIIb Cat. 3

Cat. 4

Cat. 2 Cat. 3 Cat. 4, Cat. 2 Cat. 3 Cat. 4, Cat. 2 Cat. 3 Cat. 4

Cat. 2 Cat. 3 Cat. 4, Cat. 2 Cat. 3 Cat. 4

Cat. 2 Cat. 3 Cat. 4, Cat. 2 Cat. 3 Cat. 4, Cat. 2 Cat. 3 Cat. 4

Cat. 2 Cat. 3 Cat. 4, Cat. 2 Cat. 3 Cat. 4

Cat. 2 Cat. 3 Cat. 4, Cat. 2 Cat. 3 Cat. 4, Cat. 3 Cat. 4, Type IIIc Cat. 4, - - Cat. 3 Cat. 4, Cat. 3 Cat. 4, Type IIIc Cat. 4, - - Cat. 3 Cat. 4, - - - - - Cat. 2 Cat. 3, 24V

ON

ON

24V

ON

OFF

24V

ON

OFF

ON

OFF

NOTES • Cat. B or 1 is assumed when not using safety-rated devices. • All safety input device contacts are shown in the ON/active state (for example, E-stop in the armed state, safety gate in the closed state, light screen in the clear state, etc.) • Cat. B/1, 2, 3 and 4 are per ISO 13849-1, except for two-hand control. • Two-hand categories are per ISO 13851.

Figure 60. Input devices, circuit options, and their potential safety categories

Important: Complementary (2 or 3 terminals) and Complementary (PNP device): In the actuated condition (for example, S1 closed/S2 open), a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time, see Safety Input Device Properties on page 27. WARNING: Risk Assessment The level of safety circuit integrity can be greatly affected by the design and installation of the safety devices and the means of interfacing of those devices. A risk assessment must be performed to determine the appropriate level of safety circuit integrity to ensure the expected risk reduction is achieved and all relevant regulations and standards are complied with. WARNING: Input Devices with Solid State Outputs The Safety Controller will not detect shorts between inputs or from an input to +24 V if the input signals on these terminals are coming from input devices with Solid State Outputs. The user is responsible to use a device that can detect these shorts.

www.bannerengineering.com - Tel: 763.544.3164

87

Page 88

SC22-3/-3E Safety Controller Instruction Manual

WARNING: Category 2 or 3 Input Shorts Detection of a short between two input channels (contact inputs, but not complementary contacts), if they are supplied through the same source (for example, the same terminal from the Controller in a dual-channel, 3-terminal hookup, or from an external 24 V supply) is not possible, if the two contacts are closed. Such a short can be detected only when both of the contacts are open and the short is present for at least 2 seconds.

10.1.2 Fault Exclusion An important concept within the requirements of ISO 13849-1 is the probability of the occurrence of a failure, which can be reduced using a technique termed "fault exclusion." The rationale assumes that the possibility of certain well-defined failure(s) can be reduced via design, installation, or technical improbability to a point where the resulting fault(s) can be, for the most part, disregarded - that is, "excluded" in the evaluation. Fault exclusion is a tool a designer can use during the development of the safety-related part of the control system and the risk assessment process. Fault exclusion allows the designer to design out the possibility of various failures and justify it through the risk assessment process to meet the requirements of ISO 13849-1/-2.

10.2 Protective (Safety) Stop A Protective (Safety) Stop is designed for the connection of miscellaneous devices (not otherwise listed on the “Add Safety Device” screen) that could include safeguarding (protective) devices and complementary equipment. This stop function is a type of interruption of operation that allows an orderly cessation of motion for safeguarding purposes. The function can be reset or activated either automatically or manually.

10.2.1 Protective (Safety) Stop Requirements The required safety circuit integrity level is determined by a risk assessment and indicates the level of control performance that is acceptable, for example, category 4, Control Reliability (see Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles on page 86). The protective stop circuit must control the safeguarded hazard by causing a stop of the hazardous situation(s), and removing power from the machine actuators. This functional stop typically meets category 0 or 1 as described by ANSI NFPA 79 and IEC60204-1.

10.2.2 Protective (Safety) Stop Hookup Options The device is shown in the Off (Stop) state. Single-Channel (1 terminal, 2 terminals, or PNP device) This circuit typically meets ISO 13849-1 Category 2 requirements, depending on the safety rating and the installation of the device. At a minimum, a safety-rated device must be used to achieve Category 2. The 1terminal and the PNP device circuits cannot detect a short circuit to another source of power. The two-terminal circuit uses pulse monitoring and can detect a short circuit to another source of power. Fault Exclusion must be used to achieve a higher level of safety circuit integrity.

24V

Dual-Channel (2 or 3 terminals) This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements, depending on the safety rating and the installation of the device. The Dual Channel 3-terminal hookup uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal circuits can detect a short between channels when the contacts are open for more than 2 seconds.

88 www.bannerengineering.com - Tel: 763.544.3164

24V

OFF

Page 89

SC22-3/-3E Safety Controller Instruction Manual Dual-Channel (PNP device)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating, installation, and the fault detection (such as short circuit) capabilities of the device. The Safety Controller does not provide short circuit detection in this configuration.

OFF

OFF

OFF

ON

S1

S2

Dual-Channel (4 terminals)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels or to another source of power.

Complementary (2 or 3 terminals) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time.

24V

S1

S2

Complementary (PNP device) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

10.3 Interlocked Guard or Gate The Safety Controller safety inputs may be used to monitor electrically interlocked guards or gates.

10.3.1 Safety Circuit Integrity Levels The application requirements for interlocked guards or gates vary for the level of control reliability or safety category per ISO 13849-1. While Banner Engineering always recommends the highest level of safety in any application, the user is responsible to safely install, operate, and maintain each safety system and comply with all relevant laws and regulations. The safety performance (integrity) must reduce the risk from identified hazards as determined by the machine’s risk assessment. See Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles on page 86 for guidance if the requirements as described by ISO 13849-1 need to be implemented. In addition to the requirements stated in this section, the design and installation of the interlocking device should comply with ANSI B11.19 or ISO14119.

10.3.2 Safety Interlock Switch Requirements The following general requirements and considerations apply to the installation of interlocked guards and gates for the purpose of safeguarding. In addition, the user must refer to the relevant regulations to ensure compliance with all necessary requirements. Hazards guarded by the interlocked guard must be prevented from operating until the guard is closed; a stop command must be issued to the guarded machine if the guard opens while the hazard is present. Closing the guard must not, by itself, initiate hazardous motion; a separate procedure must be required to initiate the motion. The safety interlock switches must not be used as a mechanical or end-of-travel stop. www.bannerengineering.com - Tel: 763.544.3164

89

Page 90

SC22-3/-3E Safety Controller Instruction Manual The guard must be located an adequate distance from the danger zone (so that the hazard has time to stop before the guard is opened sufficiently to provide access to the hazard), and it must open either laterally or away from the hazard, not into the safeguarded area. The guard also should not be able to close by itself and activate the interlocking circuitry. In addition, the installation must prevent personnel from reaching over, under, around, or through the guard to the hazard. Any openings in the guard must not allow access to the hazard (see OSHA 29CFR1910.217 Table O-10, ANSI B11.19, ISO 13857, ISO14120/EN953 or the appropriate standard). The guard must be strong enough to contain hazards within the guarded area, which may be ejected, dropped, or emitted by the machine. The safety interlock switches, actuators, sensors, and magnets must be designed and installed so that they cannot be easily defeated. They must be mounted securely so that their physical position cannot shift, using reliable fasteners that require a tool to remove them. Mounting slots in the housings are for initial adjustment only; final mounting holes must be used for permanent location. WARNING: Perimeter Guarding Applications If the application may result in a pass-through hazard (for example, perimeter guarding), either the safeguarding device or the guarded machine's MSCs/MPCEs must cause a Latched response following a Stop command (for example, interruption of the sensing field of a light curtain, or opening of an interlocked gate/guard). The reset of this Latched condition may only be achieved by actuating a reset switch that is separate from the normal means of machine cycle initiation. The switch must be positioned as described in this document. Lockout/Tagout procedures per ANSI Z244.1 may be required, or additional safeguarding, as described by ANSI B11 safety requirements or other appropriate standards, must be used if a passthrough hazard cannot be eliminated or reduced to an acceptable level of risk. Failure to observe this warning may result in serious bodily injury or death.

Positive-Opening Safety Interlocking Switches Safety interlock switches must satisfy several requirements. Each switch must provide electrically isolated contacts: at minimum, one normally closed (N.C.) contact from each individually mounted switch. The contacts must have positiveopening (direct-opening) design, as described by IEC 60947-5-1, with one or more normally closed contacts rated for safety. Positive-opening operation causes the switch to be forced open, without the use of springs, when the switch actuator is disengaged or moved from its home position (visit www.bannerengineering.com for examples). In addition, the switches must be mounted in a positive mode to move/disengage the actuator from its home position and open the normally closed contact when the guard opens.

Magnetically Operated Safety Interlocking Switches In higher levels of safety performance the design of a dual-channel magnetic switch typically uses complementary switching in which one channel is open and one channel is closed at all times. This provides redundancy (two contacts) and diversity (different principles of operation) to minimize the possibility of the loss of the switching function due to common mode failures, such as secondary magnetic fields. The circuitry or the Safety Controller that is monitoring the magnetic switch detects and responds to a failure that results in the loss of the complementary state (for example, a short circuit between the channels, or a short circuit to other sources of power). Coded and non-coded magnetic switches affect the ability of the switch to be defeated and to withstand common mode failures. Non-coded switches are easily defeated by the presence of a simple magnetic field and should be mounted in a concealed position. A coded magnetic switch that uses alternating magnetic poles should be used in applications that require higher levels of safety performance. The switch and its magnet must be mounted a minimum distance from any magnetized or ferrous materials for proper operation. If either the switch or magnet is mounted on a material that can be magnetized, the switching distance will be affected. This distance is stated by the manufacturer.

Monitoring Series-Connected Safety Interlock Switches When monitoring two individually mounted safety switches (as shown in the Category 4 circuit figure), a faulty switch will be detected if it fails to switch when the guard opens. In this case, the Controller de-energizes its safety outputs (OSSDs) and disables its reset function until the input requirements are met, such as the replacement of the faulty switch. However, when multiple safety interlock switches are series-connected, the failure of one switch in the system may be masked or not be detected at all (refer to Category 3 and 4 circuit figures). Series-connected safety interlock switch circuits may not meet OSHA Control Reliability or ISO 13849 Safety Category 4 requirements because of the potential of an inappropriate reset or a potential loss of the safety stop signal. Those requirements are not met due to the typical inability to fault exclude the failure of the safety interlock switch. A multiple connection of this type should not be used in applications where loss of the safety stop signal or an

90 www.bannerengineering.com - Tel: 763.544.3164

Page 91

SC22-3/-3E Safety Controller Instruction Manual inappropriate reset can lead to serious injury or death. The following scenarios assume two positive-opening safety switches on each guard, both connected in series to switches of a second guard: 1. Masking of a failure. If a guard is opened but the switch fails to open, the redundant safety switch will open and cause the Controller to de-energize its outputs. If the faulty guard is then closed, both Controller input channels also close, but because one channel did not open, the Controller will not reset. However, if the faulty switch is not replaced and a second functional guard is cycled (opening and then closing both of the Controller’s input channels), the Controller considers the failure to be corrected. With the input requirements apparently satisfied, the Controller allows a reset. This system is no longer redundant and, if the second switch fails, may result in an unsafe condition, such as the accumulation of faults resulting in loss of the safety function. 2. Non-detection of a failure. If a functional guard is opened, the Safety Controller de-energizes its outputs (a normal response). But if then a faulty guard is opened and closed before the functional guard is re-closed, the faulty guard is not detected. This system is no longer redundant and may result in a loss of safety if the second safety switch fails to switch when needed. The systems in either scenario do not inherently comply with the safety standard requirements of detecting single faults and preventing the next cycle. It is important to periodically check the functional integrity of each interlocked guard individually in multiple-guard systems using series-connected safety interlock switches. Operators, maintenance personnel, and others associated with the operation of the machine must be trained to recognize such failures and be instructed to correct them immediately. To verify series-connected safety interlock switch functionality: Open and close each safeguard separately while verifying that the Controller outputs operate correctly throughout the check procedure. Follow each safeguard closure with a manual reset, if needed. If a contact set fails, the Controller will not enable its reset function. If the Controller does not reset, a switch may have failed; that switch must be immediately replaced. This check must be performed and all faults must be cleared, at a minimum, during periodic checkouts. Do not use the series connection of the safety interlock switches if the application cannot exclude these types of failures and such a failure could result in serious injury or death.

Series Connection and Safety Circuit Integrity Considerations Category 2 Interlocked Guard Circuit A single-channel interlocked guard application typically provides a Category 2 level of circuit performance because a short circuit could cause a loss of safety function. The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of faults that can result in a loss of the safety function.

+24V dc Open

Open

Open

Figure 61. Category 2 Interlocked Guard Circuit www.bannerengineering.com - Tel: 763.544.3164

91

Page 92

SC22-3/-3E Safety Controller Instruction Manual

Category 3 Interlocked Guard Circuit A dual-channel hookup switching +24V dc is typically a Category 3 application because a single failure does not result in a loss of safety. Loss of the switching action in one channel is detected by the actuation of opening and closing the guard, allowing the monitoring function of the safety inputs to detect the discrepancy between the channels. However, a short circuit between input channels or Safety Outputs may not be detected. It should be noted that an accumulation of faults may cause a loss of the safety function. The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of undetected faults or catastrophic or common mode failures that could result in the loss of safety function.

+24V dc Open

Open

Open

Figure 62. Category 3 Interlocked Guard Circuit

Category 4 Interlocked Guard Circuit The self-monitoring safety inputs can be interfaced to achieve a Category 4 level of safety. The principle of fault exclusion must be incorporated into the design and installation to either eliminate, or reduce to an acceptable (minimal) level of risk, the possibility of catastrophic or common mode failures that could result in loss of the safety function.

Open

Figure 63. Category 4 Interlocked Guard Circuit

Interlock Switch Hookup Options All figures show the guard (gate) in the closed (Run) state. The safety contact is considered to be the normally closed contact that is of a positive-opening design (unless otherwise noted), normally marked with the symbol.

Single-Channel (1 terminal, 2 terminals, or PNP device) This circuit typically meets ISO 13849-1 Category 2 requirements, depending on the safety rating and the installation of the device. At a minimum, a safety-rated device must be used to achieve Category 2. The 1terminal and the PNP device circuits cannot detect a short circuit to another source of power. The two-terminal circuit uses pulse monitoring and can detect a short circuit to another source of power. Fault Exclusion must be used to achieve a higher level of safety circuit integrity.

92 www.bannerengineering.com - Tel: 763.544.3164

24V

Page 93

SC22-3/-3E Safety Controller Instruction Manual Dual-Channel (2 or 3 terminals) 24V

This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements, depending on the safety rating and the installation of the device. The Dual Channel 3-terminal hookup uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal circuits can detect a short between channels when the contacts are open for more than 2 seconds.

24V

24V

A single switch mounted on a single guard is typically a Category 2 applicaton.

Two switches individually mounted on a single guard is typically a Category 3 applicaton.

Dual-Channel (PNP device) ON

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating, installation, and the fault detection (such as short circuit) capabilities of the device. The Safety Controller does not provide short circuit detection in this configuration.

ON

Dual-Channel (4 terminals)

Two switches individually mounted on a single guard is typically a Category 4 application. A series connection of switches on multiple guards is typically a Category 3 application.

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels or to another source of power. One switch mounted on a single guard is typically a Category 2 application.

Complementary (2 or 3 terminals) 24V

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

www.bannerengineering.com - Tel: 763.544.3164

24V

A single coded magnetic switch mounted on a single guard can meet Category 3 or 4 depending on installation and the frequency of exercising the guard (closedopen-closed). For more information, see the GM-FA-10J data sheet (p/n 60998).

93

Page 94

SC22-3/-3E Safety Controller Instruction Manual Complementary (PNP device) This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. See Safety Input Device Properties on page 27.

ON

OFF

S1

S2

2x Complementary (4 or 5 terminals) 24V

This circuit meets ISO 13849-1 Category 3 or Category 4 requirements depending on the safety rating and the design and installation of the enabling device. This circuit can detect a short circuit between channels. In the guard closed condition (S1 open/S2 closed), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time.

24V

Two coded magnetic switches mounted on a single guard can meet Category 4.

NOTE: Coded magnetic switches typically use this hookup option.

2x Complementary (PNP device) This circuit meets ISO 13849-1 Category 3 or Category 4 requirements depending on the safety rating design and installation of the enabling device. This circuit can detect a short circuit between channels. In the actuated condition (S1 Off/S2 On), as shown, a short across the closed contact may cause the response time to increase based on the debounce time. In this situation, the response time may be longer than specified, based on the selected debounce time. Safety Input Device Properties on page 27.

ON

OFF

ON

OFF

ON

OFF

ON

OFF

10.4 Optical Sensor The Safety Controller safety inputs may be used to monitor optical-based devices that use light as a means of detection.

10.4.1 Safety Circuit Integrity Levels The application requirements for optical safeguarding vary for the level of control reliability or safety category per ISO 13849-1. While Banner Engineering always recommends the highest level of safety in any application, the user is responsible to safely install, operate, and maintain each safety system and comply with all relevant laws and regulations. The safety performance (integrity) must reduce the risk from identified hazards as determined by the machine’s risk assessment. See Safety Circuit Integrity and ISO 13849-1 Safety Circuit Principles on page 86 for guidance if the requirements as described by ISO 13849-1 need to be implemented. In addition to the requirements stated in this section, the design and installation of the optical safeguarding device must comply with ANSI B11.19 or IEC61496 (all parts).

10.4.2 Optical Sensor Requirements When used as safeguarding, optical sensors are described by IEC61496-1/-2/-3 as Active Opto-electronic Protective Devices (AOPD) and Active Opto-electronic Protective Devices responsive to Diffuse Reflection (AOPDDR). AOPDs include safety light screens (curtains) and safety grids and points (multiple-/single-beam devices). These devices generally meet Type 2 or Type 4 design requirements; a Type 2 device is allowed to be used in a Category 2 application, per ISO 13849-1, and a Type 4 device can be used in a Category 4 application.

94 www.bannerengineering.com - Tel: 763.544.3164

Page 95

SC22-3/-3E Safety Controller Instruction Manual AOPDDRs include area or laser scanners. The primary designation for these devices is a Type 3, for use in up to Category 3 applications. WARNING: Incomplete Information - many installation considerations that are necessary to properly apply input devices are not covered in this document. Refer to the appropriate device installation instructions to ensure the safe application of the device. Optical safety devices must be placed at an appropriate safety distance (minimum distance), according to the application standards. Refer to the applicable standards and to manufacturer documentation specific to your device for the appropriate calculations. For the purpose of the calculation, the Safety Controller default response is 0.010 seconds, plus any additional closed-to-open debounce time. If the debounce time is adjusted, the time in excess of 6 ms (default closed-toopen debounce time) must be added to the stated response. See Response and Recovery Times on page 23 and Run Mode on page 61, and Onboard Interface (OBI) Overview on page 59 for instructions on accessing device-specific response times. If the application includes a pass-through hazard (a person could pass through the optical device beams and stand undetected on the hazard side), other safeguarding may be required, and manual reset should be selected (see Input Device Resets on page 31).

10.4.3 Optical Sensor Hookup Options The device is shown in the actuated, in the Normally Open (Off) state. Single-Channel (1 terminal, 2 terminals, or PNP device) This circuit typically meets ISO 13849-1 Category 2 requirements, depending on the safety rating and the installation of the device. At a minimum, a safety-rated device must be used to achieve Category 2. The 1terminal and the PNP device circuits cannot detect a short circuit to another source of power. The two-terminal circuit uses pulse monitoring and can detect a short circuit to another source of power. Fault Exclusion must be used to achieve a higher level of safety circuit integrity.

OFF

24V

Dual-Channel (2 or 3 terminals) This circuit typically meets ISO 13849-1 Category 2 or Category 3 requirements, depending on the safety rating and the installation of the device. The Dual Channel 3-terminal hookup uses pulse monitoring and can detect a short circuit to another source of power. Both 2- and 3-terminal circuits can detect a short between channels when the contacts are open for more than 2 seconds.

24V

Dual-Channel (PNP device)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements depending on the safety rating, installation, and the fault detection (such as short circuit) capabilities of the device. The Safety Controller does not provide short circuit detection in this configuration.

OFF

OFF

Dual-Channel (4 terminals)

This circuit meets ISO 13849-1 Category 2, 3, or 4 requirements, depending on the safety rating and the installation of the device. This circuit can detect a short circuit between channels or to another source of power.

www.bannerengineering.com - Tel: 763.544.3164

95